Plan Review Details - Permit 08020712
Plan Review Stops For Permit 08020712
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-09 Cont ID  
Sent By mjacobs Date 2008-04-09 Time 07:08 Rev Time 0.00
Received By mjacobs Date 2008-04-09 Time 06:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By mjacobs Date 2008-04-08 Time 15:04 Rev Time 0.00
Received By mjacobs Date 2008-04-08 Time 12:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By mjacobs Date 2008-03-08 Time 09:00 Rev Time 0.00
Received By mjacobs Date 2008-03-07 Time 16:48 Sent To  
Notes
2008-03-08 09:00:35BUILDING PLAN REVIEW
 PERMIT: 08020712
 ADD: 2580 METROCENTRE BLVD WEST
 CONT: SISCA CONST. SERVICES LLC
 TEL: (561)686-5545
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE SUBMIT 2 OF ALL, REPORTS, PRODUCT APPROVALS
 FOR REVIEW FOR PERMIT 106.1* /2004 WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE THE PRODUCT APPROVALS
 FOR THE NEW OVER HEAD DOOR
  
 4) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 5) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 6)IS THERE A FIRE SPRINKLER SYSTEM INSTALLED AT THIS
 PROJECT? IF SO, INDICATE THE LOCATION OF THE SPRINKLER
 HEADS ON THE CEILING PLAN OR PROVIDE A SEPARATE SHEET
 SHOWING THE LOCATION OF EACH ONE IN RELATION TO EACH
 ROOMS AND EXIT ACCESS. FBC 106.3.5.1.1(5)
  
 7)NOTE; SHEET A.1 PLAN LEGEND MAKES REFERENCE TO
 SHEET A.4 HOWEVER, THERE IS NO SUCH SHEET SUBMITTED IN
 THE PLAN SET. CHANGE ACCORDINGLY TO SHOW COMPLIANCE.
  
 8)THE ADDRESS FOR LCA ARCHITECTURE ON THE PLANS
 DIFFERS FROM THE INFORMATION ON THE DBPR WEB SITE. SEE
 INFORMATION FROM DBPR IN THE PACKAGE. THE ADDRESS FOR
 THE ARCHITECTURE FIRM SHALL MATCH THE STATE WEBSITE
 INFORMATION
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-07 Cont ID  
Sent By btrobaug Date 2008-04-07 Time 15:52 Rev Time 0.00
Received By btrobaug Date 2008-04-07 Time 14:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By btrobaug Date 2008-03-04 Time 14:11 Rev Time 0.00
Received By btrobaug Date 2008-03-04 Time 12:05 Sent To  
Notes
2008-03-04 14:11:19 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE FEEDER CONDUITS FROM THE MAIN DISCONNECT TO THE
 JUNCTION BOX THAT IS PROPOSED TO REPLACE THE 600 AMP
 PANEL ARE NOT SIZED ON THE RISER, SHEET E.3. THE NOTE
 "2 SETS OF 250 MCM. CU" IS ALSO NOT CLEAR AS THE SIZE
 AND NUMBER OF CONDUITS IS NOT NOTED. THEREFORE BOX FILL
 PER 314.28 CANNOT BE REVIEWED. IT WOULD APPEAR THE
 12"X12" BOX IS NOT IN COMPLIANCE WITH EVEN THE 21/2"
 CONDUIT FEEDING PANEL "A". CLARIFY SIZES.
  
 2} THE 2/0 FEEDERS FROM THE JUNCTION BOX TO PANEL "A"
 DO NOT COMPLY WITH THE AMPERAGE RATING OF 225 PER
 310.16.THEY WOULD NEED TO BE 4/0 CU MINIMUM FOR 225
 AMPS.
  
 3} THE FEED FROM PANEL "A" TO PANEL "B", SAME COMMENT
 AS ABOVE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By mawillia Date 2008-04-08 Time 17:27 Rev Time 0.00
Received By mawillia Date 2008-04-08 Time 16:32 Sent To B1
Notes
2008-04-08 17:25:55*****APPROVED*****
  
 PLAN SHEETS A.1, A.2, LS.1, AND E.2, WERE STAMPED,
 INITIALED, AND DATED.
  
 ATTENTION:AS PER CONVERSATION WITH JESSICA SANCHEZ
 (OF SISCA CONSTRUCTION SERVICES) VIA THE ARCHITECT,
 THIS PROJECT SITE IS AT A NON-SPRINKLERED BUILDING;
 THE REFERENCES TO A FIRE SPRINKLER SYSTEM (SHEET T.1
 AND LS.1)ARE TO BE DISREGARDED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By mawillia Date 2008-03-10 Time 16:36 Rev Time 0.00
Received By mawillia Date 2008-03-10 Time 16:17 Sent To  
Notes
2008-03-10 16:33:22*****UNSAT*****
  
  
 1.SHOW A LAYOUT OF THE FIRE SPRINKLER AND(OR) FIRE
 ALARM DEVICES FOR THIS TENANT SPACE.IF THE SCOPE OF
 WORK HAS CAUSE FOR THE FIRE SPRINKLER AND(OR) FIRE
 ALARM SYSTEM TO BE REMODELED, SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED AFTER THE MASTER PERMIT HAS BEEN
 ISSUED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-28 Cont ID  
Sent By adarroug Date 2008-03-28 Time 16:38 Rev Time 0.00
Received By adarroug Date 2008-03-28 Time 16:38 Sent To  
Notes
2008-03-28 16:45:52TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-10 Cont ID  
Sent By mawillia Date 2008-03-10 Time 16:17 Rev Time 0.00
Received By mawillia Date 2008-02-29 Time 11:02 Sent To  
Notes
2008-02-29 11:02:19TO "BOB"#3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-03-04 Cont ID  
Sent By tgordon Date 2008-03-04 Time 11:16 Rev Time 0.30
Received By tgordon Date 2008-03-04 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-03-03 Cont ID  
Sent By jleech Date 2008-03-03 Time 09:43 Rev Time 0.00
Received By jleech Date 2008-03-03 Time 09:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-29 Cont ID  
Sent By choops Date 2008-02-29 Time 16:09 Rev Time 0.00
Received By choops Date 2008-02-29 Time 16:09 Sent To  
Notes
2008-02-29 16:10:17*ZONING REVIEW NOT REQUIRED; INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved