Plan Review Details - Permit 08030044
Plan Review Stops For Permit 08030044
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By shill Date   Time   Rev Time  
Received By shill Date 2008-05-29 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 17:56 Rev Time 0.00
Received By shill Date 2008-04-29 Time 17:56 Sent To  
Notes
2008-04-29 18:01:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FAC61G1-16.002,003.
  
 2.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G15-23.002.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-11 Cont ID  
Sent By shill Date 2008-03-11 Time 13:19 Rev Time 0.00
Received By shill Date 2008-03-11 Time 13:19 Sent To Z
Notes
2008-03-11 13:21:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.DECLARE GOVERNING CODE AND WIND DESIGN CRITERIA
 FBC1603.
  
 2.PLEASE SPECIFY, ARE ALL OF THE LUMINAIRES WALL
 MOUNT?PROVIDE STRUCTURAL SPECIFICATIONS (ANCHOR
 INFORMATION).
  
 3.IF THIS PERMIT INCLUDES LIGHT POLES, PROVIDE
 STRUCTURAL DETAILS AND CALCS.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-24 Cont ID  
Sent By btrobaug Date 2008-04-24 Time 09:10 Rev Time 0.00
Received By btrobaug Date 2008-04-23 Time 16:02 Sent To B
Notes
2008-04-24 09:09:51 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENT AS PREVIOUS REVIEW:
  
 1} 13-415.2.ABC.1.3 EXTERIOR BUILDING LIGHTING POWER.
 THE TOTAL EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL
 EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE
 INDIVIDUAL LIGHTING POWER DENSITIES PERMITTED IN TABLE
 415.2.ABC.1.3 FOR THESE APPLICATIONS, PLUS AN
 ADDITIONAL UNRESTRICTED ALLOWANCE OF 5 PERCENT OF THAT
 SUM. TRADE-OFFS ARE ALLOWED ONLY AMONG EXTERIOR
 LIGHTING APPLICATIONS LISTED IN THE TABLE
 13-415.2.ABC.1.3, "TRADABLE SURFACES" SECTION. EXTERIOR
 LIGHTING FOR ALL APPLICATIONS (EXCEPT THOSE INCLUDED IN
 THE EXCEPTIONS TO SECTIONS 415.0 AND 415.2.ABC.1.3)
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 415.1.ABC.2.* PHOTOMETRICS IS NOT LIGHTING POWER
 DENSITIES, PLEASE SEE THE SECTION SITED.
  
 NEW COMMENT:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC. THE WIND LOAD ANALYSIS SIGNATURE IS A PHOTOCOPY.
  
 2} 13-415.1.ABC.1.4 EXTERIOR LIGHTING CONTROL.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 415.0 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE, OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ASTRONOMICAL
 TIME SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING
 AND THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD
 OF AT LEAST 10 HOURS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-05 Cont ID  
Sent By btrobaug Date 2008-03-05 Time 15:27 Rev Time 0.00
Received By btrobaug Date 2008-03-05 Time 11:29 Sent To B
Notes
2008-03-05 15:00:56 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.2.ABC.1.3 EXTERIOR BUILDING LIGHTING POWER.
 THE TOTAL EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL
 EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE
 INDIVIDUAL LIGHTING POWER DENSITIES PERMITTED IN TABLE
 415.2.ABC.1.3 FOR THESE APPLICATIONS, PLUS AN
 ADDITIONAL UNRESTRICTED ALLOWANCE OF 5 PERCENT OF THAT
 SUM. TRADE-OFFS ARE ALLOWED ONLY AMONG EXTERIOR
 LIGHTING APPLICATIONS LISTED IN THE TABLE
 13-415.2.ABC.1.3, "TRADABLE SURFACES" SECTION. EXTERIOR
 LIGHTING FOR ALL APPLICATIONS (EXCEPT THOSE INCLUDED IN
 THE EXCEPTIONS TO SECTIONS 415.0 AND 415.2.ABC.1.3)
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION
 415.1.ABC.2.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-29 Cont ID  
Sent By adarroug Date 2008-05-29 Time 12:53 Rev Time 0.00
Received By adarroug Date 2008-05-29 Time 12:53 Sent To B
Notes
2008-05-29 12:53:30TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 09:43 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 09:43 Sent To Z
Notes
2008-04-21 09:43:34TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-03-12 Time   Rev Time 0.00
Received By adarroug Date 2008-03-04 Time 14:29 Sent To  
Notes
2008-03-04 14:30:16TO "E" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-23 Cont ID  
Sent By choops Date 2008-04-23 Time 15:14 Rev Time 0.00
Received By choops Date 2008-04-23 Time 15:14 Sent To E
Notes
2008-04-23 15:19:10***APPROVED - RESUB #1***
  
 PROVISO:A-POLE AT NORTH EAST LOCATION MUST BE ROTATED
 90 DEGREES TO ADEQUATELY LIGHT BOTH PARKING AREAS AS
 PER DISCUSSIONS WITH THE PLANNING AND ZONING
 DEPARTMENT.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-12 Cont ID  
Sent By choops Date 2008-03-12 Time 11:14 Rev Time 0.00
Received By choops Date 2008-03-12 Time 11:14 Sent To  
Notes
2008-03-12 11:22:03***FAILED***
  
  
 1)THE SUBMITTED LIGHTING/PHOTOMETRIC PLAN SHALL SHOW
 ALL IMPROVEMENTS AND ACCURATELY REFLECT THE CONDITION
 OF THE SITE.
  
 2)SUBMIT TWO (2) COPIES OF THE APPROVED LANDSCAPE
 PLAN SHOWING THE INTEGRATION OF THE LIGHTING AND ITS
 COHESION WITH THE LANDSCAPING.IF A CONFLICT ARISES,
 THE APPROVED LANDSCAPE PLAN SHALL BE REVISED TO REFLECT
 ANY CHANGES.
  
  
 NOTE:A REVISED EASEMENT AGREEMENT (ENCROACHING
 IMPROVEMENTS)(O.R.B. 13408, PG 1500) SHALL BE SUBMITTED
 PRIOR TO OBTAINING C.O.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720