Plan Review Details - Permit 08030318
Plan Review Stops For Permit 08030318
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-20 Cont ID  
Sent By mjacobs Date 2008-05-20 Time 08:58 Rev Time 0.00
Received By mjacobs Date 2008-05-20 Time 08:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-10 Cont ID  
Sent By mjacobs Date 2008-05-10 Time 15:23 Rev Time 0.00
Received By mjacobs Date 2008-05-10 Time 13:03 Sent To  
Notes
2008-05-10 15:23:45BUILDING PLAN REVIEW 2ND
 PERMIT: 08030318
 ADD: 4400 N. CONGRESS AVE.
 CONT: ROBB CONST. INC.
 TEL: (561)856-1643
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:2ND5-10-08
 ACTION: DENIED
  
 1)OK
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) OK
 4)OK
 5)OK
 6)OK
 7)OK
 8)OK
 NEW** SHEET D1.1 IS MISSING FROM BOTH SETS OF DRAWINGS.
 THE WOMEN?S BATHROOM DOES NOT MEET THE ACCESSIBILITY
 RREQUIREMENTS. FBC 11-4.1.6(A) NO ALTERATION SHALL
 DECREASE ANY ACCESSIBILITY OR USABILITY OF THE BUILDING
 SYSTEMS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-01 Cont ID  
Sent By mjacobs Date 2008-04-01 Time 13:01 Rev Time 0.00
Received By mjacobs Date 2008-03-31 Time 11:32 Sent To  
Notes
2008-04-01 13:00:58BUILDING PLAN REVIEW
 PERMIT: 08030318
 ADD: 4400 N. CONGRESS AVE.
 CONT: ROBB CONST. INC.
 TEL: (561)856-1643
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)PROVIDE FIRE SPRINKLER PLANS SHOWING THE
 SPRINKLER-HEAD LAYOUT AND THE EFFECTS OF THE NEW
 CONSTRUCTION IN RELATION OF THE EXISTING HEADS.
 FBC106.3.5.1.1 (5)*
  
 5)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 6)WPB AMENDMENTS 106.1.2*ADDITIONAL INFORMATION IS
 REQUIRED FOR THE CONSTRUCTABILITY OF WALL TYPE #2 WHICH
 IS NOT ATTACHED TO THE STRUCTURE OR CEILING ABOVE AND
 HAS AT LEAST SEVEN DOUBLE SOLID CORE DOORS INSTALLED IN
 THIS TYPE OF WALL. SEE SHEET A1.1 FOR MORE INFORMATION,
 ALSO ON SHEET A1.1 SOME OF THE WALLS ARE MAY BE LABELED
 WRONG.
  
 7)ARE THE EXISTING WALLS ATTACHED TO THE CEILING OR
 STRUCTURE ABOVE? IF THEY ARE ATTACHED TO EITHER
 STRUCTURE OR EXISTING CEILING WHY THE NEW INFILL WALLS
 WILL BE 4 INCHES BELOW THE CEILING?
  
 8)THE PLANS SHALL CLEARLY SHOW THE MEANS OF EGRESS
 WHICH SHALL INCLUDE EXIT ACCESS FBC 1013, EXIT FBC 1017
 AND EXIT DISCHARGE FBC 1023.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2008-05-05 Time 18:41 Sent To  
Notes
2008-05-05 18:44:49REDLINED PLANS.
  
 *** NO ELECTRICAL WORK SHOWN FOR ANY NEW LIGHTING OR
 WIRING FOR LIGHTING. IF THERE IS ANY NEW LIGHTING OR
 WIRING FOR LIGHTING, PLANS SHALL BE REVISED AND
 COMPLIANCE WITH FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2,
 .1.3 MUST BE MET. THIS WAS REDLINED ON PLANS.
  
 *** THE LOW VOLTAGE SYSTEMS SHOWN ON PLANS IS TO BE
 UNDER A SEPARATE PERMIT. THESE PLANS MAY BE REFERENCED
 FOR SCOPE OF WORK. FEE AND APPLICATION WILL BE DUE BY
 LICENSED CONTRACTOR.
  
 *** THE ELECTRICAL SYSTEMS SHOWN ON PLANS IS TO BE
 UNDER A SEPARATE PERMIT. THESE PLANS MAY BE REFERENCED
 FOR SCOPE OF WORK. FEE AND APPLICATION WILL BE DUE BY
 LICENSED CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By dpalmer Date 2008-03-19 Time 09:00 Rev Time 0.00
Received By dpalmer Date 2008-03-18 Time 16:59 Sent To  
Notes
2008-03-19 09:00:47** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE SETS OF SUBMITTED PLANS ARE NOT
 COMPLETE AT THIS TIME. FOR EXAMPLE: PLEASE SEE COVER
 SHEET WHICH LIST THE SHEET A2.1 AND A2.2 FOR REFLECTED
 CEILING HOWEVER THESE ARE NOT IN SETS. PLEASE INCLUDE
 SHOWING ALL THAT IS EXISTING MEETING. IS THERE ANY
 CEILING WORK?
 FBC 106.1.2, 106.3.1 FOR ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE ARCHITECTURAL TITLE BLOCKS WHICH
 ARE MISSING THE REQUIRED PRINTED NAME AND PRINTED
 LICENSE NUMBER OF THE ARCHITECT OF RECORD.
 FAC 61G1-16.004, FS 481
  
 3) NOTE: PLEASE SEE NOT ALL THE PANEL SCHEDULE
 DESIGNATIONS ON THE RISER DIAGRAM CORRELATE WITH THE
 DESIGNATIONS ON THE PANEL SCHEDULES.
 PLEASE SEE FOR EXAMPLE: PANELS HP2C, HP2B ETC
 PLEASE ALSO SEE THAT PANEL H2C ON E5.0 INDICATES THIS
 PANEL AS A 25AMP MLO PANEL WHICH IS NOT POSSIBLE. THIS
 PANEL CONTAINS A LOAD HIGHER THAN THE 25AMPS.
 AS THIS PANEL DESIGNATION IS NOT ON RISER, CONFIRMATION
 ON THIS CAN NOT BE DONE.
 PLEASE COORDINATE ALL PANELS.
 240.4, 220, 230 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON
 ELECTRICAL SHEET E5.0 FOR MDP ARE NOT FROM THE CURRENT
 2005 NEC.
 PLEASE SEE 220.21 LISTED, HOWEVER THE 2005 NEC DOES NOT
 CONTAIN A 220.21.
 PLEASE ADJUST AS NEEDED.
 FBC 106.1.2
  
 ** PLEASE KNOW AS SOME PLANS WERE NOT SUBMITTED AND
 SOME SCOPE OF WORK IS NOT CONFIRMED A COMPLETE REVIEW
 COULD NOT BE DONE AT THIS TIME. THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-05-19 Time 11:33 Rev Time 0.00
Received By mawillia Date 2008-05-19 Time 11:15 Sent To  
Notes
2008-05-19 11:28:35*****REVISION #2, DATED 5/14/08, APPROVED*****
  
 REVISED PLAN SHEETS LS.1 & LS.2 STAMPED, INITIALED, AND
 INITIALED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-05-12 Cont ID  
Sent By mawillia Date 2008-05-12 Time 12:54 Rev Time 0.00
Received By mawillia Date 2008-05-12 Time 12:17 Sent To  
Notes
2008-05-12 12:48:34*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS LS.1 & LS.2, A2.1 & A2.2,
 E3.0 & E3.1, AND E6.0 WERE STAMPED, INITIALED, AND
 INITIALED.
  
  
 CAPT. MICHAEL A> WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-16 Cont ID  
Sent By mawillia Date 2008-04-16 Time 14:29 Rev Time 0.00
Received By mawillia Date 2008-04-15 Time 16:23 Sent To  
Notes
2008-04-16 13:10:24*****DENIED*****
  
  
 01.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 02.ON THE SHEETS LS.1 AND LS.2, SHOW THE TRAVEL
 DISTANCE TO THE EXITS NOT PASSING THROUGH
 OBSTRUCTIONS.
  
 03.FIRE EXTINGUISHER(S) ARE TO BE 2A10BC RATED. CLASS
 C FIRE EXTINGUISHER NOTED ON SHEET LS.1
  
 04.ONLY ONE FIRE EXTINGUISHER NOTED ON SHEET LS.1,
 DOES THIS SATISFY THE 75' TRAVEL DISTANCE.
  
 05.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN ON THE
 LIFE SAFETY SHEETS.
  
 06.ON SHEET LS.2, IT APPEARS THAT THE DOUBLE DOORS OF
 THE BOARD ROOM [227] SWING INTO AN EXIT ACCESS
 CORRIDOR.BE ADVISED THAT DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF
 OF THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR,
 PASSAGEWAY, ETC, WHEN FULLY OPEN.
  
 07.NO EXIT LIGHTS AND EMERGENCY LIGHTS SHOWN ON E3.0
 AND E3.1 SHEETS.OPTIONAL IF SHOWN ON THE LIFE SAFETY
 SHEETS.
  
 08.CARD KEY ENTRY READERS NOTED ON SHEET E3.1, PLEASE
 BE ADVISED THAT SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED (ONCE THE MASTER PERMIT HAS BEEN ISSUED).
  
 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM SYSTEM REMODEL AND/OR INSTALLATION (ONCE THE
 MASTER PERMIT HAS BEEN ISSUED).
  
 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS
 PROJECT SITE.
  
