Plan Review Details - Permit 08030068
Plan Review Stops For Permit 08030068
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-04 Cont ID  
Sent By jleahy Date 2008-04-04 Time 09:50 Rev Time 0.45
Received By jleahy Date 2008-04-04 Time 09:50 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-21 Cont ID  
Sent By btrobaug Date 2008-03-21 Time 14:56 Rev Time 0.00
Received By btrobaug Date 2008-03-21 Time 14:16 Sent To FIRE
Notes
2008-03-21 14:52:39 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1,FLORIDA STATUTES 2007, AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ARCHITECT'S SIGNATURE IS A PHOTOCOPY. WHEN
 SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE WET PER
 481.221(1) (A) FLORIDA STATUTES. THE ARCHITECTURAL
 FIRM, WHOSE TITLE BLOCK APPEARS ON THE PLANS, MUST SIGN
 AND SEAL THE PLAN PER 481.221(1) (B) FS.
  
 2} AS STATED IN THE PREVIOUS FIRE REVIEW, THE
 APPLICATION INDICATES THIS WORK ON THE 18TH FLOOR, BUT
 THE PLANS ARE LABELED 15TH AND 16TH FLOOR, CORRECT THE
 ADDRESS ON THE PLANS.
  
 NOTE: UNLESS THE CONTRACTOR GOES TO THE ARCHITECT OF
 RECORD, HE MAY NEED TO DRAW HIS OWN PLANS, PRINT AND
 SIGN HIS NAME AS THE DESIGNER OF RECORD, PERMISSIBLE
 PER 471.003 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By btrobaug Date 2008-03-06 Time 13:31 Rev Time 0.00
Received By btrobaug Date 2008-03-06 Time 13:24 Sent To FIRE
Notes
2008-03-06 13:31:56 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-04 Cont ID  
Sent By mawillia Date 2008-04-04 Time 12:44 Rev Time 0.00
Received By mawillia Date 2008-04-04 Time 12:22 Sent To  
Notes
2008-04-04 12:44:18*****APPROVED*****
  
 THE 15TH AND 16TH FLOOR PLAN HAVE BEEN STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-03-24 Cont ID  
Sent By mawillia Date 2008-03-24 Time 11:18 Rev Time 0.00
Received By mawillia Date 2008-03-24 Time 10:52 Sent To  
Notes
2008-03-24 11:16:38*****UNSAT*****
  
 *THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEEDS TO BE ADDRESSED:
  
 2.THE PERMIT APPLICATION AND WHAT IS REGISTERING IN
 OUR PERMITTING SYSTEM REFERENCES SUITE 1800, HOWEVER,
 THE 15TH AND 16TH FLOOR ARE LISTED AS THE SCOPE OF WORK
 SITE.
  
 *NEW COMMENT:
  
 A.SOME OTHER FORM OFACCESS SYSTEM IDENTIFICATION
 NEEDED DUE TO THE CITY'S MICROFICHE UNABLE TO READ THE
 HIGHLIGHTED MARKINGS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING ON THE PLAN WHERE EACH ITEM HAS BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-11 Cont ID  
Sent By mawillia Date 2008-03-11 Time 17:11 Rev Time 0.00
Received By mawillia Date 2008-03-11 Time 16:18 Sent To  
Notes
2008-03-11 16:42:54*****DENIED*****
  
  
 1.ONLY ONE PLAN SET WAS SUBMITTED FOR REVIEW.PLEASE
 BE ADVISED THAT AT LEAST TWO NO MORE THAN THREE
 CONSTRUCTION DOCUMENTS, SPECIFICATIONS, AND OTHER DATA
 SHALL BE SUBMITTED WITH EACH APPLICATION FOR A PERMIT.
  
 2.THE PERMIT APPLICATION AND WHAT IS REGISTERING IN
 OUR PERMITTING SYSTEM REFERENCES SUITE 1800, HOWEVER,
 THE 15TH AND 16TH FLOOR ARE LISTED AS THE SCOPE OF WORK
 SITE.
  
 3.DOORS IN A MEANS OF EGRESS SHALL BE PERMITTED TO BE
 EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA IN NFPA 101,
 2003 EDITION, 7.2.1.6.2 ARE MET.
  
 4.SHOW THE MARKED EXIT DOORS ON THE FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING ON THE PLAN WHERE EACH ITEM HAS BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 11:14 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 11:14 Sent To E
Notes
2008-04-02 11:14:39TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 14:48 Rev Time 0.00
Received By shill Date 2008-03-19 Time 14:48 Sent To E
Notes
2008-03-19 14:49:16TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-11 Cont ID  
Sent By mawillia Date 2008-03-11 Time 16:39 Rev Time 0.00
Received By mawillia Date 2008-03-05 Time 09:08 Sent To  
Notes
2008-03-05 09:08:37TO "E" BOX