 |
Plan Review Details - Permit 08020693
Plan Review Stops For Permit 08020693 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-12-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-12-24 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-12-24 |
Time |
16:14 |
Sent To |
|
|
Notes |
2008-12-24 16:15:56 | PROVISO | | | | 1. SUBMIT AB DESIGN SITE PLAN (2ND SET) FOR RESTAMP | | | | 2. SEPARATE PERMIT ACCORDIONS & ROOF (ROOF NOA | | 07-1203.02) | | | | 3. SUBMIT SOILS INVESTIGATION REPORT | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2008-12-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-12-22 |
Time |
09:36 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-12-22 |
Time |
09:20 |
Sent To |
|
|
Notes |
2008-12-22 09:45:29 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1-5.) ADDRESSED. | | | | 6.) PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. TWO | | ORIGINALS REQUIRED. | | | | 2ND REVIEW, SEE THE SOILS REPORT AND FAC61G15-23.002, | | ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED ON | | A SIGNATURE PAGE OR COVER LETTER BY EACH PROFESSIONAL | | ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF | | THE REPORT, AND IF PRACTICING THROUGH A DULY AUTHORIZED | | ENGINEERING BUSINESS, THE NAME, ADDRESS AND CERTIFICATE | | OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. | | THE SIGNATURES ARE TO BE ORIGINALS, NOT PHOTOCOPIES. | | | | 3RD REVIEW, CERTIFICATE OF AUTHORIZATION NOT INCLUDED | | ON THE REPORT AND SIGNATURE IS A PHOTOCOPY, | | FAC61G15-23.002. | | | | 4TH REVIEW, SAME PAPERWORK SUBMITTED. CERTIFICATE OF | | AUTHORIZATION IS TO BE INCLUDED ON THE SOILS REPORT, | | ORIGINAL SIGNATURE REQUIRED FAC61G15-23.002. | | | | 7.) ADDRESSED. | | | | 8.) PARKING STRIPING IS TO COMPLY WITH CITY OF WEST | | PALM BEACH STANDARD, SEE ATTACHED DETAIL. REVISE C1. | | | | ENGINEER?S RESPONSE IS THAT THE CONTRACTOR WILL | | ADDRESS. AN ACCESSIBLE ROUTE IS REQUIRED, AS WELL AS | | ACCESSIBLE PARKING. THEREFORE, IT APPEARS THAT THE SITE | | PLAN PREPARED BY AB DESIGN IS REQUIRED FOR CODE | | COMPLIANCE. | | | | SHEET 1, THE PARKING DETAIL DOES NOT MATCH THE SITE | | PLAN ON THE SAME PAGE. THE SITE PLAN SHOWS A WHEEL | | STOP, PARKING DETAIL SHOWS A VEHICLE OVERHANG. | | COMPLIANCE NOT CLEAR, SEE FBC11-4.6.3, OVERHANG SHALL | | NOT REDUCE THE CLEAR WIDTH OF ACCESSIBLE ROUTE. | | | | SEE ALSO COMMENT 23 FROM FIRST LIST; SHOW THE WIDTH OF | | THE SIDEWALK (ROUTE FROM THE ACCESSIBLE PARKING TO THE | | FRONT ENTRY), FBC11-4.6.2(1). | | | | 3RD REVIEW, SIDEWALK WIDTH NOT INDICATED | | FBC11-4.6.2(1). STRIPING DETAIL NOT IN COMPLIANCE WITH | | CITY STANDARDS. | | | | 4TH REVIEW, IT IS UNCLEAR WHAT YOU ARE USING FOR A SITE | | PLAN. SAME PLANS SUBMITTED, SOME PHOTOCOPY PLANS WERE | | SUBMITTED (DOCUMENTS PREPARED BY AN ENGINEER TO BE | | SIGNED,SEALED, DATED ORIGINALS FS471), COMMENTS NOT | | ADDRESSED. PLEASE VOID OUT SHEETS SUBMITTED AS | | REFERENCE AND PROVIDE PLANS WHICH SHOW COMPLIANCE WITH | | THE ACCESSIBILITY REQUIREMENTS. | | | | 9-22.) ADDRESSED. | | | | 23.) FROM FIRST LIST; COMMENT NOT ADDRESSED. SHOW THE | | SIDEWALK WIDTH ON THE PLAN, SIDEWALK BETWEEN ACCESSIBLE | | PARKING AND THE BUILDING. C1 SHOWS A 44INCH SIDEWALK, | | WITH A NOTE "SIDEWALK AS SHOWN ON PLAN" BUT THE | | ENGINEER'S PLAN DOESN'T SHOW ANY SIDEWALKS. THE | | LANDSCAPE ARCHITECT'S PLAN DOES NOT DIMENSION THE | | SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE ROUTE, AND THERE | | IS A CONFLICT BETWEEN THE PARKING DETAIL AND THE | | PARKING SHOWN ON THE SITE PLAN, BOTH ON AB DESIGN PAGE | | 1. THE PARKING DETAIL SHOWS A VEHICLE OVERHANG, PLAN | | SHOWS A WHEEL STOP. SEE FBC11-4.6.3, VEHICLE OVERHANGS | | CANNOT REDUCE THE CLEAR WIDTH. DESIGN INTENT IS NOT | | CLEAR. | | | | 2ND REVIEW, ENGINEER REMOVED SIDEWALK FROM PLAN, | | RESPONSE LETTER STATES THIS WILL BE ADDRESSED BY | | CONTRACTOR. PLEASE REVISE SITE PLAN TO SHOW CODE | | COMPLIANCE. | | | | 3RD REVIEW, CIVIL SHEETS SUBMITTED AND OTHER SITE PLANS | | PREVIOUSLY SUBMITTED REMOVED. THE NEW SHEETS DO NOT | | SHOW THE SIDEWALK WIDTH, FBC11-4.6.2(1), SEE ALSO | | COMMENT 8. | | | | 4TH REVIEW, SEE ITEM 8. | | | | 24-39.) ADDRESSED. | | | | 40.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED. | | PLEASE SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT | | GLASS AND FRONT DOOR. PRODUCT APPROVALS ARE TO BE | | REVIEWED BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FBC*106. | | | | 4TH REVIEW, PLANS WERE SUBMITTED WITH A RESPONSE | | STATING THAT THE GLAZING WILL BE NON IMPACT WITH | | ACCORDIONS. THE DOOR IS AN OUTSWING DOOR SO CANNOT BE | | OPERATED FROM THE INSIDE, SEE FBC1003.6, FBC1008.1.3.5. | | PLEASE ADVISE AS TO WHERE IN THE CODE BLOCKING A | | REQUIRED EXIT IS PERMISSIBLE. | | | | 41.) FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND | | SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3. THIS CAN | | BE DONE AT THE TIME OF ROOF PERMIT APPLICATION. | | | | THE PRODUCT APPROVAL FOR THE ROOF HAS BEEN REMOVED FROM | | THE PACKAGE. THIS IS REQUIRED, REVIEWED BY DESIGNER OF | | RECORD. OTHER INFORMATION (ASSEMBLY, ENHANCED | | FASTENING) CAN BE SUBMITTED WITH THE ROOF PERMIT. | | | | 4TH REVIEW, ALL PRODUCT APPROVALS ARE TO BE REVIEWED BY | | DESIGNER OF RECORD FBC*106. | | | | 42.) SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ. | | PLEASE PROVIDE LEGIBLE COPIES. THEY MAY BE AVAILABLE AT | | WWW.BUILDINGCODEONLINE.COM. | | | | PLEASE SEE THE ROLLUP DOOR PRODUCT APPROVAL. IT IS | | ILLEGIBLE AND I CANNOT FIND/READ DESIGN PRESSURES. | | PLEASE MARK ON THE FLORIDA STATE PRODUCT APPROVAL WHICH | | PRODUCT YOU ARE USING AND SUBMIT COMPLETE, LEGIBLE | | DOCUMENTS FOR THAT PRODUCT. THIS IS AVAILABLE AT | | WWW.FLORIDABUILDING.ORG | | | | 3RD REVIEW, THE GARAGE DOOR PRODUCT APPROVAL HAS A | | DESIGN PRESSURE LIMITATION OF +-30PSF. +33.7/-36.7 | | REQUIRED, SEE PAGE A3. | | | | 4TH REVIEW, DESIGNER OF RECORD TO REVIEW ALL PRODUCT | | APPROVALS FBC*106. THE GARAGE DOOR PRODUCT APPROVAL | | SUBMITTED DOES NOT MEET THE DESIGN PRESSURE | | REQUIREMENTS. PLEASE ADDRESS. | | | | 43.) ADDRESSED. | | | | 44-45.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED. | | | | 4TH REVIEW, THE RESPONSE LETTER STATES THAT ACCORDIONS | | WILL BE USED. A SEPARATE PERMIT WILL BE REQUIRED. THE | | EXIT DOORS ARE TO BE IMPACT, FBC1003.6, FBC1008.1.3.5. | | | | 46-51.) ADDRESSED. | | | | NEW COMMENT: | | | | THE CONTRACTOR MAY CONTACT ME TO DISCUSS HOW THESE | | ITEMS COULD BE RESOLVED. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-11-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-11-19 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-11-18 |
Time |
11:28 |
Sent To |
|
|
Notes |
2008-11-19 08:54:19 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1-5.) ADDRESSED. | | | | 6.) PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. TWO | | ORIGINALS REQUIRED. | | | | 2ND REVIEW, SEE THE SOILS REPORT AND FAC61G15-23.002, | | ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED ON | | A SIGNATURE PAGE OR COVER LETTER BY EACH PROFESSIONAL | | ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF | | THE REPORT, AND IF PRACTICING THROUGH A DULY AUTHORIZED | | ENGINEERING BUSINESS, THE NAME, ADDRESS AND CERTIFICATE | | OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. | | THE SIGNATURES ARE TO BE ORIGINALS, NOT PHOTOCOPIES. | | | | 3RD REVIEW, CERTIFICATE OF AUTHORIZATION NOT INCLUDED | | ON THE REPORT AND SIGNATURE IS A PHOTOCOPY, | | FAC61G15-23.002. | | | | 7.) ADDRESSED. | | | | 8.) PARKING STRIPING IS TO COMPLY WITH CITY OF WEST | | PALM BEACH STANDARD, SEE ATTACHED DETAIL. REVISE C1. | | | | ENGINEER?S RESPONSE IS THAT THE CONTRACTOR WILL | | ADDRESS. AN ACCESSIBLE ROUTE IS REQUIRED, AS WELL AS | | ACCESSIBLE PARKING. THEREFORE, IT APPEARS THAT THE SITE | | PLAN PREPARED BY AB DESIGN IS REQUIRED FOR CODE | | COMPLIANCE. | | | | SHEET 1, THE PARKING DETAIL DOES NOT MATCH THE SITE | | PLAN ON THE SAME PAGE. THE SITE PLAN SHOWS A WHEEL | | STOP, PARKING DETAIL SHOWS A VEHICLE OVERHANG. | | COMPLIANCE NOT CLEAR, SEE FBC11-4.6.3, OVERHANG SHALL | | NOT REDUCE THE CLEAR WIDTH OF ACCESSIBLE ROUTE. | | | | SEE ALSO COMMENT 23 FROM FIRST LIST; SHOW THE WIDTH OF | | THE SIDEWALK (ROUTE FROM THE ACCESSIBLE PARKING TO THE | | FRONT ENTRY), FBC11-4.6.2(1). | | | | 3RD REVIEW, SIDEWALK WIDTH NOT INDICATED | | FBC11-4.6.2(1). STRIPING