Plan Review Details - Permit 08030236
Plan Review Stops For Permit 08030236
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-04-16 Cont ID  
Sent By lursu Date 2008-04-16 Time 13:23 Rev Time 0.00
Received By lursu Date 2008-04-16 Time 12:02 Sent To  
Notes
2008-04-16 13:23:55A NEW SITE ADDRESS IS ASSIGNED TO THE NEW WAREHOUSE TO
 BE BUILT ON PCN = 74434309060060100 AS:
 932 28TH ST , WEST PALM BEACH, FL 33407
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-04-10 Cont ID  
Sent By jwitmer Date 2008-04-10 Time 11:11 Rev Time 5.55
Received By jwitmer Date 2008-04-10 Time 09:28 Sent To  
Notes
2008-04-10 13:38:53BUILDING PLAN REVIEW
 PERMIT: 08030236
 ADD: 928 28TH ST
 CONT: TIM GIVINS BUILDING
 TEL: (561) 533-5828
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
 PLEASE PROVIDE ON YOUR PLANS
 THE 2007 SUPPLEMENTS.
  
 2) PLEASE CORRECT, THE PERMIT APPLICATION INDICATES BY
 ADDRESS AND PCN THIS WORK WILL BE COMPLETED ON LOT 14
 WHERE AS THE PLANS INDICATE LOT 10. SEE ALSO AREAL
 VIEWS INDICATE A STRUCTURE ON LOT 14 AND NO DEMO
 PERMITS. PLEASE MAKE CORRECTION ON THE PERMIT
 APPLICATION FOR THE ADDRESS AND LCORRECT PROPERTY
 CONTROLNUMBER. CONTACT LILY AT ADDRESSING FOR THE NEW
 ADDRESS FOR LOT# 10
 AT 822-1239.
  
 3)LANDSCAPE ARCHITECT MORIKOMI IS MISSING THEIR
 CERTIFICATE OF AUTHORIZATION.481.219 F.S. CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET
 BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO
 EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 4)1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 6) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 7) SHEET A-1 PLEASEPROVIDE THE CODE INFORMATION
 DESIGNED TOO! SEE 1E.
  
 8) SHEET A-1 CORRECT THE BUILDING TYPE, PLANS INDICATE
 A TYPE IV WHICH IS HEAVY TIMBER PLEASE SEE TABLE 503
 AND 602.4.
  
 NOTE FOR THIS BUILDING REVIEW THIS BUILDING WILL BE
 REVIEWED TO THE MINIMUM BUILDING TYPE:
 2004 FBC W/ 2007 SUPPLEMENTS
 BUILDING TYPE: V-BF-1MAX OF 8,500 SQ FT.
  
 9) THE PLANS INDICATE THE BACK WALL WILL BE LOCATED 7.5
 FT. FROM THE PROPERTY LINE REQUIRING A 1 HR FIRE
 RATING, PLEASE PROVIDE HOW THIS SHALL BE ACCOMPLISHED.
 SEE TABLE 602.
  
 10) SHEET A-1 IN F OCCUPANCIES COMMON PATH OF TRAVEL IS
 LIMITED TO 50'. THE END UNITS 1 & 4 APPEAR TO BE OVER
 BY A PROXXIMATELY 2'-0". PLEASE SEE 1013.3 EXCEPTION#
 4.
  
 11)SHEET A-1 THE END UNITS 1 & 4 BOTH REQUIRING 2
 EXITS WILL ALSO NEED TO MAKE THE REAR EXIT COMPLY WITH
 11-4.1.3(8)(A)(II)ACCESSIBLE ENTRANCES MUST BE
 PROVIDED IN A NUMBER AT LEAST EQUIVALENT TO THE NUMBER
 OF EXITS REQUIRED BY THE APPLICABLE BUILDING/ FIRE
 CODES.THE REAR EXITS WILL NEED TO BE ACCESSIBLE NO
 DROPPED WALKWAY AND ACCESSIBLE TO THE PUBLIC WAY. (9)
 IN BUILDINGS OR FACILITIES, OR PORTIONS OF BUILDINGS OR
 FACILITIES, REQUIRED TO BE ACCESSIBLE, ACCESSIBLE MEANS
 OF EGRESS SHALL BE PROVIDED IN THE SAME NUMBER AS
 REQUIRED FOR EXITS BY LOCAL BUILDING/ FIRE SAFETY
 REGULATIONS.
  
 12) THE TWO INTERIOR UNITS THAT DO NOT HAVE ACCESSIBLE
 EXITS WILL INDICATE AS SUCH: 11-4.30.7.
  
 13) SHEET A-3 WALL SECTION- C, INDICATE ONE-HOUR RATED
 GYPSUM STEEL STUD WALL 3 1/2 INCH STUD @ 12" ON CENTER.
 PLEASE SEE TABLE 2508.1 EITHER GA-216 OR ASTM C 754 FOR
 NON-LOAD BEARING WALLS ,FOR STUD LIMITATIONS AND FOR
 MINIMUM LATERAL LOADING OF 5 LPSF.THE LIMITATION OF
 22'-6". THE WALL AT THE CENTER OF THE BUILDING IS
 APPROXIMATELY 26'-0" TALL THE EAVES 22'-0" TALL.
  
 14) PLEASE ALSO PROVIDE INFORMATION FOR A 1 HOUR FIRE
 RESISTANT FLEXIBLE SEALENT TO THE ROOF DECK. 708.4./
 713.1.
  
 15) SHEET A-1 DOES NOT INDICATE ANY EXIT SIGNS SHOW
 COMPLIANCE WITH 1006.3.1.
  
 16) SHEET A-3 INDICATES THE STEEL FRAME IS A PRE-FAB BY
 OTHERS, THERE IS NO ENGINEERED INFORMATION NOR PLANS
 SUBMITED WITH THIS PACKAGE. 1609..1.1 AND 1609.1.3.
  
 17)SHEET A-3 INDICATES EAVE TRIM BUT NO GUTTERS.
 1503.3.6 PROTECTION AGAINST DECAY & TERMITES.
 CONDENSATE LINES & ROOF DOWN SPOUTS SHALL DISCHARGE AT
 LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS.
  
 18)MISSING WIND INFORMATION FOR DESIGN:
 1609.6.2 WIND DESIGN PROCEDURES
 1)THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WTIH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 19) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 20)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 A) EXTERIOR DOORS WITH GLAZED OPENINGS
 B) EXTERIOR HOLLOW MEETAL DOORS
 C) OVERHEAD OR COIL DOORS
 D) SIDING
 E) ROOFING ASSEMBLIES.
  
 21) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 22) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 23) NOTE CANVAS AWNINGS SHALL EQUIRE A SEPERATE
 PERMIT.
  
 24) PLEASE SEE CALCULATED VALUE OF PROJECT 4600 SQ FT X
 55.46= $ 255,116.00 ADDITIONAL FEES DUE.
  
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3*BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BYTHE INTERNATIONAL CODE
 CONGRESS.
  
 25)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-18 Cont ID  
Sent By dpalmer Date 2008-03-18 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2008-03-18 Time 16:28 Sent To  
Notes
2008-03-18 16:28:37** DENIED REVIEW **
  
  
  
  
 1) NOTE: ** IMPORTANT**PLEASE SEE THERE ARE NUMEROUS
 ITEMS MISSING FOR MINIMUM CODE COMPLIANCE, A FULL AND
 COMPLETE REVIEW OF MANY ITEMS COULD NOT BE DONE. THERE
 MAY VERY WELL BE SEVERAL NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
 FBC 106.3.1, 106.1.2, 106.3.5.1.2 ADMIN SECTIONS FOR
 COMPLETE PLANS.
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODE SHALL BE STATED
 ON PLANS RELEVANT TO THE MINIMUM DESIGNS. PLANS STATE
 THE LATEST EDITIONS WHICH IS NOT ACCEPTABLE. PLEASE BE
 SURE THE ELECTRICAL AS WELL AS COVER SHEET REFLECTS THE
 FOLLOWING REQUIRED FOR THIS TRADE REVIEWER.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 FBC 106.1.2, FS 553.73
  
