2008-04-10 13:38:53 | BUILDING PLAN REVIEW |
| PERMIT: 08030236 |
| ADD: 928 28TH ST |
| CONT: TIM GIVINS BUILDING |
| TEL: (561) 533-5828 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. |
| PLEASE PROVIDE ON YOUR PLANS |
| THE 2007 SUPPLEMENTS. |
| |
| 2) PLEASE CORRECT, THE PERMIT APPLICATION INDICATES BY |
| ADDRESS AND PCN THIS WORK WILL BE COMPLETED ON LOT 14 |
| WHERE AS THE PLANS INDICATE LOT 10. SEE ALSO AREAL |
| VIEWS INDICATE A STRUCTURE ON LOT 14 AND NO DEMO |
| PERMITS. PLEASE MAKE CORRECTION ON THE PERMIT |
| APPLICATION FOR THE ADDRESS AND LCORRECT PROPERTY |
| CONTROLNUMBER. CONTACT LILY AT ADDRESSING FOR THE NEW |
| ADDRESS FOR LOT# 10 |
| AT 822-1239. |
| |
| 3)LANDSCAPE ARCHITECT MORIKOMI IS MISSING THEIR |
| CERTIFICATE OF AUTHORIZATION.481.219 F.S. CERTIFICATE |
| OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET |
| BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER A |
| FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE |
| CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO |
| EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| |
| 4)1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 6) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION |
| TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| SECTION 113 OF THIS CHAPTER. |
| |
| 7) SHEET A-1 PLEASEPROVIDE THE CODE INFORMATION |
| DESIGNED TOO! SEE 1E. |
| |
| 8) SHEET A-1 CORRECT THE BUILDING TYPE, PLANS INDICATE |
| A TYPE IV WHICH IS HEAVY TIMBER PLEASE SEE TABLE 503 |
| AND 602.4. |
| |
| NOTE FOR THIS BUILDING REVIEW THIS BUILDING WILL BE |
| REVIEWED TO THE MINIMUM BUILDING TYPE: |
| 2004 FBC W/ 2007 SUPPLEMENTS |
| BUILDING TYPE: V-BF-1MAX OF 8,500 SQ FT. |
| |
| 9) THE PLANS INDICATE THE BACK WALL WILL BE LOCATED 7.5 |
| FT. FROM THE PROPERTY LINE REQUIRING A 1 HR FIRE |
| RATING, PLEASE PROVIDE HOW THIS SHALL BE ACCOMPLISHED. |
| SEE TABLE 602. |
| |
| 10) SHEET A-1 IN F OCCUPANCIES COMMON PATH OF TRAVEL IS |
| LIMITED TO 50'. THE END UNITS 1 & 4 APPEAR TO BE OVER |
| BY A PROXXIMATELY 2'-0". PLEASE SEE 1013.3 EXCEPTION# |
| 4. |
| |
| 11)SHEET A-1 THE END UNITS 1 & 4 BOTH REQUIRING 2 |
| EXITS WILL ALSO NEED TO MAKE THE REAR EXIT COMPLY WITH |
| 11-4.1.3(8)(A)(II)ACCESSIBLE ENTRANCES MUST BE |
| PROVIDED IN A NUMBER AT LEAST EQUIVALENT TO THE NUMBER |
| OF EXITS REQUIRED BY THE APPLICABLE BUILDING/ FIRE |
| CODES.THE REAR EXITS WILL NEED TO BE ACCESSIBLE NO |
| DROPPED WALKWAY AND ACCESSIBLE TO THE PUBLIC WAY. (9) |
| IN BUILDINGS OR FACILITIES, OR PORTIONS OF BUILDINGS OR |
| FACILITIES, REQUIRED TO BE ACCESSIBLE, ACCESSIBLE MEANS |
| OF EGRESS SHALL BE PROVIDED IN THE SAME NUMBER AS |
| REQUIRED FOR EXITS BY LOCAL BUILDING/ FIRE SAFETY |
| REGULATIONS. |
| |
| 12) THE TWO INTERIOR UNITS THAT DO NOT HAVE ACCESSIBLE |
| EXITS WILL INDICATE AS SUCH: 11-4.30.7. |
| |
| 13) SHEET A-3 WALL SECTION- C, INDICATE ONE-HOUR RATED |
| GYPSUM STEEL STUD WALL 3 1/2 INCH STUD @ 12" ON CENTER. |
| PLEASE SEE TABLE 2508.1 EITHER GA-216 OR ASTM C 754 FOR |
| NON-LOAD BEARING WALLS ,FOR STUD LIMITATIONS AND FOR |
| MINIMUM LATERAL LOADING OF 5 LPSF.THE LIMITATION OF |
| 22'-6". THE WALL AT THE CENTER OF THE BUILDING IS |
| APPROXIMATELY 26'-0" TALL THE EAVES 22'-0" TALL. |
| |
| 14) PLEASE ALSO PROVIDE INFORMATION FOR A 1 HOUR FIRE |
| RESISTANT FLEXIBLE SEALENT TO THE ROOF DECK. 708.4./ |
| 713.1. |
| |
| 15) SHEET A-1 DOES NOT INDICATE ANY EXIT SIGNS SHOW |
| COMPLIANCE WITH 1006.3.1. |
| |
| 16) SHEET A-3 INDICATES THE STEEL FRAME IS A PRE-FAB BY |
| OTHERS, THERE IS NO ENGINEERED INFORMATION NOR PLANS |
| SUBMITED WITH THIS PACKAGE. 1609..1.1 AND 1609.1.3. |
| |
| 17)SHEET A-3 INDICATES EAVE TRIM BUT NO GUTTERS. |
| 1503.3.6 PROTECTION AGAINST DECAY & TERMITES. |
| CONDENSATE LINES & ROOF DOWN SPOUTS SHALL DISCHARGE AT |
| LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY |
| UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS. |
| |
| 18)MISSING WIND INFORMATION FOR DESIGN: |
| 1609.6.2 WIND DESIGN PROCEDURES |
| 1)THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| |
| 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| ACCORDANCE WTIH SECTION1609.5. |
| |
| 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4. |
| |
| 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| |
| 19) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| |
| 20)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES, |
| 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| A) EXTERIOR DOORS WITH GLAZED OPENINGS |
| B) EXTERIOR HOLLOW MEETAL DOORS |
| C) OVERHEAD OR COIL DOORS |
| D) SIDING |
| E) ROOFING ASSEMBLIES. |
| |
| 21) PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| WWW.FLORIDABUILDING.ORG |
| |
| 22) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 23) NOTE CANVAS AWNINGS SHALL EQUIRE A SEPERATE |
| PERMIT. |
| |
| 24) PLEASE SEE CALCULATED VALUE OF PROJECT 4600 SQ FT X |
| 55.46= $ 255,116.00 ADDITIONAL FEES DUE. |
| |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT |
| FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS |
| REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3*BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BYTHE INTERNATIONAL CODE |
| CONGRESS. |
| |
| 25)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |