Plan Review Details - Permit 08030399
Plan Review Stops For Permit 08030399
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By rmcdouga Date 2008-04-08 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2008-04-08 Time 16:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-21 Cont ID  
Sent By rmcdouga Date 2008-03-21 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2008-03-21 Time 07:40 Sent To  
Notes
2008-03-21 10:38:472004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) ON SHEET A1 DEMO NOTE #1 SPECIFIES COMPLIANCE WITH
 THE TOWN OF PALM BEACH AMENDMENTS. PLEASE REVISE TO
 NOTE TO SPECIFY CITY OF WEST PALM BEACH AMENDMENTS. FBC
 106.1.1* CITY AMENDMENTS.
  
 3) ON SHEET S2 THE 1/2" X 10' STEEL PLATE IS SPECIFIED
 TO BE ATTACHED TO THE (2) 2 X 12 BEAM WITH (3) ROWS OF
 16D NAILS @ 6" OC STAGGERED. SECTION 2 ON S3 SPECIFIES
 THE STEEL PLATE ATTACHED WITH (2) ROWS OF 14" DIAMETER
 X 3-1/2" WOOD SCREWS @ 12" OC STAGGERED. PLEASE
 CORRECT.
  
 4) SECTION 2 ON S-4 SPECIFIES (2) 2 X 12 WITH 1/2"
 PLYWOOD BETWEEN W/2 ROWS OF 10D NAILS @ 6" OC STAGGERED
 AND SECTIONS 3 AND 4 ON S4 SPECIFY 16D NAILS. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-21 Cont ID  
Sent By btrobaug Date 2008-05-21 Time 15:31 Rev Time 0.00
Received By btrobaug Date 2008-05-21 Time 15:03 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-07 Cont ID  
Sent By btrobaug Date 2008-04-07 Time 12:52 Rev Time 0.00
Received By btrobaug Date 2008-04-07 Time 12:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By btrobaug Date 2008-03-20 Time 08:50 Rev Time 0.00
Received By btrobaug Date 2008-03-20 Time 06:54 Sent To Z
Notes
2008-03-20 08:49:59 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2004 FBC AS AMENDED, CHAPTER
 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, THE
 METER ENCLOSURE IS NOT ON THE PLAN. INDICATE IF THE
 RISER IS CORRECT SHOWING AN UNDERGROUND FEED TO THE
 EXISTING PANELS (TO CONFIRM COMPLIANCE WITH 230.70(A)
 (1)).
  
 2) THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. 250.6
 2005 NEC.
 NOTE:
 IT IS SHOWN AS AN EXISTING SERVICE BUT MUST BE
 CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE IS A
 POTENTIAL OF ENERGIZING ALL METAL PARTS AND EQUIPMENT
 THE EQUIPMENT GROUNDS ARE CONNECTED TO.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR IS SHOWN AS A
 #1/0, A #2 IS ALL THAT'S REQUIRED PER 250.66. PER
 250.104(A) (1) THE COLD WATER BOND MUST BE SIZED PER
 250.66, THEREFORE A #2 CU IS REQUIRED. FIELD VERIFY ALL
 CONDITIONS SHOWN ON THE RISER.
 NOTE: THE IMPLICATION THAT THE TRANSFER SWITCH WILL BE
 IN A REMOTE LOCATION FROM THE PANELS, SHOWN WITH MAIN
 BREAKERS WITH NO MAIN DISCONNECT AT THE METER, THIS
 COULD BE A VIOLATION OF 230.72(A), 2005 NEC.
  
 4} THERE IS A STAIRWELL WITH A PARTITION BEING SHOWN TO
 BE REMOVED AT THE LANDING. SHOW WORK BEING DONE IN THAT
 AREA SO THE REQUIRED ELECTRICAL ISSUES MAY BE
 REVIEWED.
  
 5} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 14:37 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 14:37 Sent To E
Notes
2008-05-15 14:37:56TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 10:53 Sent To Z
Notes
2008-04-03 10:54:05TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-21 Cont ID  
Sent By rmcdouga Date 2008-03-21 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2008-03-18 Time 11:46 Sent To  
Notes
2008-03-18 11:46:43TO "SFR" Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-20 Cont ID  
Sent By jleech Date 2008-03-20 Time 15:24 Rev Time 0.20
Received By tgordon Date 2008-03-20 Time 12:05 Sent To P
Notes
2008-03-20 12:05:46NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By jleech Date 2008-04-08 Time 09:06 Rev Time 0.00
Received By jleech Date 2008-04-08 Time 09:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-04-08 Cont ID  
Sent By jleech Date 2008-03-20 Time 15:14 Rev Time 0.00
Received By rmcdouga Date 2008-03-20 Time 14:53 Sent To B
Notes
2008-03-20 15:23:20NOT ENOUGH INFORMATION TO DO A PLUMBING REVIEW. PLEASE
 SHOW ON DEMOLITION PLAN PLUMBING TO BE REMOVED, (HOW
 AREA WAS BEFORE DEMO). IF NEW PLUMBING FIXTURES ARE
 ADDED PLEASE SHOW A SANITARY RISER DIAGRAM SHOWING
 ALLVENTS AND PIPE SIZES. INCUDE MANUFACTURE SPEC SHEET
 FOR ICE MACHINE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 8056695

Review Stop Z ZONING
Rev No 2 Status N Date 2008-04-04 Cont ID  
Sent By choops Date 2008-04-04 Time 10:54 Rev Time 0.00
Received By choops Date 2008-04-04 Time 10:54 Sent To E
Notes
2008-04-04 10:55:15*ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY, AND
 THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status N Date 2008-03-20 Cont ID  
Sent By choops Date 2008-03-20 Time 09:41 Rev Time 0.00
Received By choops Date 2008-03-20 Time 09:41 Sent To M
Notes
2008-03-20 09:41:59*ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY, AND
 THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
  
  
  
 SENT TO "M" - SF RACK