Plan Review Stops For Permit 08030069
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-02-03 Cont ID  
Sent By jwitmer Date 2009-02-03 Time 07:26 Rev Time 0.79
Received By jwitmer Date 2009-02-03 Time 07:26 Sent To  
Notes
2009-02-03 07:34:17FIELD DIRECTIVE# 13
 1.1 CONTRACTOR SUPPLIED DETAIL# 1 DIAGONAL BRACING FOR
 INTERIOR (NON-STRUCTURAL) PARTITIONS.
 1.2 CONTRACTOR SUPPLIED DETAIL# 2 POST TO DECK
 CONNECTIONDETAIL.
  
 FIELD DIRECTIVE# 11
 1.1 THIS FIELD DERECTIVE REPLACES FIELD DIRECTIVE# 9
 ENTIRELY.
 1.2 SKETCH 1OF 2 STOREFRONT DIAGONAL BRACING AT RIBS.
 THIS DETAIL IS TO MODIFY EXISTING CONNECTION TO MEET
 STOREFRONT WIND LOADINGREQUIREMENTS. SIGNED AND RAISED
 SEAL
 1.3 SKETCH 2 OF 2 STOREFRONT DIAGONAL BRACING BETWEEN
 RIBS. THIS DETAIL IS TO MODIFY EXISTING CONNECTION TO
 MEET WIND LOAD REQUIREMENTS. SIGNED AND RAISED SEAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2009-01-14 Cont ID  
Sent By jwitmer Date 2009-01-14 Time 10:03 Rev Time 0.44
Received By jwitmer Date 2009-01-14 Time 10:03 Sent To B
Notes
2009-01-14 10:12:37BUILDING PLAN REVIEW
 PERMIT: 08030069
 ADD: 700 S ROSEMARY "VICTORIA SECRETS"
 CONT: RCC
 TEL: (561)818-7777
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 CONTRACTOR SUPPLIED DETAILS REVIEW
 ACTION: DENIED
  
 1) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC... PLEASE HAVE THE ARCHITECT OF
 RECORD REVIEW SHOP DRAWINGS, STAMP THE DRAWINGS WITH
 THEIR SHOP DRAWING STAMP OF APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-01-14 Cont ID  
Sent By jwitmer Date 2009-01-14 Time 10:02 Rev Time 0.44
Received By jwitmer Date 2009-01-14 Time 10:02 Sent To PC
Notes
2009-01-14 10:03:36OK- FIELD DIRECTIVE# 11 2 HEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-01-02 Cont ID  
Sent By jwitmer Date 2009-01-02 Time 17:50 Rev Time 1.00
Received By jwitmer Date 2009-01-02 Time 17:00 Sent To PC
Notes
2009-01-02 17:54:27JAN. 02-2009 5:00-6:00PM
 EXPEDITED OVERTIME REVIEW:
 STOREFRONT CONNECTION DETAILS GLAZING SUPPORT DETAILS
 SKETCH B & C WITH SUPPORTING SCREW ATTACHMENT
 CALCULATIONS FOR WOOD & STEEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-02 Cont ID  
Sent By jwitmer Date 2009-01-02 Time 12:18 Rev Time 0.66
Received By jwitmer Date 2009-01-02 Time 12:18 Sent To  
Notes
2009-01-02 12:28:42FIELD DECECTIVE# 8 AND UL WALL LISTINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-01-02 Cont ID  
Sent By jwitmer Date 2008-12-11 Time 12:16 Rev Time 2.22
Received By jwitmer Date 2008-12-11 Time 12:16 Sent To  
Notes
2009-01-02 12:17:46REVISION RELEASING CAPRI FROM PRIVATE PROVIDERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-01 Cont ID  
Sent By jwitmer Date 2008-07-01 Time 14:30 Rev Time 2.22
Received By jwitmer Date 2008-07-01 Time 14:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-29 Cont ID  
Sent By jwitmer Date 2008-04-29 Time 14:09 Rev Time 2.22
Received By jwitmer Date 2008-04-29 Time 14:09 Sent To  
Notes
2008-04-29 14:10:24BUILDING PLAN REVIEW
 PERMIT: 08020069
 ADD: 700 S ROSEMARY AV# 108
 CONT: RCC ASSOCIATES INC
 TEL: (954)429-3700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)2ND REQUEST, NO RESPONSE LETTERS WERE SUBMITTED.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2-6) COMPLIED.
  
 7) 2ND REQUEST,SHEET S04.1 DETAIL C,D & LPLEASE
 PROVIDE ADDITIONAL INFORMATION ON THE FLOOR SHEATHING
 PRODUCT CONCRETE BONDED PARTICLE BOARD, PROVIDE THE
 THICKNESS OF THE PRODUCT SPAN RATINGS , ADDITIONAL
 INFORMATION REQUIRED 106.1.2. DURAROCK CEMENT BOARD,
 CCMC EVALUATION REPORT 10788-RUNDER USAGE AND
 LIMITATIONS DURAROCK CEMENT BOARD MAY BE USED AS A
 NON-STRUCTURALBACKER BOARD. PLEASE PROVIDE A REPORT
 INDICATING THIS PRODUCT CAN BE USED AS A STRUCTURAL
 COMPONENT.
  
 8)2ND REQUEST, SHEET S04.1 PROVIDE COMPUTATIONS WITH AN
 AFFIDAVIT FROM THE ARCHITECT OR ENGINEER STATING THE
 SAFE ALLOWABLE FLOOR LOAD ON EACH FLOOR (DECK ABOVE
 RESTROOMS) IN POUNDS PER SQUARE FOOT UNIFORMLY
 DISTRIBUTED. 110.4.2.
  
 110.4.3 SIGN REQUIRED, IN EVERY BUILDING OR PART OF
 BUILDING USED FOR STORAGE THE SAFE FLOOR LOADS AS
 REVIEWED BY THE BUILDING OFFICIAL ON THE PLANS, SHALL
 BE MARKED ON PLATES OF APPROVED DESIGN WHICH SHALL BE
 SUPPLIED AND SECURELY AFFIXED BY THE OWNER OF THE
 BUILDING IN A CONSPICUOUS PLACE IN EVERY STORY WHICH IT
 RELATES.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-21 Cont ID  
Sent By jwitmer Date 2008-03-21 Time 07:35 Rev Time 4.55
Received By jwitmer Date 2008-03-18 Time 11:41 Sent To PC
Notes
2008-03-21 07:36:54BUILDING PLAN REVIEW
 PERMIT: 08020069
 ADD: 700 S ROSEMARY AV# 108
 CONT: RCC ASSOCIATES INC
 TEL: (954)429-3700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S. S. 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) ARCHITECT CHRIS DOERSCHLAG IS MISSING THE FOLLOWING
 INFORMATION IN THE TITLE BLOCK.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 XX - STATE PROJECT NAME OR IDENTIFICATION SUITE NUMBER
 - STATE DATE PREPARED
 XX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL -
 INCLUDE THE PRINTED NAME OF THE
 ARCHITECT & SEAL NUMBER SEALING THE PLANS.
  