 3) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER
 DIAGRAM SHOWING CODE COMPLIANCE. PLEASE SEE THE
 FOLLOWING SUB SECTIONS AS THERE ARE SEVERAL ITEMS
 MISSING.
 A) PLEASE SEE MISSING REQUIRED GROUNDING ELECTRODE
 SYSTEM. FOR EXAMPLE: PLEASE SEE ONE OF THE ITEMS
 MISSING IS THE REQUIRED FOOTER STEEL.
 B) PLEASE SEE MISSING DISCONNECTS FOR TENANTS.
 C) PLEASE SEE MISSING FEEDERS AFTER THE FIRST MEANS OF
 DISCONNECT.
 D) PLEASE SEE MISSING TAPPED CONDUCTORS.
 E) PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR(S)
 AFTER THE FIRST MEANS OF DISCONNECT.
 F) PLEASE SEE MISSING CONDUIT TO VERIFY CONDUIT FILL.
 G) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE
 EQUIPMENT.
 I) PLEASE SEE MAIN SHOWN AS NEMA 32, WHICH IS NOT
 CORRECT. THERE IS NO SUCH LISTING.
 J) PLEASE SEE MISSING FLOATING NEUTRAL REQUIRED AT
 METERS AFTER THE FIRST MEANS OF DISCONNECT.
 K) PLEASE SEE MISSING PANEL SCHEDULES.
 L) PLEASE SEE MISSING MINIMUM BRANCH CIRCUIT CONDUCTORS
 AND OVER CURRENT PROTECTION(S).
 ETC ETC.
 2005 NEC.
 215.5, 110.9, 90.7, 110.3, 250.122, 250.6, 250.66,
 250.50, 240.4, 310.16, 230.70, 240.24, 250.50, 408.4
 ETC
  
 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO
 NOT REFLECT ANY CALCULATIONS FROM THE NATIONAL
 ELECTRICAL CODE.
 PLEASE SEE NEC 220.
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED. PLEASE
 BE SURE TO SEE 700.12F FOR CIRCUITING OF EMERGENCY AND
 EXIT LIGHTS.
 310.16, 240.4, 408.4
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE PLANS CALLS FOR 150AMP SERVICE
 TO EACH BAY HOWEVER BASED ON THE RISER DIAGRAM THIS ARE
 ONLY 100AMPS.
 PLEASE CORRELATE ALL.
 FBC106.1.2, NEC 215.5, 240.4, 220 ETC
  
 7) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER FBC
 13-400.3.A, 13-400.3.B,ETC
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3, 13-415.2
 FOR INTERIOR ALLOWANCES.
 PLEASE SEE MISSING LIGHTING CONTROLS PER
 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING ETC
 AS NO INFORMATION WAS SUBMITTED NO REVIEW OF ANY ITEMS
 COULD BE DONE.
 PLEASE SEE ALL OF CHAPTER 13 AND COMMENTS FROM OTHER
 TRADES.\
  
 8) NOTE: PLEASE SUBMIT PLANS WHICH ARE SIGNED, DATED
 AND SEALED BY THE DESIGN PROFESSIONAL. PLEASE SEE ONE
 SET SUBMIT HAD THE DESIGNER OF RECORD SIGNATURE
 SCRATCHED OUT AND MISSING RAISED SEAL.
 PLEASE SEE FAC 61G15-23.002 AND FS471.025 AS EACH
 SECTION NOTED REQUIRES BOTH SETS TO BE SIGNED, DATED
 AND SEALED BY THE DESIGNER OF RECORD.
  
 9) NOTE: PLEASE SEE THE LANDSCAPE ARCHITECTURAL
 PLANS/TITLE BLOCKS ARE MISSING THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED PER FAC 61G1-16.004
 AND FS 481.219.
 PLEASE ALSO SEE THE TITLE BLOCKS ARE MISSING THE
 REQUIRED PRINTED NAME AND PRINTED LICENSE NUMBER OF
 SAID DESIGNER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 ** DUE TO THE EXTENT OF COMMENTS ABOVE, ONE COPY OF
 PLANS IS BEING RETAINED BY THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By rchokshi Date 2008-03-20 Time 08:55 Rev Time 0.00
Received By rchokshi Date 2008-03-20 Time 08:47 Sent To  
Notes
2008-03-20 08:55:23FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 IF THE TOTAL SITE AREA IS LESS THAN AN ACRE, NOI IS NOT
 REQUIRED.
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. DUMPSTERLOCATION MUST BE ACCESSIBLE FOR PICKUP
 TRUCK.
  
 6. PLEASE PROVIDE A WATER QUALITY CALCULATIONS. PLEASE
 SHOW ON CALCULATION THAT YOU HAVE CONSIDERED FLOOD ZONE
 AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA AND CROWN OF
 THE ROAD WHEN YOU DETERMINE THE FIRST FLOOR ELEVATION.
 FIRST FLOOR ELEVATION SHOULD BE ATLEAST 1 FOOT HIGHER
 THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS. STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-04-14 Cont ID  
Sent By mawillia Date 2008-04-14 Time 14:04 Rev Time 0.00
Received By mawillia Date 2008-04-14 Time 12:51 Sent To  
Notes
2008-04-14 13:49:57*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE
 VICINTITY THEREOF (INCLUDING STREETS, ALLEYS, ETC.) .
  
 03.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 28TH STREET.
 AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO
 LESS THAN 6' IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.
  
 04.IT APPEARS THAT THERE WILL BE FOUR UNITS IN THIS
 BUILDING, DISPLAY/SHOW THE UNIT NUMBER AS PER WEST PALM
 BEACH CODE OF 3' IN HEIGHT AND 1" IN WIDTH/STROKE.
 UNIT NUMBERS SHALL NOT BE ON THE FRONT DOORS.UNIT
 NUMBERS MAY BO ON THE REAR DOOR.
  
 05.LIST THE HAZARD CLASSIFICATION OF THE CONTENTS AS
 LOW, ORDINARY, OR HIGH.
  
 06.PLEASE SHOW TRAVEL DISTANCE TO THE EXITS.
  
 07.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S)
 WHICH SATIFIES THE 75' TRAVEL DISTANCE.
  
 08.PLANS INDICATE THAT THIS IS A NEW ONE STORY
 PREFABRICATED METAL BUILDING, WHEREAS IT SHOWN THAT
 THIS BUILDING HAS MAXIMUM OF FIVE STORIES.PLEASE
 EXPLAIN.
  
 09.IT IS STATED THAT THE MAXIMUM NUMBER OF OCCUPANCY
 IS 46 PERSONS, IS THIS FOR THE ENTIRE BUILDING OR FOR
 EACH UNIT?
  
 10.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-14 Cont ID  
Sent By mawillia Date 2008-04-14 Time 12:51 Rev Time 0.00
Received By mawillia Date 2008-03-12 Time 14:53 Sent To  
Notes
2008-03-12 14:53:49TO "COMM" BD#46

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-03-25 Cont ID  
Sent By lfranco Date 2008-03-25 Time 17:46 Rev Time 0.00
Received By RKUSSNER Date 2008-03-25 Time 17:51 Sent To  
Notes
2008-03-25 17:51:03LANDSCAPING:*** PASSED WITH PROVISO ****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2.SEE MARK-UPS ON SHEET L-1.RELOCATE HEDGE LOCATED
 ON THE FRONT OF THE PROPERTY, TO INSIDE PERIMETER AS
 NOTED.
  
 3.PROVIDE SOD AND IRRIGATION IN RIGHT-OF-WAY PER
 ZONING CODE REQUIREMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 ROBERT KUSSNER
 LANDSCAPE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1462
 EMAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-03-27 Cont ID  
Sent By tgordon Date 2008-03-27 Time 15:40 Rev Time 0.25
Received By tgordon Date 2008-03-27 Time 15:40 Sent To  
Notes
2008-03-27 15:44:29NOTE: A MECHANICAL PERMIT WILL BE REQUIRED FOR THE 4
 BATHROOM EXHAUST FANS.
  
