Plan Review Stops For Permit 08030399 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-04-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-04-08 |
Time |
17:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-04-08 |
Time |
16:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-03-21 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-03-21 |
Time |
07:40 |
Sent To |
|
|
Notes |
2008-03-21 10:38:47 | 2004 FBC W/2007 REVISIONS | | LEVEL 2 ALTERATIONS | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | BE REQUIRED. | | | | 2) ON SHEET A1 DEMO NOTE #1 SPECIFIES COMPLIANCE WITH | | THE TOWN OF PALM BEACH AMENDMENTS. PLEASE REVISE TO | | NOTE TO SPECIFY CITY OF WEST PALM BEACH AMENDMENTS. FBC | | 106.1.1* CITY AMENDMENTS. | | | | 3) ON SHEET S2 THE 1/2" X 10' STEEL PLATE IS SPECIFIED | | TO BE ATTACHED TO THE (2) 2 X 12 BEAM WITH (3) ROWS OF | | 16D NAILS @ 6" OC STAGGERED. SECTION 2 ON S3 SPECIFIES | | THE STEEL PLATE ATTACHED WITH (2) ROWS OF 14" DIAMETER | | X 3-1/2" WOOD SCREWS @ 12" OC STAGGERED. PLEASE | | CORRECT. | | | | 4) SECTION 2 ON S-4 SPECIFIES (2) 2 X 12 WITH 1/2" | | PLYWOOD BETWEEN W/2 ROWS OF 10D NAILS @ 6" OC STAGGERED | | AND SECTIONS 3 AND 4 ON S4 SPECIFY 16D NAILS. PLEASE | | CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-05-21 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-05-21 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-05-21 |
Time |
15:03 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-04-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-04-07 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-04-07 |
Time |
12:07 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-03-20 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-03-20 |
Time |
06:54 |
Sent To |
Z |
|
Notes |
2008-03-20 08:49:59 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2004 FBC AS AMENDED, CHAPTER | | 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, THE | | METER ENCLOSURE IS NOT ON THE PLAN. INDICATE IF THE | | RISER IS CORRECT SHOWING AN UNDERGROUND FEED TO THE | | EXISTING PANELS (TO CONFIRM COMPLIANCE WITH 230.70(A) | | (1)). | | | | 2) THE EQUIPMENT GROUND BETWEEN THE METER AND | | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH | | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. 250.6 | | 2005 NEC. | | NOTE: | | IT IS SHOWN AS AN EXISTING SERVICE BUT MUST BE | | CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE IS A | | POTENTIAL OF ENERGIZING ALL METAL PARTS AND EQUIPMENT | | THE EQUIPMENT GROUNDS ARE CONNECTED TO. | | | | 3} THE GROUNDING ELECTRODE CONDUCTOR IS SHOWN AS A | | #1/0, A #2 IS ALL THAT'S REQUIRED PER 250.66. PER | | 250.104(A) (1) THE COLD WATER BOND MUST BE SIZED PER | | 250.66, THEREFORE A #2 CU IS REQUIRED. FIELD VERIFY ALL | | CONDITIONS SHOWN ON THE RISER. | | NOTE: THE IMPLICATION THAT THE TRANSFER SWITCH WILL BE | | IN A REMOTE LOCATION FROM THE PANELS, SHOWN WITH MAIN | | BREAKERS WITH NO MAIN DISCONNECT AT THE METER, THIS | | COULD BE A VIOLATION OF 230.72(A), 2005 NEC. | | | | 4} THERE IS A STAIRWELL WITH A PARTITION BEING SHOWN TO | | BE REMOVED AT THE LANDING. SHOW WORK BEING DONE IN THAT | | AREA SO THE REQUIRED ELECTRICAL ISSUES MAY BE | | REVIEWED. | | | | 5} PLEASE PROVIDE A PANEL SCHEDULE SO THAT | | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT | | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, | | 106.3.5.4 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-05-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-15 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-15 |
Time |
14:37 |
Sent To |
E |
|
Notes |
2008-05-15 14:37:56 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-04-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-03 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-03 |
Time |
10:53 |
Sent To |
Z |
|
Notes |
2008-04-03 10:54:05 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2008-03-21 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-03-18 |
Time |
11:46 |
Sent To |
|
|
Notes |
2008-03-18 11:46:43 | TO "SFR" Z" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-03-20 |
Time |
15:24 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2008-03-20 |
Time |
12:05 |
Sent To |
P |
|
Notes |
2008-03-20 12:05:46 | NO MECHANICAL PLANS SUBMITTED, AND NO | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | THIS TIME. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2008-04-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-04-08 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-04-08 |
Time |
09:02 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2008-04-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-03-20 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2008-03-20 |
Time |
14:53 |
Sent To |
B |
|
Notes |
2008-03-20 15:23:20 | NOT ENOUGH INFORMATION TO DO A PLUMBING REVIEW. PLEASE | | SHOW ON DEMOLITION PLAN PLUMBING TO BE REMOVED, (HOW | | AREA WAS BEFORE DEMO). IF NEW PLUMBING FIXTURES ARE | | ADDED PLEASE SHOW A SANITARY RISER DIAGRAM SHOWING | | ALLVENTS AND PIPE SIZES. INCUDE MANUFACTURE SPEC SHEET | | FOR ICE MACHINE. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 8056695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
N |
Date |
2008-04-04 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-04-04 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-04-04 |
Time |
10:54 |
Sent To |
E |
|
Notes |
2008-04-04 10:55:15 | *ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY, AND | | THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. | | | | | | | | | | SENT TO "E" - BT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-03-20 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-03-20 |
Time |
09:41 |
Sent To |
M |
|
Notes |
2008-03-20 09:41:59 | *ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY, AND | | THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. | | | | | | | | | | SENT TO "M" - SF RACK |
|
|