Plan Review Details - Permit 08030142
Plan Review Stops For Permit 08030142
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-29 Cont ID  
Sent By mjacobs Date 2008-04-29 Time 07:49 Rev Time 0.00
Received By mjacobs Date 2008-04-29 Time 06:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-09 Cont ID  
Sent By mjacobs Date 2008-04-09 Time 18:42 Rev Time 0.00
Received By mjacobs Date 2008-04-09 Time 17:39 Sent To PC
Notes
2008-04-09 18:46:06BUILDING PLAN REVIEW #2
 PERMIT: 08030142
 ADD: 230 MIRAMAR WAY
 CONT: SCHMIDT ELECTRIC, INC.
 TEL: (561)588-6881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 4-9-08
 ACTION: DENIED
  
 1)OK
  
 *NO RESPONSE NOT ADDRESSED*
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 *NO RESPONSE NOT ADDRESSED*
 3)1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR.
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF TO BE USED FOR THE SELECTION OF
 EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 **THE TRACED SIGNATURE OVER THE PHOTO-COPY SIGNATURE IS
 NOT ACCEPTABLE. OUR OFFICE WILL RETAIN ONE REPORT AS
 EVIDENCE**
 4)61G15-23.002A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS PROVIDED
 TO THE OWNER OR THE OWNER?S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT AND
 BEING FILED FOR PUBLIC RECORD. THE SHEET WITH P.E.
 #22920 NEEDS TO BE SIGN DATED AND SEALED BY THE
 INDIVIDUAL.
  
 **THE TRACED SIGNATURE OVER THE PHOTO-COPY SIGNATURE IS
 NOT ACCEPTABLE.**
 5)THE LETTER FROM STRUCTURAL ENGINEER SONIA TORRES
 REQUIRES AN ORIGINAL SIGNATURE, PHOTOCOPY SIGNATURES
 ARE NOT ACCEPTABLE. ALL INFORMATION BEING FILED FOR
 PUBLIC RECORD SHALL CONTAIN THE ORIGINAL SIGNATURE OF
 THE RESPONSIBLE PERSON.
  
 61G15-23.002EACH SHEET OF PLANS AND PRINTS WHICH MUST
 BE SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S.,
 SHALL BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-15 Cont ID  
Sent By mjacobs Date 2008-03-15 Time 13:24 Rev Time 0.00
Received By mjacobs Date 2008-03-15 Time 11:35 Sent To PC
Notes
2008-03-15 13:24:03BUILDING PLAN REVIEW
 PERMIT: 08030142
 ADD: 230 MIRAMAR WAY
 CONT: SCHMIDT ELECTRIC, INC.
 TEL: (561)588-6881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON
 THE ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING.
  
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 PLEASE PROVIDE A SITE PLAN INDICATE PROVIDE PLANS
 ENOUGH TO VERIFY LOCATION OF GENERATOR VERSES BUILDING
 OPENINGS WINDOWS, DOORS OR SOFFIT TYPE VENTS, ETC.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR.
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF TO BE USED FOR THE SELECTION OF
 EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4)61G15-23.002A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS PROVIDED
 TO THE OWNER OR THE OWNER?S REPRESENTATIVE, OR OTHER
 DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT AND
 BEING FILED FOR PUBLIC RECORD. THE SHEET WITH P.E.
 #22920 NEEDS TO BE SIGN DATED AND SEALED BY THE
 INDIVIDUAL.
  
 5)THE LETTER FROM STRUCTURAL ENGINEER SONIA TORRES
 REQUIRES AN ORIGINAL SIGNATURE, PHOTOCOPY SIGNATURES
 ARE NOT ACCEPTABLE. ALL INFORMATION BEING FILED FOR
 PUBLIC RECORD SHALL CONTAIN THE ORIGINAL SIGNATURE OF
 THE RESPONSIBLE PERSON.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By btrobaug Date 2008-04-08 Time 16:06 Rev Time 0.00
Received By btrobaug Date 2008-04-08 Time 15:58 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-03-11 Cont ID  
Sent By btrobaug Date 2008-03-11 Time 10:40 Rev Time 0.00
Received By btrobaug Date 2008-03-11 Time 10:24 Sent To M
Notes
2008-03-11 10:39:30 
  
  
 PROVISO
  
 225.31 DISCONNECTING MEANS
 MEANS SHALL BE PROVIDED FOR DISCONNECTING ALL
 UNGROUNDED CONDUCTORS THAT SUPPLY OR PASS THROUGH THE
 BUILDING OR STRUCTURE.
 225.32 LOCATION
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED
 OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR
 STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A
 READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS
 SECTION, THE REQUIREMENTS IN 230.6 SHALL BE UTILIZED.
  
 ALL GENERATOR CONDUCTORS MUST BE CAPABLE OF BEING
 DISCONNECTED ELECTRICALLY ON THE OUTSIDE OF THE
 BUILDING WITHOUT GOING TO THE ROOF TO DISCONNECT THE
 BREAKER AT THAT POINT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-04-28 Cont ID  
Sent By mperson Date 2008-04-28 Time 13:29 Rev Time 0.00
Received By mperson Date 2008-04-28 Time 13:29 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-04-08 Cont ID  
Sent By mperson Date 2008-04-08 Time 16:44 Rev Time 0.00
Received By mperson Date 2008-04-08 Time 16:42 Sent To M
Notes
2008-04-08 16:54:53GAS PLAN REVIEW:
 DENIED 2ND TIME
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NOTE: THERE WERE NO COMMENT RESPONSES FROM THE
 DESIGNER.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. CORRELATE THE PLANS WITH THE CORRECT BTU LOAD FOR
 THE PROPOSED GENERATOR (NOTE: GENERATOR SUBMITTAL
 INDICATES 375,000 BTU'S) AND CORRECT THE TOTAL BTU LOAD
 AS BEING 1,399,000 ALSO DELETE "FUTURE" STATUS FOR
 GENERATOR BECAUSE GENERATOR IS PERMANENT. PER FBC FUEL
 GAS SECTION 401.1 SCOPE.
 **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED. THE GAS
 DRAWINGS SUBMITTED BY THE CONTRACTOR (ENTERPRISE
 PLUMBING) NEED TO HAVE THE PRINTED NAME, SIGNED NAME
 AND THE DATE OF THE PERSON TAKING RESPONSIBILITY OF THE
 DRAWINGS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-03-11 Cont ID  
Sent By mperson Date 2008-03-11 Time 15:05 Rev Time 0.00
Received By mperson Date 2008-03-11 Time 15:05 Sent To B
Notes
2008-03-11 15:08:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/RES
 PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE
 PROPOSED GENERATOR LOCATION. **ZONING FAILED PERMIT
 APPLICATION 3/10/08.
  
 2. CORRELATE THE PLANS WITH THE CORRECT BTU LOAD FOR
 THE PROPOSED GENERATOR (NOTE: GENERATOR SUBMITTAL
 INDICATES 375,000 BTU'S) AND CORRECT THE TOTAL BTU LOAD
 AS BEING 1,399,000 ALSO DELETE "FUTURE" STATUS FOR
 GENERATOR BECAUSE GENERATOR IS PERMANENT. PER FBC FUEL
 GAS SECTION 401.1 SCOPE.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-23 Cont ID  
Sent By adarroug Date 2008-04-23 Time 15:57 Rev Time 0.00
Received By adarroug Date 2008-04-23 Time 15:57 Sent To G
Notes
2008-04-23 15:58:14TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 14:15 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 14:15 Sent To Z
Notes
2008-04-03 14:16:20TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-03-15 Time 14:04 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 11:26 Sent To  
Notes
2008-03-07 11:27:02TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-09 Cont ID  
Sent By tgordon Date 2008-04-09 Time 13:54 Rev Time 0.20
Received By tgordon Date 2008-04-09 Time 13:54 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-03-11 Cont ID  
Sent By tgordon Date 2008-03-11 Time 11:58 Rev Time 0.20
Received By tgordon Date 2008-03-11 Time 11:58 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-04 Cont ID  
Sent By choops Date 2008-04-04 Time 16:05 Rev Time 0.00
Received By choops Date 2008-04-04 Time 16:05 Sent To E
Notes
2008-04-04 16:05:51***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By choops Date 2008-03-10 Time 14:42 Rev Time 0.00
Received By choops Date 2008-03-10 Time 14:42 Sent To E
Notes
2008-03-10 14:44:17***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF AN ELEVATION PLAN
 SHOWING THE HEIGHT OF THE PROPOSED GENERATOR, MEASURED
 FROM GRADE.NOTE: SHALL NOT EXCEED THE DISTRICT HEIGHT
 LIMIT OF 30 FEET.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - GENRES. BOX