 11.PLAN SHEET A2.1 & A2.2 MISSING FROM ONE OF THE
 SUBMITTED PLAN SETS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A> WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 14:54 Sent To P
Notes
2008-05-22 14:54:49TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 10:37 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 10:37 Sent To  
Notes
2008-05-19 09:44:51PLANS ROUTED TO "DPALMER" DESK/PER "RBROWN"
2008-05-16 10:40:39TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-23 Cont ID  
Sent By adarroug Date 2008-04-23 Time 13:59 Rev Time 0.00
Received By adarroug Date 2008-04-23 Time 13:59 Sent To  
Notes
2008-04-23 14:03:16TO "COMM" BD#31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-15 Cont ID  
Sent By mawillia Date 2008-04-15 Time 16:23 Rev Time 0.00
Received By mawillia Date 2008-03-18 Time 10:20 Sent To  
Notes
2008-03-18 10:26:14TO "COMM" BD#2

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-06-20 Cont ID  
Sent By mperson Date 2008-06-20 Time 08:16 Rev Time 0.00
Received By mperson Date 2008-06-20 Time 08:16 Sent To PC
Notes
2008-06-20 10:00:57REVISION SHEET PE1.0: "OK" SANITRY AND WATER RISER
 DIAGRAM FOR NEW ADA LAV.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-19 Cont ID  
Sent By kstevens Date 2008-05-19 Time 12:32 Rev Time 0.00
Received By kstevens Date 2008-05-19 Time 12:32 Sent To  
Notes
2008-05-19 12:33:07PASSED/PROVISO--REVISION REQUIRED--SUBMIT A
 ISOMETRIC SANITARY RISER DIAGRAM FOR NEW LAV PRIOR TO
 INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-02 Cont ID  
Sent By kstevens Date 2008-05-02 Time 17:57 Rev Time 0.00
Received By kstevens Date 2008-05-02 Time 17:57 Sent To  
Notes
2008-05-02 18:02:03DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SHT D1.1 THE REMOVAL OF THE WOMEN'S TOILET ROOM IN
 EFFECT DECREASES THE ACCESSIBILITY OF THE BUILDING.
 SECTION 11-4.1.6(1)(A). THIS IS NOT ACCEPTABLE. PLEASE
 CHOOSE AN ALTERNATIVE SUCH AS A UNISEX TOILET ROOM OR
 ALTERING THE STALL IN THE EXISTING TOILET ROOM TO
 COMPLY WITH THE ACCESSIBLITY CODE.
 ****RESPONSE NOTED, BUT THE EXISTING STALL WITH THE LAV
 INSTALLED STILL DECREASES THE ACCESSIBILITY AS THE LAV
 NOW ENCROCHES INTO THE CLEAR FLOOR SPACE REQUIRED TO
 TRANSFER FROM THE WHEECHAIR ONTO THE WATER CLOSET.
  
 6. SHTS D1.1 & PE1.0 IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5. ALL DEMO'D/CAPPED LINES SHALL BE LEFT UNCOVERED
 UNTIL FIELD INSPECTOR INSPECTION & APPROVAL. PLEASE
 INDICATE ON PLANS.
 ****RESPONSE NOTED, BUT THE NOTE IS NOT STATED ON THE
 D1.1 SHEET. ALSO SHT D1.1 HAS NOT BEEN RESUBMITTED BUT
 IS INDICATED ON THE INDEX OF DRAWINGS SHT CS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By kstevens Date 2008-04-11 Time 09:55 Rev Time 0.00
Received By kstevens Date 2008-04-11 Time 09:55 Sent To  
Notes
2008-04-11 10:59:42DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS REQUIRE THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENTS IN THE TITLE BLOCK.
 FAC 61G1-16.004(6) & FS 481.2055.
  
 2. ALL SHEETS WITH CONNORS DESIGN GROUP LLC TITLE
 BLOCK. THE ADDRESS INDICATED ON THE TITLE BLOCK DOES
 NOT REFLECT THE ADDRESS OF RECORD ON THE STATE OF
 FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE
 UPDATE THE DBPR WEBSITE OR THE TITLE BLOCKS TO SHOW THE
 CORRECT ADDRESS AND SO THEY REFLECT. FAC 61G1-16.004(1)
 & FS 481.2055.
  
 3. SHTS DC1.1 & DC1.2 ARE INDICATED AS SHTS DC.1 & DC.2
 ON THE RELATED SHEETS. PLEASE CORRELATE. SECTION
 106.1.1.
  
 4. SHTS A2.1 & A2.2 WERE NOT SUBMITTED IN ONE SET OF
 PLANS. PLEASE SUBMIT COMPLETE SETS OF PLANS FOR REVIEW.
 SECTION 106.1.
  
 5. SHT D1.1 THE REMOVAL OF THE WOMEN'S TOILET ROOM IN
 EFFECT DECREASES THE ACCESSIBILITY OF THE BUILDING.
 SECTION 11-4.1.6(1)(A). THIS IS NOT ACCEPTABLE. PLEASE
 CHOOSE AN ALTERNATIVE SUCH AS A UNISEX TOILET ROOM OR
 ALTERING THE STALL IN THE EXISTING TOILET ROOM TO
 COMPLY WITH THE ACCESSIBLITY CODE.
  
 6. SHTS D1.1 & PE1.0 IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5. ALL DEMO'D/CAPPED LINES SHALL BE LEFT UNCOVERED
 UNTIL FIELD INSPECTOR INSPECTION & APPROVAL. PLEASE
 INDICATE ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]