 NO MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL PERMIT
 NUMBER APPLIED FOR AT THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-11 Cont ID  
Sent By kstevens Date 2008-04-11 Time 06:42 Rev Time 0.00
Received By kstevens Date 2008-04-10 Time 14:19 Sent To  
Notes
2008-04-11 07:40:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THE CODES USED TO DESIGN THE PROJECT. THE
 PLANS WILL BE REVIEWED PER THE FLORIDA BUILDING CODE
 2004 EDITION WITH AMENDMENTS UP TO AND INCLUDING THE
 2007 VERSION. SECTION 106.1.2 & FS 553.73(1)(A). PLEASE
 INDICATE ON PLANS.
  
 2. SHTA-1 PER TABLE 403.1 A SERVICE SINK AND A
 DRINKING FOUNTAIN ARE REQUIRED IN EACH TENANT SPACE.
 THE WATER COOLER SHOWN ON THE FLOOR PLAN DOES NOT MEET
 THE REQUIREMENT FOR A DRINKING FOUNTAIN. SECTION 410.1.
 PLEASE SHOW THE LOCATIONS OF THE SERVICE SINKS AND THE
 DRINKING FOUNTAINS ON THE FLOOR PLAN, SANITARY RISER
 DIAGRAM & THE WATER RISER DIAGRAM. SECTION 403.6.
  
 3. SHT A-3 BATHROOM ELEVATIONS. SHOW COMPLIANCE WITH
 THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS (BEHIND W/C)
 D. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 4. SHT A-3 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. PLEASE SUBMIT A RISER DIAGRAM THAT WOULD
 REFLECT THE ACTUAL INSTALLATION. SECTION 106.3.5.1.3.
  
 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM THAT REFLECT
 THE FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES ETC.
 SECTION 106.3.5.1.3(3)(13).
  
 6. PER SECTION 607.1 HOT WATER IS REQUIRED FOR BUILDING
 MAINTENANCE.
  
 7. SHT A-2 PER SECTION 1503.6 GUTTERS WITH DOWNSPOUTS
 ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS THAN 6
 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES
 OR ON A ROOF ABOVE ANOTHER ROOF. PLEASE INDICATE GUTTER
 SIZE AND DOWNSPOUT SIZE AND WELL AS SQUARE FOOTAGE
 BEING DRAINED. DOWNSPOUTS SHALL DISCHARGE A MINIMUM 1
 FOOT FROM THE STRUCTRUE SIDEWALLS OF BUILDING.
  
 8. INFORMATIONAL: AN IRRIGATION PERMIT AND PLANS ARE
 REQUIRED. THIS CAN BE SUBMITTED BY THE IRRIGATION
 CONTRACTOR SEPARATELY AFTER BLDG PERMIT IS ISSUED.
 SECTION 106.3.5.1.3.
  
 9. SHTS L-1 & L-2 THE CERTIFICATE OF AUTHORIZATION,
 (FIRM LICENSE), IS REQUIRED IN THE TITLE BLOCK OF THE
 LANDSCAPE ARCHITECT PER FAC 61G1_16.004(2) & FS
 481.306.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop X PERMIT EXTENSION
Rev No 1 Status   Date 2008-10-21 Cont ID  
Sent By dfulcher Date 2008-10-21 Time 14:56 Rev Time 0.00
Received By dfulcher Date   Time   Sent To  
Notes
2008-10-21 14:55:52APP EXTENDED TO JAN 13, 2009 PY

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-25 Cont ID  
Sent By lfranco Date 2008-03-25 Time 17:38 Rev Time 0.00
Received By lfranco Date 2008-03-25 Time 17:38 Sent To  
Notes
2008-03-25 17:45:00PLANNING AND ZONING: **** PASSED WITH PROVISO ****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2. THERE SHALL BE A 2-FOOT CLEARANCE BETWEEN THE
 BACK OF THE WHEEL STOP AND THE SIDEWALK OR CURB. PLACE
 HANDICAP SYMBOL'S BOTTOM, 2 FEET FROM THE EDGE OF THE
 PARKING STRIPE.REFER TO MARK-UPS ON SHEETS C-1 AND
 C-3.RE-SUBMIT SHEETS WITH CHANGES ACCORDINGLY.A
 COPY OF THE PARKING DETAIL IS ATTACHED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME BELOW.
  
 LINDA MIAFRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]