 3)SHEET A00.3 CODE SYNOPSIS PLEASE CORRECT THE
 CORRELATION FROM THE 2001 FBC TYPE
 II SPRINKLED FROM 2004 FBC TYPE II-A TO 2004 FBC TYPE
 I-B, SEE CODE COMMENTARY
 FIGURE 600.
  
 4) SHEET A00.3 KEY NOTES REFERS TO THE SSMA (STEEL STUD
 MANUFACTURERS ASSOCIATION)
 AS THE REFERENCEDSTANDARD. PLEASE SEE TABLE 2508.1
 STEEL FRAMING FOR GYPSUM BOARD.
 ASTM C 754 FOR NON-LOAD BEARING WALLS 5.3.1.2/ NOTE 1
 REFERS TO APPENDIX X1.
 ASTM C 1007 FOR LOAD BEARING WALLS.
 GA -216
  
 5)A01.1 DEMOLITION NOTE 15 IS STRUCK THROUGH
 APPEARING TO REMOVE IT FROM THE SCOPE OF WORK, BUT
 A02.1 INDICATES A NEW DOORWAY AND RATED WALLS.
 DISCREPANCY, PLEASE PROVIDE ADDITIONAL INFORMATION,
 106.1.2. PROVIDE RATING OF DOOR AND WALL.
  
 6) A01.1 DEMOLITION NOTE 23 INDICATES TWO DOORS ARE TO
 BE WELDED SHUT, PLEASE SEE NFPA 80- 5.2.4 (3)DOOR ,
 FRAME HINGES, HARDWARE AND NONCOMBUSTIBLE THRESHOLD ARE
 SECURED, ALIGNED AND IN WORKING ORDER WITH NO VISIBLE
 SIGNS OF DAMAGE.
  
  
 NFPA 80- 5.2.4.2 (10) NO FIELD MODIFICATIONS TO THE
 DOOR ASSEMBLY HAVE BEEN PREFORMED THAT VOID THE LABEL.
  
 7)SHEET S04.1 DETAIL C,D & LPLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE FLOOR SHEATHING PRODUCT
 CONCRETE BONDED PARTICLE BOARD, PROVIDE THE THICKNESS
 OF THE PRODUCT SPAN RATINGS AND FIRE RATING IS THIS
 PRODUCT FIRE RETARDANT TREATED, ADDITIONAL INFORMATION
 REQUIRED 106.1.2.
  
 8) SHEET S04.1 PROVIDE COMPUTATIONS WITH AN AFFIDAVIT
 FROM THE ARCHITECT OR ENGINEER STATING THE SAFE
 ALLOWABLE FLOOR LOAD ON EACH FLOOR (DECK ABOVE
 RESTROOMS) IN POUNDS PER SQUARE FOOT UNIFORMLY
 DISTRIBUTED. 110.4.2.
  
 110.4.3 SIGN REQUIRED, IN EVERY BUILDING OR PART OF
 BUILDING USED FOR STORAGE THE SAFE FLOOR LOADS AS
 REVIEWED BY THE BUILDING OFFICIAL ON THE PLANS, SHALL
 BE MARKED ON PLATES OF APPROVED DESIGN WHICH SHALL BE
 SUPPLIED AND SECURELY AFFIXED BY THE OWNER OF THE
 BUILDING IN A CONSPICUOUS PLACE IN EVERY STORY WHICH IT
 RELATES.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-02-05 Cont ID  
Sent By dpalmer Date 2009-02-05 Time 13:12 Rev Time 0.00
Received By dpalmer Date 2009-02-05 Time 13:12 Sent To PC
Notes
2009-02-05 13:12:50NO GROSS ERRORS

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2009-01-28 Cont ID  
Sent By dpalmer Date 2009-01-28 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2009-01-28 Time 13:59 Sent To B
Notes
2009-01-28 13:59:44** DENIED PLANS/REVISIONS**
  
 1) NOTE: SEE THE NOTES FROM THE PREVIOUS ELECTRICAL
 REVIEW. THE METHOD *C* CALCULATIONS ARE STILL BEING
 SUBMITTED. THESE MAY HAVE BEEN LEFT OVER FROM PREVIOUS
 REVIEW AND SHOULD BE REMOVED.
 THE NEW SUBMITTED METHOD *B* IS NOT SEALED BY THE
 DESIGN PROFESSIONAL AS REQUIRED. FS 471.025/ FAC
 61G15-23.002, FBC 13-101
 THE NEW THE METHOD *B* DOES NOT HAVE ANY INPUT DATA
 REPORT ATTACHED TO THE SUMMARY SHEETS. THIS WAS ALSO A
 COMMENT FROM THE PREVIOUS REVIEW. THE COMPLIANCE
 SUMMARY SHEET #2 STATES THE * INPUT DATA REPORT MUST BE
 SUBMITTED*. IN ORDER FOR CODE COMPLIANCE REVIEW TO TAKE
 PLACE THIS OFFICE MUST HAVE THE IDR TO REVIEW WITH THE
 SUBMITTED PLANS.
  
 2) NOTE: THE BEAUTY CASES ARE NOT MANUFACTURED WITH
 LIGHTING INSTALLED FROM THE MANUFACTURE. BASED ON THE
 PRODUCT SHEETS SUBMITTED THESE ARE LIGHT FIXTURES ADDED
 TO GENERAL DISPLAY CASES/RACKS.13-415.2.ABC.1. THERE IS
 ALLOWANCES PERMITTED FOR ADDITIONAL LIGTHING FOR
 DSIPLAY AREAS HOWEVER SEE 13-415.2.B.2. PLEASE
 RE-CONFIGURE CALCULATIONS.
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 14:11 Sent To  
Notes
2008-12-24 14:11:22** DENIED REVIEW OF REVISIONS**
  
  
 1) NOTE: METHOD *C* FLA-COMM SUBMITTED DOES NOT CONTAIN
 ANY INPUT DATA REPORT. THE DESIGN WATTAGE IS HIGHER
 THAN ALLOWANCE PER FBC 13-415.2.ABC.1.1,.1.2, TABLE
 13-415.2.C.
 PLEASE SEE PLANS WHICH CONTAINS METHOD *B* TABLE
 13-415.2.B FOR COMPLIANCE WHICH HAS NOT BEEN UPDATED
 FOR CHANGES IN LIGHTING ON PLANS.
 PLEASE SEE 13-415.2.ABC.1. IT IS NOT PERMISSIBLE BY
 CODE TO USE MULTIPLE METHODS OF ENERGY CALCULATIONS TO
 TRY AND ACHIEVE CODE COMPLIANCE.
  
 ** PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR
 BEAUTY CASES IN WHICH EXEMPTION IN 13-415.2.ABC.1 IS
 BEING APPLIED.
 110.3, 90.7.
 FBC 13-415.2.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE SUBMIT COMPLETE UPDATE AND REVISED
 PLANS FOR CODE COMPLIANCE. THE INPUT DATA REPORT AS
 STATED ON SHEET TWO OF THE SUBMITTED CALCULATIONS MUST
 ACCOMPANY THE SUBMITTED DOCUMENTS. NO REVIEW FOR CODE
 COMPLIANCE CAN BE ACHIEVED.
 FBC 106.1.1 FOR COMPLETE INFORMATION, CLARITY AND
 COORDINATION.
 CODE SECTIONS NOTED IN NOTE #1.
  
 3) NOTE: FEE DUE FOR ENERGY CALCULATIONS SUBMITTED AS A
 SUBMITTAL. THIS IS ACTUALLY A REVISION TO BE REVIEWED
 AND COORDINATED WITH PLANS SUBMITTED.
  
 4) NOTE: LETTERS SUBMITTED BY CITY PLACE AND RCC WERE
 NOT CORRECTLY NOTARIZED PER FS 117.05. PLACING THE
 NOTARY STAMP ON LETTER AND SIGNING IS NOT THE ONLY
 INFORMATION REQUIRED. LETTER FROM RCC DOES CONTAIN SOME
 MORE INFORMATION HOWEVER NOT ALL. A COMPLETED STATEMENT
 IN SECTION GIVEN CAN BE VIEWED ON LINE AT STATE
 WEBSITE. THE INFORMATION CAN BE FOUND IN SECTION
 117.05(12)(B).
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-08-14 Cont ID  
Sent By dpalmer Date 2008-08-14 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2008-08-14 Time 14:01 Sent To PC
Notes
2008-08-14 14:02:29METHOD B CALCS SENT BACK WITH ALL OLD/VOIDED DOCUMENTS
 AS THE PERFORMANCE CALCULATIONS ARE SHOWN ON PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-26 Cont ID  
Sent By dpalmer Date 2008-06-26 Time 17:03 Rev Time 0.00
Received By dpalmer Date 2008-06-26 Time 17:03 Sent To  
Notes
2008-06-26 17:03:35** DENIED3RD AUDIT **
  
  
 1) NOTE:PLEASE SEE THE SUBMITTED FLA-COM ENERGY
 CALCULATIONS STATES METHOD *C* HOWEVER PLEASE SEE
 13-415.2.C, 13-415.2.C.1. THE SUBMITTED CALCULATIONS
 ARE NOT CODE COMPLIANT BASED ON *C* AS METHOD C FOR
 AREA ONLY ALLOWS 1.5 WATTS/PER/SQFT.
 BASED ON THE SQUARE FOOTAGE THIS WOULD BE SUBSTANTIALLY
 LOWER THAN THE DESIGN WATTAGE OF JUST OVER
 18,000WATTS.
 THE OTHER ITEM IS THE SHEET ON PLANS SHOWS SPACE BY
 SPACE FOR METHOD *B*.PLEASE SEE THE SALES AREA AS A
 TOTAL IS SHOWING 2.1 WATTS/PER/SQFT ALLOWANCE WHICH
 EXCEEDS THE MAXIMUM ALLOWANCES ON TABLE 13-415.2.B.
 PLEASE LOOK AT SALES AREAS ON THE TABLE WHICH HAS A
 BASE ALLOWANCE OF 1.7, NOT 2.1.
 WHICH IS GOING TO BE USED?
 PLEASE SEE 13-415.2.ABC.1.1, .1.2, .1.3.
  
 BASED ON ALL CODE SECTIONS GIVEN ABOVE AND BASED ON THE
 FACT THE LIGHTING DESIGN IS SUBSTANTIALLY OVER THE
 MAXIMUM ALLOWANCES ALLOWED BY THE CODE.
 THIS AUDIT SHALL BE PLACED INTO A FAILED STATUS FOR THE
 THIRD TIME.
  
 2) NOTE: PLEASE SEE AREAS AROUND DRESSING ROOMS. WHERE
 IS THE LIGHTING CONTROL? THIS IS ONE EXAMPLE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR ALL
 REQUIRED CONTROLS ONCE AGAIN.
  
 3) NOTE: PLEASE SEE ONE SET OF THE SUBMITTED FLA COM
 CALCULATIONS WERE INDEED PHOTO-COPIES AND NOTE
 ORIGINAL.
 FAC 61G15-23.002, FS 471.025
  
 ** PLEASE KNOW ELECTRICAL LIGHTING SHEETS, ELECTRICAL
 SHEETS WITH LIGHTING CALCULATIONS AS WELL AS FLACOM
 CALCULATIONS HAVE BEEN RETAINED BY THIS OFFICE.
  
 ** A CALL WAS PLACED TO THE ENGINEERED SIGNED AND
 SEALED ON PLANS AS OF THIS REVIEW. MR. VAN STRATEN WAS
 IN NEED OF LOCATING THE ELECTRICAL DESIGNER WHO WORKED
 ON PROJECT.HE WAS NOT ABLE TO GO OVER COMMENTS.
  