DETAIL NOT IN COMPLIANCE WITH | | CITY STANDARDS. | | | | 9-22.) ADDRESSED. | | | | 23.) FROM FIRST LIST; COMMENT NOT ADDRESSED. SHOW THE | | SIDEWALK WIDTH ON THE PLAN, SIDEWALK BETWEEN ACCESSIBLE | | PARKING AND THE BUILDING. C1 SHOWS A 44INCH SIDEWALK, | | WITH A NOTE "SIDEWALK AS SHOWN ON PLAN" BUT THE | | ENGINEER'S PLAN DOESN'T SHOW ANY SIDEWALKS. THE | | LANDSCAPE ARCHITECT'S PLAN DOES NOT DIMENSION THE | | SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE ROUTE, AND THERE | | IS A CONFLICT BETWEEN THE PARKING DETAIL AND THE | | PARKING SHOWN ON THE SITE PLAN, BOTH ON AB DESIGN PAGE | | 1. THE PARKING DETAIL SHOWS A VEHICLE OVERHANG, PLAN | | SHOWS A WHEEL STOP. SEE FBC11-4.6.3, VEHICLE OVERHANGS | | CANNOT REDUCE THE CLEAR WIDTH. DESIGN INTENT IS NOT | | CLEAR. | | | | 2ND REVIEW, ENGINEER REMOVED SIDEWALK FROM PLAN, | | RESPONSE LETTER STATES THIS WILL BE ADDRESSED BY | | CONTRACTOR. PLEASE REVISE SITE PLAN TO SHOW CODE | | COMPLIANCE. | | | | 3RD REVIEW, CIVIL SHEETS SUBMITTED AND OTHER SITE PLANS | | PREVIOUSLY SUBMITTED REMOVED. THE NEW SHEETS DO NOT | | SHOW THE SIDEWALK WIDTH, FBC11-4.6.2(1), SEE ALSO | | COMMENT 8. | | | | 24-29.) ADDRESSED. | | | | 30.) THE PREVIOUS LISTS STATED THAT THE SHOWER BATHROOM | | MUST BE ACCESSIBLE, NOT ADAPTABLE. THE PLANS HAVE BEEN | | REVISED TO MAKE THIS ROOM ACCESSIBLE, BUT THE NOTE | | STATING THIS IS ADAPTABLE IS STILL ON THE PLAN. PLEASE | | REVISE TO REMOVE THIS NOTE. | | | | 31.) PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB | | BARS, MIRRORS, FBC 11. | | | | 2ND REVIEW, SEE PLUMBING COMMENTS. | | | | 3RD REVIEW, THE W/C IS SHOWN AS 1'4" FROM WALL, 18" | | REQUIRED, FBC11-4.16.2. PLEASE REVISE. | | | | 32-39.) ADDRESSED. | | | | 40.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED. | | PLEASE SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT | | GLASS AND FRONT DOOR. PRODUCT APPROVALS ARE TO BE | | REVIEWED BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FBC*106. | | | | 41.) FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND | | SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3. THIS CAN | | BE DONE AT THE TIME OF ROOF PERMIT APPLICATION. | | | | THE PRODUCT APPROVAL FOR THE ROOF HAS BEEN REMOVED FROM | | THE PACKAGE. THIS IS REQUIRED, REVIEWED BY DESIGNER OF | | RECORD. OTHER INFORMATION (ASSEMBLY, ENHANCED | | FASTENING) CAN BE SUBMITTED WITH THE ROOF PERMIT. | | | | 42.) SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ. | | PLEASE PROVIDE LEGIBLE COPIES. THEY MAY BE AVAILABLE AT | | WWW.BUILDINGCODEONLINE.COM. | | | | PLEASE SEE THE ROLLUP DOOR PRODUCT APPROVAL. IT IS | | ILLEGIBLE AND I CANNOT FIND/READ DESIGN PRESSURES. | | PLEASE MARK ON THE FLORIDA STATE PRODUCT APPROVAL WHICH | | PRODUCT YOU ARE USING AND SUBMIT COMPLETE, LEGIBLE | | DOCUMENTS FOR THAT PRODUCT. THIS IS AVAILABLE AT | | WWW.FLORIDABUILDING.ORG | | | | 3RD REVIEW, THE GARAGE DOOR PRODUCT APPROVAL HAS A | | DESIGN PRESSURE LIMITATION OF +-30PSF. +33.7/-36.7 | | REQUIRED, SEE PAGE A3. | | | | 43.) ADDRESSED. | | | | 44-45.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED. | | | | 46-51.) ADDRESSED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-08-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-08-01 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-08-01 |
Time |
09:01 |
Sent To |
|
|
Notes |
2008-08-01 09:02:07 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)WHEN RESUBMITTING, ALL CHANGES TO THE PLAN ARE TO | | BE CLOUDED AND INDICATED WITH REVISION MARKERS, REMOVE | | AND REPLACE REVISED SHEETS AS NECESSARY.INCLUDE A | | RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | ADDRESSED. | | | | 2.)ADDRESSED. | | | | 3.)PLEASE PROVIDE A BREAKDOWN OF COST FOR THE | | RENOVATION AREA AND NEW AREAS. | | | | 2ND REVIEW, PLEASE PROVIDE A REASONABLE VALUE FOR THIS | | JOB OR AN ESTIMATE WILL BE DONE USING MARSHALL & SWIFT | | OR MEANS. | | | | 4.)ALL CODE REFERENCES WERE REVISED TO INCLUDE 2007 | | REVISIONS/SUPPLEMENTS WITH THE EXCEPTION OF C1, | | PROPOSED, STILL REFERS TO 06 REVISIONS. | | | | 5.)PROVIDE A SURVEY FOR THIS PARCEL.THE SITE PLANS | | PROVIDED ARE NOT CONSISTENT. | | | | 2ND REVIEW, SEE SITE PLAN PREPARED BY AB DESIGN.THE | | EXISTING WAREHOUSE DOES NOT MATCH THE SURVEY OR C1. | | ONLY ONE SET OF THE SITE PLAN PREPARED BY AB DESIGN WAS | | SUBMITTED.TWO SETS NEEDED FOR PERMIT ISSUANCE.ONE | | SET HAS BEEN RETAINED.THEREFORE, IF THESE SHEETS ARE | | REQUIRED, SUBMIT TWO NEW ORIGINAL SETS. | | | | 6.)PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. | | TWO ORIGINALS REQUIRED. | | | | 2ND REVIEW, SEE THE SOILS REPORT AND FAC61G15-23.002, | | ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED ON | | A SIGNATURE PAGE OR COVER LETTER BY EACH PROFESSIONAL | | ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF | | THE REPORT, AND IF PRACTICING THROUGH A DULY AUTHORIZED | | ENGINEERING BUSINESS, THE NAME, ADDRESS AND CERTIFICATE | | OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS. | | THE SIGNATURES ARE TO BE ORIGINALS, NOT PHOTOCOPIES. | | | | 7.)ADDRESSED. | | | | 8.)PARKING STRIPING IS TO COMPLY WITH CITY OF WEST | | PALM BEACH STANDARD, SEE ATTACHED DETAIL.REVISE C1. | | | | ENGINEER?S RESPONSE IS THAT THE CONTRACTOR WILL | | ADDRESS.AN ACCESSIBLE ROUTE IS REQUIRED, AS WELL AS | | ACCESSIBLE PARKING.THEREFORE, IT APPEARS THAT THE | | SITE PLAN PREPARED BY AB DESIGN IS REQUIRED FOR CODE | | COMPLIANCE. | | | | SHEET 1, THE PARKING DETAIL DOES NOT MATCH THE SITE | | PLAN ON THE SAME PAGE.THE SITE PLAN SHOWS A WHEEL | | STOP, PARKING DETAIL SHOWS A VEHICLE OVERHANG. | | COMPLIANCE NOT CLEAR, SEE FBC11-4.6.3, OVERHANG SHALL | | NOT REDUCE THE CLEAR WIDTH OF ACCESSIBLE ROUTE. | | | | SEE ALSO COMMENT 23 FROM FIRST LIST; SHOW THE WIDTH OF | | THE SIDEWALK (ROUTE FROM THE ACCESSIBLE PARKING TO THE | | FRONT ENTRY), FBC11-4.6.2(1). | | | | 9.)ACCESSIBLE PARKING SIGNAGE IS TO COMPLY WITH | | FBC11-4.6.4; THE SIGN IS TO ALSO INCLUDE THE PENALTY. | | REVISE C1 AND AB DESIGN SHEET 1 OF 3. | | | | 2ND REVIEW, NOT ADDRESSED.SHEET 1 WAS NOT REVISED, | | AND ENGINEER?S RESPONSE IS THAT CONTRACTOR IS TO | | ADDRESS ACCESSIBLE PARKING. | | | | SHOW ACCESSIBLE PARKING SIGN LOCATION. | | | | 10-14.) ADDRESSED. | | | | 15.) TENANT SEPARATIONS SHOWN, BUT THE 1 HOUR REQUIRED | | DETAIL IS NOT COMPLETE.DETAIL 1 A5 WAS PROVIDED, BUT | | NOTHING ON THE FLOOR PLAN CORRELATES WITH THIS WALL | | DETAIL. PLEASE PROVIDE A DETAIL MARKER ON THE FLOOR | | PLAN TO SHOW COMPLIANCE WITH FBC703.2. | | | | PLEASE NOTE ALL REQUIRED FIRE RESISTIVE RATED | | CONSTRUCTION REQUIREMENTS ON THE PLAN.FOR INSTANCE, | | WALL BETWEEN OFFICE 1/MENS BATHROOM/BREAK ROOM/CLOSET | | AND WAREHOUSE BAY 2.ALTHOUGH BLOCK WOULD BY DESIGN BE | | A 1 HOUR WALL, UNLESS REQUIREMENTS ARE CLARIFIED, IT | | WOULD NOT BE CLEAR WHETHER FIRE DAMPERS, PENETRATION | | PROTECTION, SIGNAGE ABOVE DROPPED CEILINGS, ETC. WOULD | | BE REQUIRED.IF DESIGNING WITH OCCUPANCY SEPARATION, A | | 3 HOUR IS REQUIRED, SEE OTHER COMMENTS. | | | | 16-18.) ADDRESSED. | | | | 19.)SEE FBC TABLES 601, 602, 704.8.COMPLIANCE IS TO | | BE SHOWN ON THE PLAN. | | | | 2ND REVIEW, NORTH WALL IS SHOWN AS >30FEET.THE | | SERVICE ROAD IS 40FEET; DIMENSION SHOULD BE FROM THE | | EXTERIOR WALL TO CENTERLINE OF THE ROAD, 26FEET. PLEASE | | REVISE AND CHECK ALL. | | | | 20.) ADDRESSED. | | | | 21.)AB DESIGN LLC HAS AN APPLICATION PENDING FOR THE | | BUSINESS LICENSE.UNTIL THIS IS ISSUED, THIS COMPANY | | NAME CANNOT BE USED ON PLANS. | | | | A SET HAS BEEN RETAINED.PLEASE SEE OTHER COMMENTS, | | REVISE TO ADDRESS COMMENTS, AND SUBMIT TWO NEW ORIGINAL | | SIGNED, SEALED, DATED SETS.AB DESIGN, LLC IS TO BE | | REMOVED FROM THE TITLE BLOCK UNLESS A CERTIFICATE OF | | AUTHORIZATION HAS BEEN OBTAINED. | | | | 22.)SHOW ALL REQUIRED DETECTABLE WARNINGS, | | FBC11-4.29. | | | | 23.)FROM FIRST LIST; COMMENT NOT ADDRESSED.SHOW THE | | SIDEWALK WIDTH ON THE PLAN, SIDEWALK BETWEEN ACCESSIBLE | | PARKING AND THE BUILDING.C1 SHOWS A 44INCH SIDEWALK, | | WITH A NOTE "SIDEWALK AS SHOWN ON PLAN" BUT THE | | ENGINEER'S PLAN DOESN'T SHOW ANY SIDEWALKS.THE | | LANDSCAPE ARCHITECT'S PLAN DOES NOT DIMENSION THE | | SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE ROUTE, AND THERE | | IS A CONFLICT BETWEEN THE PARKING DETAIL AND THE | | PARKING SHOWN ON THE SITE PLAN, BOTH ON AB DESIGN PAGE | | 1.THE PARKING DETAIL SHOWS A VEHICLE OVERHANG, PLAN | | SHOWS A WHEEL STOP.SEE FBC11-4.6.3, VEHICLE OVERHANGS | | CANNOT REDUCE THE CLEAR WIDTH. DESIGN INTENT IS NOT | | CLEAR. | | | | 2ND REVIEW, ENGINEER REMOVED SIDEWALK FROM PLAN, | | RESPONSE LETTER STATES THIS WILL BE ADDRESSED BY | | CONTRACTOR.PLEASE REVISE SITE PLAN TO SHOW CODE | | COMPLIANCE. | | | | 24-25.) ADDRESSED. | | | | 26.)SEE FIGURE 11-7(6), TURNS AROUND AN OBSTRUCTION, | | AND DOOR 3 INTO THE GARAGE, FBC11-4.3.3. | | | | 27.)LABEL EACH ROOM AS TO USE, AREAS BEHIND THE | | BIFOLD DOORS 9 AND 10. | | | | 28.)SHOW THE ELEVATION ON EACH SIDE OF THE EXTERIOR | | DOORS, FBC11-4.13.8. | | | | 29.)IF 9 AND 10 ARE CLOSETS, THESE AREAS ARE TO BE | | ACCESSIBLE, SEE FBC11-4.25. | | | | 2ND REVIEW, PLEASE NOTE REQUIREMENT OF ACCESSIBLE DOORS | | AND HARDWARE ON THE PLAN. | | | | 30.)THE SHOWER IS TO COMPLY WITH FBC 11-4.23, | | FBC11-4.1.2(6).PROVIDE A DETAIL AND SHOW TURNING | | RADIUS. | | | | RESPONSE LETTER STATES THAT THE SHOWER IS ADAPTABLE AS | | NOTED ON THE PLAN.THIS BATHROOM MUST BE FULLY | | ACCESSIBLE FBC11-4.2(6); ADAPTABLE APPLIES ONLY TO | | PRIVATE TOILET ROOM (SUCH AS PRIVATE BATHROOM IN AN | | OFFICE), FBC11-4.1.3(11).PROVIDE A DETAIL FOR THE | | SHOWER FBC11-4.21. | | | | 31.)PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB | | BARS, MIRRORS, FBC 11. | | | | SEE PLUMBING COMMENTS. | | | | 32.)ADDRESSED. | | | | 33.)PROVIDE A DETAIL FOR THE BREAK ROOM SINK SHOWING | | COMPLIANCE WITH ALL REQUIREMENTS OF FBC11-4.24. | | | | I WAS UNABLE TO LOCATE A DETAIL.ALSO PLEASE NOTE THAT | | THERE IS NOT ENOUGH SPACE FOR TURNING RADIUS | | FBC11-4.2.3. | | | | 34-36.) ADDRESSED. | | | | 37.)BUILDING INFORMATION, C1, ITEM 8 NEW ADDITION | | STATES NON RATED, TABLE 302.3.2.THIS CODE SECTION IS | | FOR SEPARATED USE WHICH WOULD REQUIRE A FIRE RATED | | SEPARATION.SEE FBC 302.3.1, CORRELATE INFORMATION AND | | REVISE PLAN AS NECESSARY. | | | | NOT ADDRESSED; IF YOU ARE DESIGNING TO FBC 302.3.2 AS | | INDICATED ON PROPOSED, OCCUPANCY SEPARATION, 3 HOUR | | REQUIRED BETWEEN S1 AND B, FBC TABLE 302.3.2.NO | | OCCUPANCY SEPARATION IS REQUIRED IF DESIGNING USING NON | | SEPARATED USE FBC30.3.1 AND THE BUILDING COMPLIES WITH | | THE MOST STRINGENT OCCUPANCY REQUIREMENT OF FBC TABLE | | 501.A TENANT SEPARATION OF 1 HOUR WOULD STILL BE | | REQUIRED, SEE OTHER COMMENTS.PLEASE CONTACT ME IF YOU | | WOULD LIKE FURTHER CLARIFICATION. | | | | 38-39.) ADDRESSED. | | | | 40.)A NON IMPACT GLASS DOOR PRODUCT APPROVAL WAS | | SUBMITTED.SEE FBC10 FBC1003.6, MEANS OF EGRESS | | CONTINUITY.THE PATH OF EGRESS TRAVEL ALONG A MEANS OF | | EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT | | OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN | | CHAPTER 10.YOU CANNOT BLOCK EXIT DOORS WITH A | | HURRICANE PANELS. | | | | 2ND REVIEW, ENGINEER HAS SPECIFIED AN IMPACT GLASS DOOR | | BUT THE PRODUCT APPROVAL FOR IMPACT RATED GLASS DOOR | | WAS NOT SUBMITTED. THE NON IMPACT GLASS DOORS CAN BE | | USED WITH ACCORDION SHUTTERS FBC1008.1.3.6.AN | | ACCORDION PRODUCT APPROVAL WAS SUBMITTED, BUT THE | | INSTALLATION SCHEDULE WAS NOT COMPLETED SO IT CANNOT BE | | DETERMINED WHERE THE ACCORDIONS ARE PROPOSED. | | | | 41.)FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND | | SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3.THIS CAN | | BE DONE AT THE TIME OF ROOF PERMIT APPLICATION. | | | | THE PRODUCT APPROVAL FOR THE ROOF HAS BEEN REMOVED FROM | | THE PACKAGE.THIS IS REQUIRED, REVIEWED BY DESIGNER OF | | RECORD.OTHER INFORMATION (ASSEMBLY, ENHANCED | | FASTENING) CAN BE SUBMITTED WITH THE ROOF PERMIT. | | | | 42.)SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ. | | PLEASE PROVIDE LEGIBLE COPIES.THEY MAY BE AVAILABLE | | AT WWW.BUILDINGCODEONLINE.COM. | | | | PLEASE SEE THE ROLLUP DOOR PRODUCT APPROVAL.IT IS | | ILLEGIBLE AND I CANNOT FIND/READ DESIGN PRESSURES. | | PLEASE MARK ON THE FLORIDA STATE PRODUCT APPROVAL WHICH | | PRODUCT YOU ARE USING AND SUBMIT COMPLETE, LEGIBLE | | DOCUMENTS FOR THAT PRODUCT.THIS IS AVAILABLE AT | | WWW.FLORIDABUILDING.ORG | | | | 43.)ADDRESSED. | | | | 44.)SEE ATTACHED INSTALLATION SCHEDULE AND COMPLETE | | THIS FORM (REQUIRED FOR HURRICANE SHUTTERS). | | | | 2ND REVIEW, RETURNED BLANK.UPON REQUEST, THIS | | INFORMATION CAN BE PROVIDED WITH A SEPARATE PERMIT FOR | | SHUTTERS.HOWEVER, THE PLAN IS REQUIRED TO ADDRESS | | ITEM 40.EITHER SUBMIT AN IMPACT RATED PRODUCT | | APPROVAL FOR THIS DOOR, OR NOTE ON THE PLAN THAT IT | | WILL BE IMPACT WITH AN ACCORDION SHUTTER (CANNOT USE | | PANELS FOR THIS OPENING). | | | | SEE OTHER COMMENTS.THIS CAN, UPON REQUEST, BE | | PROVIDED WITH AN APPLICATION FOR SHUTTERS ON A SEPARATE | | PERMIT IF OTHER ISSUES ARE ADDRESSED ? PRESTORM | | PREPARATION PLAN (ITEM 45) AND EXITING ISSUE (ITEM | | 40). | | | | 45.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL | | PROPERTIES REQUIRES APPROVAL FROM THE BUILDING | | OFFICIAL.IF YOU ARE PROPOSING TO USE REMOVABLE | | SHUTTERS, SUBMIT A PRE STORM PREPARATION PLAN, SEE | | ATTACHED POLICY, ITEM 13.PROVIDE PRODUCT APPROVALS | | AND COMPLETE AN INSTALLATION SCHEDULE. | | | | THE INSTALLATION PLAN MAY BE SENT VIA EMAIL PRIOR TO | | RESUBMITTAL OF THE PLANS.CONTRACTOR IS ENCOURAGED TO | | GET THIS ISSUE RESOLVED PRIOR TO RESUBMITTAL TO AVOID | | DELAYS IN PERMITTING. | | | | 2ND REVIEW, NOT ADDRESSED.THIS IS REQUIRED FOR | | REMOVABLE PANELS BUT NOT FOR ACCORDIONS.BOTH PRODUCT | | APPROVALS WERE SUBMITTED.PLEASE CLARIFY DESIGN | | INTENT. | | | | 46-47.) ADDRESSED. | | | | NEW COMMENTS: | | | | 48.) SEE ENERGY CALCS SUBMITTED, SQUARE FOOT AREA IS TO | | MATCH THE PLAN; CONDITIONED AND UNCONDITIONED AREA IS | | TO BE INCLUDED. FBC13-101. | | | | 49.)WALL SECTIONS TO BE NOTED ON THE FLOOR PLAN.AN | | INSULATED WALL IS REQUIRED BETWEEN THE GARAGE AND | | CONDITIONED SPACE. | | | | 50.)ALL REQUIRED FIRE RESISTANCE IS TO BE SHOWN ON | | THE PLAN AS PENETRATIONS WILL BE REQUIRED TO BE | | PROTECTED.FOR INSTANCE, THE WALL BETWEEN BAY 2 AND | | THE GARAGE IS TO HAVE A 1 HOUR FIRE RESISTIVE RATING, | | FBC708.1(5).IF USING AN EXCEPTION, NOTE ON THE PLAN | | AND SHOW FIRE AREA. | | | | 51.)PLEASE NOTE THAT SOME COMMENTS WOULD HAVE BEEN | | REDLINE OR PROVISO ITEMS; HOWEVER, AS PLANS NEED TO BE | | CHANGED DUE TO COMMENTS FROM OTHER REVIEWERS, PLEASE | | REVISE AT THIS TIME. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-03-21 |
Time |
18:50 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-03-21 |
Time |
18:50 |
Sent To |
|
|
Notes |
2008-03-21 18:52:15 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)WHEN RESUBMITTING, ALL CHANGES TO THE PLAN ARE TO | | BE CLOUDED AND INDICATED WITH REVISION MARKERS, REMOVE | | AND REPLACE REVISED SHEETS AS NECESSARY.INCLUDE A | | RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | ADDRESSED. | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL | | 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE | | STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE | | PERMIT APPLICATION. | | | | 3.)PLEASE PROVIDE A BREAKDOWN OF COST FOR THE | | RENOVATION AREA AND NEW AREAS. | | | | 4.)GOVERNING CODE SHOULD INCLUDE 2007 | | REVISIONS/SUPPLEMENTS, FS553.ALSO SEE MP4, REFERS TO | | COUNTY AMENDMENTS TO THE STANDARD BUILDING CODE.OTHER | | CODE REFERENCES ON THIS PAGE ARE INCORRECT OR OUTDATED. | | CHECK ALL. | | | | 5.)PROVIDE A SURVEY FOR THIS PARCEL.THE SITE PLANS | | PROVIDED ARE NOT CONSISTENT. | | | | 6.)PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. | | TWO ORIGINALS REQUIRED. | | | | 7.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), | | FBC*106.3.3. | | | | 8.)PARKING STRIPING IS TO COMPLY WITH CITY OF WEST | | PALM BEACH STANDARD, SEE ATTACHED DETAIL.REVISE C1. | | | | 9.)ACCESSIBLE PARKING SIGNAGE IS TO COMPLY WITH | | FBC11-4.6.4; THE SIGN IS TO ALSO INCLUDE THE PENALTY. | | REVISE C1 AND AB DESIGN SHEET 1 OF 3. | | | | 10.)BUILDING INFORMATION IS TO STATE WHETHER THE | | BUILDING IS SPRINKLERED OR UN SPRINKLERED. | | | | 11.)BUILDING INFORMATION STATES THAT THE EXISTING | | BUILDING IS F1, NEW USE IS SHOWN AS WAREHOUSE WHICH | | WOULD BE STORAGE OCCUPANCY,FBC 311.NOTE CHANGE OF | | OCCUPANCY ON THE PLAN; THIS JOB WILL BE REQUIRED TO | | COMPLY WITH FBC EB CHAPTER 8. | | | | 12.)OCCUPANCY CALCULATIONS SHEET C1 STATE THAT THIS | | IS M, OTHER PLACES DECLARE THIS AS B BUT ALSO STATE | | THAT THIS IS STORAGE, GARAGE, AND WAREHOUSE.SEE FBC | | 302.1, PORTIONS OF BUILDINGS TO BE CLASSIFIED WITH | | RESPECT TO OCCUPANCY.DECLARE OCCUPANCY CLASSIFICATION | | AND SUB CLASSIFICATION FOR EACH AREA AS WELL AS SQUARE | | FOOT AREA FOR EACH OCCUPANCY. | | | | 13.)FOR THE STORAGE OCCUPANCIES (WAREHOUSE, STORAGE, | | GARAGE), DECLARE S1 AND S2 WITH SQUARE FOOT AREAS FOR | | EACH, SEE FBC311.2, FBC406. | | | | 14.)DECLARE OCCUPANT LOAD FOR EACH AREA, FBC1004. | | | | 15.)IS THIS BUILDING FOR ONE TENANT OR MULTIPLE | | TENANTS?NOTE THIS INFORMATION ON THE PLAN AND SHOW | | TENANT SEPARATION IF REQUIRED.NO SEPARATION SHOWN | | BETWEEN THE OFFICE, BAY 1, AND BAY 2. | | | | 16.)PROPERTY APPRAISER WEBSITE AND AB DESIGN SHOWS | | THE EXISTING BUILDING AS 1710 SF, ENGINEER SHOWS THIS | | BUILDING AS 1438 ON C1.EITHER REVISE OR PROVIDE | | INFORMATION TO SHOW WHY ENGINEER?S SQUARE FOOT TOTAL | | CONFLICTS WITH PAPA AND LANDSCAPE ARCHITECT. | | | | 17.)THIS BUILDING APPEARS TO BE A MIXED OCCUPANCY | | FBC302, PLEASE DECLARE AS SUCH AND DECLARE AS EITHER | | SEPARATED OR NON SEPARATED USE. | | | | 18.)EXISTING BUILDING DECLARES THIS AS BUILDING TYPE | | IIB, BUT A1 SHOWS FIRE DAMAGED WOOD GIRDER, OTHER WOOD | | STRUCTURAL ELEMENTS, AND S4 SHOWS PT WOOD BUCKS.TYPE | | II IS NONCOMBUSTIBLE CONSTRUCTION; SEE ALSO FBC603. | | | | 19.)SEE FBC TABLES 601, 602, 704.8.COMPLIANCE IS TO | | BE SHOWN ON THE PLAN. | | | | 20.)EE-S3, F-S3, ANY OTHER APPLICABLE DETAILS, | | SPECIFY THE WELDS. | | | | 21.)AB DESIGN LLC HAS AN APPLICATION PENDING FOR THE | | BUSINESS LICENSE.UNTIL THIS IS ISSUED, THIS COMPANY | | NAME CANNOT BE USED ON PLANS. | | | | 22.)SHOW ALL REQUIRED DETECTABLE WARNINGS, | | FBC11-4.29. | | | | 23.)SHOW THE SIDEWALK WIDTH ON THE PLAN, SIDEWALK | | BETWEEN ACCESSIBLE PARKING AND THE BUILDING.C1 SHOWS | | A 44INCH SIDEWALK, WITH A NOTE ?SIDEWALK AS SHOWN ON | | PLAN? BUT THE ENGINEER?S PLAN DOESN?T SHOW ANY | | SIDEWALKS.THE LANDSCAPE ARCHITECT?S PLAN DOES NOT | | DIMENSION THE SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE | | ROUTE, AND THERE IS A CONFLICT BETWEEN THE PARKING | | DETAIL AND THE PARKING SHOWN ON THE SITE PLAN, BOTH ON | | AB DESIGN PAGE 1.THE PARKING DETAIL SHOWS A VEHICLE | | OVERHANG, PLAN SHOWS A WHEEL STOP.SEE FBC11-4.6.3, | | VEHICLE OVERHANGS CANNOT REDUCE THE CLEAR WIDTH. DESIGN | | INTENT IS NOT CLEAR. | | | | 24.)N/A | | | | 25.)IS THE LANDSCAPE ARCHITECT TAKING RESPONSIBILITY | | FOR COMPLIANCE WITH FBC CHAPTER 11, FBC TABLE 601, 602, | | 704.8 AS THE ENGINEER HAS NOT PROVIDED A SITE PLAN | | SHOWING THE INFORMATION REQUIRED TO DETERMINE CODE | | COMPLIANCE?ON THE SITE PLAN, DECLARE GOVERNING CODE | | FS553. | | | | 26.)SEE FIGURE 11-7(6), TURNS AROUND AN OBSTRUCTION, | | AND DOOR 3 INTO THE GARAGE, FBC11-4.3.3. | | | | 27.)LABEL EACH ROOM AS TO USE, AREAS BEHIND THE | | BIFOLD DOORS 9 AND 10. | | | | 28.)SHOW THE ELEVATION ON EACH SIDE OF THE EXTERIOR | | DOORS, FBC11-4.13.8. | | | | 29.)IF 9 AND 10 ARE CLOSETS, THESE AREAS ARE TO BE | | ACCESSIBLE, SEE FBC11-4.25. | | | | 30.)THE SHOWER IS TO COMPLY WITH FBC 11-4.23, | | FBC11-4.1.2(6).PROVIDE A DETAIL AND SHOW TURNING | | RADIUS. | | | | 31.)PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB | | BARS, MIRRORS, FBC 11. | | | | 32.)SHOW CLEAR FLOOR SPACE FOR ALL FIXTURES AND | | CLOSETS. | | | | 33.)PROVIDE A DETAIL FOR THE BREAK ROOM SINK SHOWING | | COMPLIANCE WITH ALL REQUIREMENTS OF FBC11-4.24. | | | | 34.)THE BATHROOM AT DOOR 4 IS TO BE ACCESSIBLE, | | FBC11-4.1.2(6). | | | | 35.)SHOW MANEUVERING CLEARANCE, PULL SIDE, FBC FIGURE | | 11-25 DOORS 3, 6, 7. | | | | 36.)INTERIOR FINISHES TO COMPLY WITH FBC TABLE 803.5. | | IT APPEARS TO BE COMPLIANT BUT CANNOT BE CONFIRMED | | UNTIL SPRINKLER AND OCCUPANCY INFORMATION HAS BEEN | | CONFIRMED. | | | | 37.)BUILDING INFORMATION, C1, ITEM 8 NEW ADDITION | | STATES NON RATED, TABLE 302.3.2.THIS CODE SECTION IS | | FOR SEPARATED USE WHICH WOULD REQUIRE A FIRE RATED | | SEPARATION.SEE FBC 302.3.1, CORRELATE INFORMATION AND | | REVISE PLAN AS NECESSARY. | | | | 38.)SPECIFY COMPONENTS AND CLADDING PRESSURES FOR THE | | ROOF. | | | | 39.)PROVIDE A DETAIL FOR THE AC UNIT CURB, FBC1609. | | | | 40.)A NON IMPACT GLASS DOOR PRODUCT