Plan Review Details - Permit 08030139
Plan Review Stops For Permit 08030139
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-03 Cont ID  
Sent By rmcdouga Date 2008-04-02 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2008-04-02 Time 16:22 Sent To  
Notes
2008-04-02 16:24:28LEFT MESSAGE FOR CONTRACTOR / NEED STORM PANEL
 INSTALLATION INFORMATION AND NOC.
  
 4/3/08 CONTRACTOR CALLED AND PROVIDED STORM PANEL
 INSTALLATION INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-12 Cont ID  
Sent By rmcdouga Date 2008-03-12 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2008-03-11 Time 12:32 Sent To E
Notes
2008-03-12 07:40:282004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE PLANS WITH THE ENGINEER'S TITLE BLOCK IS
 REQUIRED TO BE SIGNED SEALED AND DATED BY THE ENGINEER.
 FS 471 AND FBC 106.1* CITY AMENDMENTS
  
 3) PROVIDE STRUCTURAL DETAILS FOR THE NEW DOOR OPENING
 AT THE EXISTING WINDOW. PROVIDE BUCK DETAILS.FBC
 106.1.1* CITY AMENDMENTS
  
 4) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE
 NEW DOOR AND NEW WINDOWS THAT WERE MISSED. FBC TABLE R
 301.2(2)
  
 5) SPECIFY WHICH WINDOWS ARE SINGLE HUNG AND CASEMENT.
 FBC 106.1.1* CITY AMENDMENTS
  
 6) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW
 MULLIONS AS REQUIRED BY RULE 9B-72 F.A.C.
  
 7) SUBMIT TWO (2) COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE CONNECTION
 TYPE, FASTENER TYPE AND SPACING, EDGE DISTANCE, SPANS,
 ETC. SEE SAMPLE SCHEDULE ATTACHED.
  
 8) SHOW COMPLIANCE WITH R311.6.3 HANDRAILS REQUIRED.
 HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF ALL
 RAMPS EXCEEDING A SLOPE OF ONE UNIT VERTICAL IN 12
 UNITS HORIZONTAL (8.33-PERCENT SLOPE).
  
 9) SHOW COMPLIANCE WITH R 311.6.3.2 HANDRAIL GRIP SIZE
 AND R311.6.3.3 CONTINUITY.
  
 10) AN EXTERIOR LIGHT FIXTURE WITH A SWITCH IS REQUIRED
 AT THE NEW EXTERIOR DOOR PER THE 2005 NEC SECTION
 210.70(2)(B).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-27 Cont ID  
Sent By btrobaug Date 2008-03-27 Time 13:01 Rev Time 0.00
Received By btrobaug Date 2008-03-27 Time 11:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-13 Cont ID  
Sent By btrobaug Date 2008-03-13 Time 13:37 Rev Time 0.00
Received By btrobaug Date 2008-03-13 Time 13:27 Sent To I
Notes
2008-03-13 13:36:49 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} 210.70(A) (2) (B) FOR DWELLING UNITS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER, AT
 LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL
 ACCESS. A VEHICLE DOOR IN A GARAGE SHALL NOT BE
 CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT. SHOW
 COMPLIANCE AT THE NEW DOOR LOCATION.
  
 2} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 13:12 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 13:12 Sent To Z
Notes
2008-03-25 13:13:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-13 Cont ID  
Sent By btrobaug Date 2008-03-13 Time 14:01 Rev Time 0.00
Received By btrobaug Date 2008-03-07 Time 11:19 Sent To PC
Notes
2008-03-07 11:19:57TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-27 Cont ID  
Sent By choops Date 2008-03-27 Time 08:34 Rev Time 0.00
Received By choops Date 2008-03-27 Time 08:34 Sent To E
Notes
2008-03-27 08:34:36***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-11 Cont ID  
Sent By choops Date 2008-03-11 Time 09:21 Rev Time 0.00
Received By choops Date 2008-03-11 Time 09:21 Sent To B
Notes
2008-03-11 09:25:13***FAILED***
  
  
 1)PLANS INCONSISTENT.EXISTING SIDE SETBACKS DO NOT
 MATCH BETWEEN SURVEY AND SITEPLAN AND DO NOT MAKE SENSE
 GIVEN THE SIZE OF THE PROPOSED RAMP.PLEASE CLARIFY.
 ALSO INDICATE THE SETBACK DIMENSION FROM THE PROPOSED
 RAMP TO THE SIDE PROPERTY LINE.NOTE:MUST MAINTAIN A
 MINIMUM 2 FOOT SETBACK TO SIDE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - MISC. 2