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-05 Cont ID  
Sent By dpalmer Date 2008-05-05 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2008-05-05 Time 10:13 Sent To PC
Notes
2008-05-05 10:14:07** DENIEDAUDIT **
  
 1) NOTE: PLEASE SEE THE NOTICE TO BUILDING OFFICIAL
 NEEDS TO COORDINATE WITH THE SIGNED AFFIDAVITS. PLEASE
 SEE THESE SHOW SEPARATE PRIVATE PROVIDERS AS THE
 RESPONSIBLE ENGINEERS.
 PLEASE SUBMIT.
 FS 553.791
  
 2) NOTE: PLEASE SEE THE AFFIDAVITS DO NOT LIST THE
 ENERGY/PERFORMANCE CALCULATIONS.
 FS553.791
  
 3) NOTE: PLEASE SEE ONLY ONE COPY OF THE CALCULATIONS
 DATED 2/4/08 WERE SUBMITTED.
 PLEASE SEE THE SUBMITTED INPUT DATA REPORT WHICH
 FOLLOWS DOES NOT CORRELATE WITH LIGHTING ON PLANS. IN
 FACT THERE ARE SEVERAL LIGHT FIXTURES ON PLANS WHICH
 ARE NOT ON THE IDR.
 PLEASE SEE FOR EXAMPLE: PLANS CLEARLY SHOW EXTERIOR
 LIGHTS, HOWEVER THE IDR DO NOT INDICATE ANY LIGHTS.
 THIS IS ACTUALLY BLANK.
 PLEASE SEE 13-415.2.ABC.1.3.
 PLEASE SEE FOR EXAMPLE:
 TRACK LIGHTS ARE NOT SHOWN PER 13-415.2.ABC.1.1, .1.2.
  
 ** THESE ARE ONLY SOME EXAMPLES AND IS NOT AN EXHAUSTED
 LIST OF ALL ITEMS WHICH DO NOT CORRELATE WITH PLANS.
  
 4) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW. THERE
 IS NOT ENOUGH INFORMATION FOR REVIEW OF THE REQUIRED
 LIGHTING CONTROL SYSTEM. THE RESPONSE LETTER STATES
 THREE OVER RIDES WERE ADDED HOWEVER WHERE ARE THE
 LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2,
 .1.3 AND .1.4?
 THERE ARE A COUPLE OF NOTES ON PLANS WHICH MENTIONS
 THERE WILL BE SOME SORT OF LIGHTING CONTROLS HOWEVER
 PLACING NOTES ON PLANS IN LIEU OF SHOWING CODE
 COMPLIANCE IS NOT PERMITTED.
 THE RESPONSE LETTER ALSO STATES IT IS *NOT CAPABLE* TO
 SHOW ZONES. THIS OFFICE DOES NOT UNDERSTAND HOW MEETING
 * MINIMUM REQUIRED* BY CODE IS NOT POSSIBLE.
 ONE AGAIN PLEASE SHOW COMPLETE LIGHTING CONTROL(S)
 SYSTEM(S) PER SECTIONS GIVEN ABOVE.
  
 5) NOTE: PLEASE SEE SECTION NOTED ABOVE FOR EXTERIOR
 LIGHTS PER 13-415.1.ABC.1.4.
 PLEASE COMPLETE WITH ONE OF THE TWO MINIMUM REQUIRED BY
 CODE.
  
 6) NOTE: PLEASE SEE COMMENT #9 FROM PREVIOUS REVIEW.
 PLEASE SEE ONCE AGAIN THESE ARE *STANDARD SWITCHES*
 BEING NOTED IN THE SPECIFICATIONS.
 SEE NOTE #4 ABOVE.
  
 7) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE IS
 GIVEN.
 FS 553.80(2)(B) IS APPLICABLE TO ANY PROJECT AS IT IS
 FOR THE DESIGN PROFESSIONAL WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By dpalmer Date 2008-03-08 Time 23:40 Rev Time 0.00
Received By dpalmer Date 2008-03-08 Time 23:40 Sent To  
Notes
2008-03-08 23:40:432008-03-08 23:40:43
  
 ** DENIED REVIEW **
  
 *** PLEASE KNOW THAT SUBMITTED DOCUMENTS ARE NOT
 COMPLETE AT THIS TIME.
  
 1) NOTE: PLEASE SEE COVER SHEET A0.00 WHICH STATES
 NFPA-70 2005 AS THE SPRINKLER CODE WHEN NFPA-70 IS THE
 NATIONAL ELECTRICAL CODE. PLEASE SEE THIS SAME COVER
 SHEET STATES NFPA-101 2003 ALSO AS THE SPRINKLER CODE
 WHICH IS ALSO NOT POSSIBLE. THE 2003 NFPA-101 IS THE
 LIFE SAFETY CODE.
 PLEASE ADJUST ON COVER SHEET AND IN PLANS AS NEEDED.
 PLEASE BE SURE THE FOLLOWING RELEVANT CODES ARE STATED
 ON ELECTRICAL PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE FLA-COM ENERGY CALCULATIONS
 SUBMITTED WHICH DO NOT CONTAIN ANY INPUT DATA REPORT.
 PLEASE SEE SHEET WHICH SPECIFICALLY STATES THE IDR MUST
 BE SUBMITTED. A REVIEW OF COORDINATION WITH THE ACTUAL
 ITEMS ON PLANS CAN NOT BE DONE AT THIS TIME WITHOUT
 THESE SHEETS.
 PLEASE BE SURE TO CORRELATE ALL LIGHTING ON PLANS WITH
 THE IDR WHEN RESUBMITTING. PLEASE BE SURE TO SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3.
 PLEASE SEE 13-415.2.ABC.1( TRACK LTS, AND OTHER
 SPECIALTY LIGHTING SYSTEMS)
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH
 RESPECT TO THE ENERGY CALCULATIONS SUBMITTED.
 ** PLEASE BE SURE THE DESIGNER OF RECORD SIGNS DATES
 AND SEALS THE CERTIFICATION SHEETS ALONG WITH THE
 SIGNATURE FROM THE OWNER AGENT.
 FS 471.025, FBC 13-103.1.1.1
  
 3) NOTE: PLEASE SEE MISSING PRINTED NAME AND PRINTED
 LICENSE NUMBER IS LISTED ON TITLE BLOCKS AS REQUIRED
 PER FAC 61G15-23.002
 ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWS
 WHETHER OR NOT COMMENT IS MADE BY THOSE OTHER TRADES.
 ** PLEASE KNOW FOR ANY SHEETS WHICH DO NOT NEED TO BE
 RE-PRINTED FOR COMMENTS, THIS MAY BE NEATLY PRINTED OR
 STAMPED ON TITLE BLOCKS.
  
 4) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS. PLEASE PROVIDE AN ORIGINAL NOTARIZED LETTER
 FOR SIGNATURE VERIFICATION. THIS WILL BE PLACED IN
 SIGNATURE FILE FOR FUTURE REFERENCE.
 FS 471.025
  
 5) NOTE: PLEASE SEE THE UNIT AS STATED ON TITLE BLOCKS
 IS SHOWN AS *B-5* WHEN THE ACTUAL SUITE/UNIT NUMBER AT
 LOCATION IS #108. PLEASE ADJUST TITLE BLOCKS.
 ** ONCE AGAIN FOR SHEETS WHICH MAY NOT NEED TO BE
 REVISED FOR COMMENTS THIS MAY BE NEATLY PRINTED OR
 STAMPED ON THE TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002, FBC ADMIN SECTION 106.5
  
 6) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4). PLEASE
 SEE THE MINIMUM LEVELS FOR ADA COMPLIANCE FOR ALL
 STROBE DEVICES SHALL MEET 75CD MINIMUM. PLEASE SEE THE
 LEVELS FOR THE HORN/STROBES INDICATE 75CD HOWEVER ALL
 STROBES ARE SHOWN AS 15CD WHICH IS WAY BELOW MINIMUM.
 PLEASE ADJUST.
 PLEASE SEE SOUND LEVELS ALSO WHICH MAY
  
 7) NOTE:PLEASE ADJUST THE COLOR CODING FOR 277/480V
 SYSTEMS TO BROWN, PURPLE AND YELLOW.
 THE CITY OF WEST PALM BEACH AND ALL SURROUNDING
 JURISDICTIONS CONTAINED LOCAL AMENDMENTS FOR THE LAST
 20PLUS YEARS WHICH HAD THE ABOVE COLORING CODING. EVEN
 AS THE TECHNICAL AMENDMENTS ARE NOT LONGER IN AFFECT
 KEEPING WITH ALL OTHER WIRING SYSTEMS ALREADY PRESENT
 IN THIS JURISDICTION AS WELL KEEPING WITH THE
 ELECTRICAL SYSTEMS ALREADY ON SITE THE ABOVE WILL BE
 REQUIRED.THE NEC ONLY PROVIDES ORANGE FOR A HIGH-LEG
 OPEN DELTA SYSTEMS, WHICH 277/480V IS NOT. AS THE NEC
 DOES NOT PROVIDE ANY COLOR CODING THIS IS PER AHJ AS A
 LIFE SAFETY, FIRE HAZARD, AND PROPERTY DAMAGE SAFETY
 MEASURE.
 90.4.
  
 8) NOTE: PLEASE VERIFY THE NOTE #3 IN SECTION 26 51 00
 ON SHEET E01.1 WHICH STATES ** THE ENERGY POLICY ACT OF
 1992*??
 PLEASE KNOW THAT ANY ENERGY CODE COMPLIANCE MEASURES
 SHALL BE ACCORDANCE WITH THE FLORIDA ENERGY CODE
 CHAPTER 13.
  
 9) NOTE: PLEASE SEE SECTION 26 27 28 FOR SWITCHING
 DEVICES DOES NOT APPLY.
  
 10) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
 PLEASE SEE THAT NOT ENOUGH INFORMATION WAS SUBMITTED
 FOR LIGHTING CONTROL SYSTEM.
 PLEASE SHOW ALL OVER RIDE DEVICE LOCATIONS AS REQUIRED.
 FOR EXAMPLE REAR ENTRANCE. OCCUPANT IS REQUIRED TO
 VISUALLY SEE THE LIGHTING BEING CONTROLLED OR MEETING
 THE EXCEPTION OF PILOT LIGHTS ETC.
 PLEASE PROVIDE TIMED SCHEDULING AND MAXIMUM OVER RIDE
 TIMES.
 PLEASE SHOW A LAYOUT OF ZONES REQUIRED.
 ** PLEASE KNOW AS NOTED ABOVE REVIEW FOR LIGHTING
 COMPLIANCE CAN NOT BE DONE.SEE NOTE ABOVE #2
  
 12) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED IN THE
 LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70
 (NEC).
 PLEASE SEE SHOW WINDOWS ARE NOW IN 220.43. (PLANS
 REFLECT 220.12)
  
 13) NOTE: PLEASE KNOW DEPENDING ON THE STRUCTURAL SCOPE
 OF WORK, THREE SETS OF PLANS MAY BE REQUIRED AS THIS IS
 A THRESHOLD BUILDING. THIS IS ONLY NOTED ONLY FOR
 INFORMATION.
  
 14) NOTE: PLEASE VERIFY BUS RATING OF PANELS A, B AND C
 AS THESE ARE SHOWN AS 100A YET 42CIR PANELS. 110.3,
 90.7.
 SUBMIT SPEC SHEET.
 FBC 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2009-02-02 Cont ID  
Sent By mawillia Date 2009-02-02 Time 14:43 Rev Time 0.00
Received By mawillia Date 2009-02-02 Time 14:18 Sent To  
Notes
2009-02-02 14:43:37*****REVISION DENIED****
  
 PLAN SHEETS A00.4, F01.1, F02.2, AND F0.4 WERE STAMPED,
 INITIALED, AND DATED; HOWEVER THE FOLLOWING COMMENTS,
 WITH SUGGESTION(S), ARE TO BE ADDRESSED:
  
 1. NO TENANT SPACE NUMBER SHOWN ON THE EXTERIOR
 ELEVATION FRONTING SOUTH ROSEMARY AVENUE. AS PER WEST
 PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 3"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. DISPLAY
 SUITE NUMBER (108) ON SHEET A08.1 & A08.1A
  
 2. SHEETS E03.1 & E03.2 ARE TO BE FIRE-STAMPED. THESE
 SHEETS ARE TO BE FIRE-STAMPED WHEN THE ELECTRICAL
 EXAMINER'S COMMENT HAVE BEEN SATISFIED
  
 3. THE REVISED COVER SHEET DOES NOT INDICATE THAT
 DRAWING F01.2 HAS BEEN VOIDED (LINED THRU) AS SHOWN IN
 THE CITY'S FILED PLAN SET. VERIFY/CLARIFY AS NECESSARY
  
 4. WHAT IS BEING VOIDED ON OR TO DRAWING F02.1 IN THE
 REVISED PLANS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-12-16 Cont ID  
Sent By mwennerg Date 2008-12-16 Time 14:10 Rev Time 0.00
Received By mwennerg Date 2008-12-16 Time 14:10 Sent To  
Notes
2008-12-16 14:27:19***DENIED***
  
 1) SOME OF THE FIRE PROTECTION SHEETS SUBMITTED HAVE
 BEEN VOIDED WITH NO EXPLANATION. IN ADDITION TO THIS
 SUBMITTAL, SEPARATE SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 PRIOR TO INSTALLATION. INDICATE MINIMUM REQUIRED LEVELS
 FOR AUDIBLE AND VISUAL DEVICES.
  
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-30 Cont ID  
Sent By mwennerg Date 2008-04-30 Time 09:54 Rev Time 0.00
Received By mwennerg Date 2008-04-30 Time 09:54 Sent To  
Notes
2008-04-30 09:55:01COMMENTS FROM FIRST FIRE REVIEW HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By mawillia Date 2008-03-20 Time 19:17 Rev Time 0.00
Received By mawillia Date 2008-03-20 Time 18:38 Sent To  
Notes
2008-03-20 18:49:08*****DENIED*****
  
  
 1.THE CODES LISTED ON COVER SHEET ARE INCORRECT;
 REFERENCE SHOULD BE AS FOLLOWS:*FIRE ALARM - 2002
 NFPA 72,*LIFE SAFETY - 2003 NFPA 101, *SPRINKLER -
 2002 NFPA 13
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE/HINDER ACCESS
 TO AND (OR) EGRESS FROM THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRELANES, ETC).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH ROSEMARY AVENUE, SHOW/DISPLAY THE SUITE NUMBER
 FOR THIS TENANT SPACE.AS PER WEST PALM BEACH CODE,
 SUITE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.
  
 6.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALL
 AND CEILINGS IN TERMS OF CLASS A OR CLASS B.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT IS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-02-10 Cont ID  
Sent By adarroug Date 2009-02-10 Time 08:29 Rev Time 0.00
Received By adarroug Date 2009-02-10 Time 08:29 Sent To M
Notes
2009-02-10 08:30:08TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-02-04 Cont ID  
Sent By adarroug Date 2009-02-04 Time 16:34 Rev Time 0.00
Received By adarroug Date 2009-02-04 Time 16:34 Sent To E
Notes
2009-02-04 16:34:48TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-02-02 Cont ID  
Sent By adarroug Date 2009-02-02 Time 08:31 Rev Time 0.00
Received By adarroug Date 2009-02-02 Time 08:31 Sent To B
Notes
2009-02-02 08:31:28TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-01-22 Cont ID  
Sent By adarroug Date 2009-01-22 Time 09:52 Rev Time 0.00
Received By adarroug Date 2009-01-22 Time 09:52 Sent To  
Notes
2009-01-22 09:53:08TO "KSTEVENS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-01-21 Cont ID  
Sent By adarroug Date 2009-01-21 Time 16:36 Rev Time 0.00
Received By adarroug Date 2009-01-21 Time 16:36 Sent To E
Notes
2009-01-21 16:36:50TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-01-12 Cont ID  
Sent By adarroug Date 2009-01-12 Time 16:56 Rev Time 0.00
Received By adarroug Date 2009-01-12 Time 16:56 Sent To B
Notes
2009-01-12 16:57:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-01-02 Cont ID  
Sent By shill Date 2009-01-02 Time 16:29 Rev Time 0.00
Received By shill Date 2009-01-02 Time 16:29 Sent To B
Notes
2009-01-02 16:29:21TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 09:45 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 09:45 Sent To B
Notes
2008-12-18 09:46:10TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-12-15 Cont ID  
Sent By adarroug Date 2008-12-15 Time 11:41 Rev Time 0.00
Received By adarroug Date 2008-12-15 Time 11:41 Sent To E
Notes
2008-12-15 11:41:52TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-03 Cont ID  
Sent By adarroug Date 2008-12-03 Time 09:23 Rev Time 0.00
Received By adarroug Date 2008-12-03 Time 09:22 Sent To  
Notes
2008-12-03 09:23:18TO "COMM" BD#45--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 11:08 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 11:08 Sent To E
Notes
2008-08-01 11:08:51TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-14 Cont ID  
Sent By adarroug Date 2008-07-14 Time 09:39 Rev Time 0.00
Received By adarroug Date 2008-07-14 Time 09:39 Sent To  
Notes
2008-07-14 09:45:20TO "COMM" BD#25/ PLANS ON RACK--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 08:43 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 08:43 Sent To  
Notes
2008-06-19 08:51:39TO "COMM" BD#35/PLANS ON RACK/1 ROLL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-24 Cont ID  
Sent By adarroug Date 2008-04-24 Time 08:22 Rev Time 0.00
Received By adarroug Date 2008-04-24 Time 08:22 Sent To  
Notes
2008-04-24 08:24:29TO"COMM"BD#41-PLANS ON RAC/-PRIVATE PROVIDER/1 ROLL, 2
 LARGE FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-20 Cont ID  
Sent By mawillia Date 2008-03-20 Time 18:40 Rev Time 0.00
Received By mawillia Date 2008-03-05 Time 09:44 Sent To  
Notes
2008-03-05 09:45:00 
 --PRIVATE PROVIDER--
  
 TO "COMM" BD#13/PLANS ON RACK/3 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-01-11 Cont ID  
Sent By rregueir Date 2009-01-11 Time 11:39 Rev Time 0.00
Received By rregueir Date 2009-01-11 Time 11:10 Sent To  
Notes
2009-01-11 11:39:44*******PROVISO*********
 RETURN DUCT NEAR FRONT ENTRANCE IS MISSING DUCT SIZE ON
 PLANS. REVISE PLAN TO SHOW THE MISSING SIZE PRIOR TO
 FINAL MECHANICAL INSPECTION. FBCM 603.1
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-28 Cont ID  
Sent By rregueir Date 2008-04-28 Time 10:41 Rev Time 0.00
Received By rregueir Date 2008-04-28 Time 10:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-12 Cont ID  
Sent By rregueir Date 2008-03-12 Time 16:06 Rev Time 0.00
Received By rregueir Date 2008-03-12 Time 13:41 Sent To  
Notes
2008-03-12 16:06:37REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OUTSIDE AIR OR VENTILATION CALCULATIONS COULD NOT BE
 FOUND ON PLANS. THE MINIMUM VENTILATION RATE OF
 REQUIRED OUTDOOR AIR SHALL BE DETERMINED IN ACCORDANCE
 WITH SECTION 403.3. PROVIDE CALCULATIONS SHOWING
 OCCUPANCY CLASSIFICATIONS, OCCUPANT LOADS, VENTILATION
 RATE REQUIRED AND VENTILATION PROVIDED FOR EACH SPACE
 WITHIN THE PROPOSED WORK AREA IN ACCORDANCE WITH FBCM
 TABLE 403.3.
  
 2. AHU SCHEDULE INDICATES THAT OUTSIDE AIR IS BEING
 PROVIDED. ONCE VENTILATION RATES HAVE BEEN VERIFIED IN
 RELATION TO COMMENT #1, PLEASE VERIFY THAT SUPPLY,
 RETURN AND EXHAUST SYSTEMS ARE IN BALANCE. THE AMOUNT
 OF SUPPLY AIR SHALL BE APPROXIMATELY EQUAL TO THE
 AMOUNT OF RETURN AND EXHAUST AIR IN ACCORDANCE WITH
 FBCM 403.1. IN OTHER WORDS, FOR THE SYSTEM TO BE
 BALANCED THE SUPPLY SHOULD BE APPROXIMATELY EQUAL TO
 THE RETURN MINUS THE EXHAUST PLUS THE OUTSIDE AIR, WITH
 A SLIGHT DIFFERENCE TO THE POSITIVE TO BE IN COMPLIANCE
 WITH THIS SECTION AND FBCB 13-409.1.ABC.2. EXAMPLE: AHU
 2 ON FLOOR PLAN CALLS FOR 4410 CFM SUPPLY AND 4165 CFM
 RETURN. THAT LEAVES A DIFFERENCE OF 235 CFM. THE AHU
 SCHEDULE CALLS FOR 1371 CFM OF OUTSIDE AIR. IT?S NOT
 POSSIBLE TO INTRODUCE MORE OUTSIDE AIR THAN THE
 DIFFERENCE BETWEEN THE SUPPLY AND RETURN(IN THIS CASE
 235 CFM). PLEASE CORRECT AIR BALANCES, KEEPING IN MIND
 THE REQUIRED VENTILATION RATES RELATED TO COMMENT #1.
  
 3. SHUTOFF DAMPER CONTROLS ARE REQUIRED IN ACCORDANCE
 WITH FBCB 13-409.1.ABC.3.3. BOTH OUTDOOR AIR SUPPLY AND
 EXHAUST SYSTEMS SHALL BE EQUIPPED WITH MOTORIZED
 DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS
 OR SPACES SERVED ARE NOT IN USE. GRAVITY
 (NON-MOTORIZED) DAMPERS ARE ACCEPTABLE IN BUILDING
 EXHAUST AIR SYSTEMS IN ACCORDANCE WITH EXCEPTION #1 OF
 THIS SECTION. IT IS ACKNOWLEDGED THAT MOTORIZED DAMPERS
 ARE CALLED FOR IN THE AHU SEQUENCE ON PG M04.1, BUT
 THESE DAMPERS ARE NOT SHOWN ON PLANS. PLEASE CORRECT.
  
 4.EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET
 IN ACCORDANCE WITH FAC 61G15-23.002(2). THE FULL LEGAL
 SIGNATURE OF THE DESIGNER OF RECORD SHOULD ALSO BE
 USED. THESE PLANS APPEAR TO HAVE BEEN SIGNED WITH AN
 INITIAL. PLEASE VERIFY THAT THIS IS THE DESIGNER'S FULL
 SIGNATURE PRIOR TO RESUBMITTAL. SEE SIMILAR COMMENTS
 FROM OTHER TRADES.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-01-22 Cont ID  
Sent By kstevens Date 2009-01-22 Time 18:06 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 18:06 Sent To E
Notes
2009-01-22 18:07:24REVISIONS OK -- SHTS P01.1, P02.1, P02.2 & P03.1.

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-12-15 Cont ID  
Sent By kstevens Date 2008-12-15 Time 14:49 Rev Time 0.00
Received By kstevens Date 2008-12-15 Time 14:49 Sent To  
Notes
2008-12-15 15:03:30DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P01.1 REVISIONS 3A, 3B, & 4 WERE NOT INDICATED
 ON THE SHEET AS REVISIONS. THE ONLY CLOUD IS FOR
 REVISION 5 AND IT INDICATES THE COMPLETE SHEET. UNLESS
 ALL INFORMATION ON THE SHEET HAS BEEN REVISED, ONLY
 CLOUD AND NUMBER EACH REVISION ONLY ON THE SHEET.
 SECTION 106.1.3.
  
 2. SHT P02.1 REVISIONS 3B & 4 WERE NOT INDICATED ON THE
 SHEET AS REVISIONS. THE ONLY CLOUD IS FOR REVISION 5
 AND IT INDICATES THE COMPLETE SHEET. UNLESS ALL
 INFORMATION ON THE SHEET HAS BEEN REVISED, ONLY CLOUD
 AND NUMBER EACH REVISION ONLY ON THE SHEET. SECTION
 106.1.3.
  
 3. SHT P02.2 REVISIONS 3B & 4 WERE NOT INDICATED ON THE
 SHEET AS REVISIONS. THE ONLY CLOUD IS FOR REVISION 5
 AND IT INDICATES THE COMPLETE SHEET. UNLESS ALL
 INFORMATION ON THE SHEET HAS BEEN REVISED, ONLY CLOUD
 AND NUMBER EACH REVISION ONLY ON THE SHEET. SECTION
 106.1.3.
  
 4. SHT P03.1 REVISIONS 3A, 3B, & 4 WERE NOT INDICATED
 ON THE SHEET AS REVISIONS. THE ONLY CLOUD IS FOR
 REVISION 5 AND IT INDICATES THE COMPLETE SHEET. UNLESS
 ALL INFORMATION ON THE SHEET HAS BEEN REVISED, ONLY
 CLOUD AND NUMBER EACH REVISION ONLY ON THE SHEET.
 SECTION 106.1.3.
  
 5. THIS OFFICE WAS UNABLE TO GLEAN ALL THE INFORMATION
 REQUIRED ON THE SEAL BY FAC 61G15-23.001(1)(2) & FS
 471.025. PLEASE RESEAL ALL SHEETS SO THAT EMBOSSING
 INFORMATION IS LEGIBLE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-15 Cont ID  
Sent By kstevens Date 2008-06-27 Time 12:55 Rev Time 0.00
Received By kstevens Date 2008-06-27 Time 12:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-25 Cont ID  
Sent By kstevens Date 2008-04-25 Time 06:12 Rev Time 0.00
Received By kstevens Date 2008-04-25 Time 06:12 Sent To  
Notes
2008-04-25 06:22:19AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS AUDIT:
  
 1.ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE PLANS IS REQUIRED. THE SIGNATURE OF
 THE PERSON SEALING THE DOCUMENTS IS REQUIRED. FAC
 61G1-16.003, 61G1-16.004(5)(6) & FS 481.2055. IT
 APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH INITALS.
 IF IT IS INDEED THE LEGAL SIGNATURE OF THE ARCHITECT
 THEN A SIGNED, SEALED, NOTORIZED LETTER INDICATING THE
 LEGAL SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR
 OUR FILES.
 ****RESPONSE NOTED, BUT LETTER NOT SUBMITTED.
  
  
 2. SHT A01.1 DEMO KEY NOTE #10 INDICATES CAPPING
 PLUMBING IN THE NEAREST DEMISING WALL. SECTION 704.5
 PROHIBITS DEAD ENDS. PLEASE SHOW COMPLIANCE WITH
 SECTION AND SHOW THE LOCATION OF ALL DEMO'D PIPING.
 ****RESPONSE NOTED, BUT THE NOTE STILL INDICATES "CAP
 ALL PLUMBING LINES TO THE NEAREST WALL. IF PIPES ARE IN
 THE SLAB, CAP LEVEL WITH THE FLOOR SLAB". THIS DOES NOT
 MEET THE CODE REQUIREMENTS OF SECTION 704.5 PROHIBITING
 DEAD ENDS. ALL PLUMBING LINES SHALL BE DEMO'D BACK TO
 THE MAIN BRANCH LINE, OR IF THE BRANCH LINE IS NOT IN
 USE, THE PLUMBING LINE SHALL BE DEMO'D BACK TO THE
 BUILDING DRAIN. THERE IS NO REQUIREMENT FOR
 ACCESSIBILITY TO A DEMO'D PLUMBING LINE.
  
 3. OK
 4. OK
 5. OK
  
 **********NEW COMMENT**********
  
 1B. THE NOTICE TO BUILDING OFFICIAL USE OF PRIVATE
 PROVIDER INDICATES THE PRIVATE PROVIDER TO BE MORGAN
 DICKINSON, P.E., ADDRESS: 5808-D BRECKENRIDGE PARKWAY,
 TAMPA, FL 33610, BUT THE PRIVATE PROVIDER ON THE
 PRIVATE PROVIDER BUILDING PLANS COMPLIANCE AFFIDAVIT IS
 INDICATED ASVALDO AREVALO, P.E., ADDRESS: 1011 SHOTGUN
 ROAD, SUNRISE, FL 33326. PLEASE CLARIFY. FS 553.791.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By kstevens Date 2008-03-08 Time 13:06 Rev Time 0.00
Received By kstevens Date 2008-03-08 Time 13:05 Sent To  
Notes
2008-03-08 13:31:32AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE PRINTED NAME OF THE
 PERSON SEALING THE PLANS IS REQUIRED. THE SIGNATURE OF
 THE PERSON SEALING THE DOCUMENTS IS REQUIRED. FAC
 61G1-16.003, 61G1-16.004(5)(6) & FS 481.2055. IT
 APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH INITALS.
 IF IT IS INDEED THE LEGAL SIGNATURE OF THE ARCHITECT
 THEN A SIGNED, SEALED, NOTORIZED LETTER INDICATING THE
 LEGAL SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR
 OUR FILES.
  
 2. SHT A01.1 DEMO KEY NOTE #10 INDICATES CAPPING
 PLUMBING IN THE NEAREST DEMISING WALL. SECTION 704.5
 PROHIBITS DEAD ENDS. PLEASE SHOW COMPLIANCE WITH
 SECTION AND SHOW THE LOCATION OF ALL DEMO'D PIPING.
  
 3. SHT A13.1 DETAIL D ELEVATION D-4 SHOWS THE DISPENSER
 MINIMUM OF 15" ABOVE THE FLOOR. PER SECTION 11-4.16.6
 THE MINIMUM IS 19" TO THE DISPENSER. PLEASE SHOW
 COMPLIANCE.
  
 4. ALL PLUMBING SHEETS. THE PRINTED NAME OF THE
 ENGINEER AND THE ENGINEER'S LICENSE NUMBER SHALL BE
 LEGIBLY INDICATED ON EACH SHEET. FAC 61G15-23.002(2).
 ALSO THE SIGNATURE OF THE ENGINEER IS REQUIRED ON ALL
 SHEETS. IT APPEARS THAT INITALS HAVE BEEN USED TO SIGN
 THE PLANS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE OF THE ENGINEER SHALL BE
 SUBMITTED FOR OUR FILES.
  
 5. SHT P02.2 DOMESTIC WATER PIPING ISOMETRIC RISER
 DIAGRAM SHOWS WATER HAMMER ARRESTORS AT THE TOP OF THE
 DROPS, IN THE CEILING. PER PDI-WH 201 THE WATER HAMMER
 ARRESTORS, IF INSTALLED, SHALL BE LOCATED NEAR THE
 FIXTURES, IN AN "EFFECTIVE RANGE", NOT IN THE CEILING
 AS SHOWN. PLEASE SHOW THE WATER HAMMER ARRESTORS NEAR
 THE FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-12-03 Cont ID  
Sent By eschneid Date 2008-12-03 Time 17:40 Rev Time 0.00
Received By eschneid Date 2008-12-03 Time 17:40 Sent To  
Notes
2008-12-03 17:40:52PASSED (RESTAMP)
  
 PLEASE NOTE THAT ALL SIGNAGE, TO INCLUDE THOSE ON THE
 CONSTRUCTION BARRIER, REQUIRES A SEPARATE SIGN PERMIT.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-25 Cont ID  
Sent By eschneid Date 2008-04-25 Time 08:58 Rev Time 0.00
Received By eschneid Date 2008-04-25 Time 08:58 Sent To  
Notes
2008-04-25 08:58:42PASSED (RESTAMP)
  
 PLEASE NOTE THAT ALL SIGNAGE, TO INCLUDE THOSE ON THE
 CONSTRUCTION BARRIER, REQUIRES A SEPARATE SIGN PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-13 Cont ID  
Sent By eschneid Date 2008-03-13 Time 10:16 Rev Time 0.00
Received By eschneid Date 2008-03-13 Time 10:16 Sent To  
Notes
2008-03-13 10:18:37PASSED
  
 PLEASE NOTE THAT ALL SIGNAGE, TO INCLUDE THOSE ON THE
 CONSTRUCTION BARRIER, REQUIRES A SEPARATE SIGN PERMIT.