APPROVAL WAS | | SUBMITTED.SEE FBC10 FBC1003.6, MEANS OF EGRESS | | CONTINUITY.THE PATH OF EGRESS TRAVEL ALONG A MEANS OF | | EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT | | OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN | | CHAPTER 10.YOU CANNOT BLOCK EXIT DOORS WITH A | | HURRICANE SHUTTERS. | | | | 41.)FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND | | SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3.THIS CAN | | BE DONE AT THE TIME OF ROOF PERMIT APPLICATION. | | | | 42.)SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ. | | PLEASE PROVIDE LEGIBLE COPIES.THEY MAY BE AVAILABLE | | AT WWW.BUILDINGCODEONLINE.COM. | | | | 43.)THE EASTERN METAL PRODUCT APPROVAL IS ILLEGIBLE. | | PROVIDE LEGIBLE COPIES. | | | | 44.)SEE ATTACHED INSTALLATION SCHEDULE AND COMPLETE | | THIS FORM (REQUIRED FOR HURRICANE SHUTTERS). | | | | 45.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL | | PROPERTIES REQUIRES APPROVAL FROM THE BUILDING | | OFFICIAL.IF YOU ARE PROPOSING TO USE REMOVABLE | | SHUTTERS, SUBMIT A HURRICANE INSTALLATION PLAN, SEE | | ATTACHED POLICY, ITEM 13.PROVIDE PRODUCT APPROVALS | | AND COMPLETE AN INSTALLATION SCHEDULE. | | | | THE INSTALLATION PLAN MAY BE SENT VIA EMAIL PRIOR TO | | RESUBMITTAL OF THE PLANS.CONTRACTOR IS ENCOURAGED TO | | GET THIS ISSUE RESOLVED PRIOR TO RESUBMITTAL TO AVOID | | DELAYS IN PERMITTING. | | | | 46.)THE PRODUCT APPROVALS FOR THE STORM PANELS ARE | | EXPIRED, FBC2001 RATHER THAN FBC2004.CURRENT | | APPROVALS REQUIRED FAC9B72. | | | | 47.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | IN ADDITION TO THE NOA SUBMITTED, FAC9B72. | | WWW.FLORIDABUILDING.ORG |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2008-12-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-12-05 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-12-05 |
Time |
09:04 |
Sent To |
|
|
Notes |
2008-12-05 09:05:16 | ** PROVISO** | | | | | | | | 1) NOTE: WATER HEATER LOAD IN AMPERAGE NOT SHOWN | | CORRECTLY. LOAD IS ALSO A CONTINUOUS LOAD UNDER 2005 | | NEC 422.13. | | | | REVISE CALCULATIONS AND LOADS ALONG ON WATER HEATER. | | THIS WILL BE NEEDED ALONG WITH ANY OTHER REVISIONS MADE | | TO PLANS. | | | | IF THERE ARE QUESTIONS, PLEASE CALL. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2008-12-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-12-01 |
Time |
14:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-12-01 |
Time |
14:48 |
Sent To |
|
|
Notes |
2008-12-01 15:00:47 | ** TEMP FAILED** | | | | | | 1) NOTE: THE PLANS SUBMITTED IN THE TWO SETS ARE THE | | SAME EXACT SHEETS SIGNED, DATED AND SEALED OCTOBER 3RD, | | 2008. THE LAST ELECTRICAL REVIEW WAS DONE ON OCTOBER | | 21ST, 2008. | | THE SUBMITTED ENERGY CALCULATIONS ARE THE SAME FROM THE | | PREVIOUS REVIEW ALSO. | | | | CALLED AND LEFT MESSAGE WITH CONTRACTOR TO FIND OUT | | WHERE NEW SHEETS AND PLANS ARE? | | | | | | | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-10-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-30 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-30 |
Time |
16:55 |
Sent To |
|
|
Notes |
2008-10-30 16:55:32 | | | | | ** DENIED REVIEW** | | | | ** A CALL WAS PLACED TO THE ENGINEER OF RECORD AT THE | | TIME OF THIS REVIEW HOWEVER WAS NOT IN THE OFFICE. A | | MESSAGE WAS LEFT SO THESE ITEMS BELOW COULD BE GONE | | OVER. PLANS ARE COMING BACK WITH COMMENTS FROM OTHER | | TRADES | | | | 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS CAN NOT BE | | STAMPED OR SIGNED OFF BY ELECTRICAL AS THERE ARE ERRORS | | WITH OTHER COMPONENTS TO THE BUILDING WHICH DO NOT | | COORDINATE WITH PLANS. SEE COMMENTS FROM OTHER TRADES. | | (BUILDING) | | EXAMPLE WOULD BE THE FLOORS WHICH ARE USING CARPET AND | | RUBBER PADDING WHERE THE FINISH SCHEDULE ON THE C SHEET | | INDICATE CONCRETE, TILE, ETC | | THE IDR NEEDS TO INDICATE THE WATER HEATER SIZE WHICH | | COORDINATES WITH PLANS. SEE NEXT COMMENT FOR LOADS. | | FBC 13-400.3A | | | | 2) NOTE: PLEASE SEE THE LOADS WHICH ARE SHOWN ON THE | | PANEL SCHEDULES ARE IN QUESTION. THE PANEL INDICATES | | LOADS BY *AMPS* FOR EACH PHASE HOWEVER PLEASE SEE SMALL | | APPLIANCE(S), MICROWAVE AND OTHER SIMILAR ITEMS WHICH | | ARE SHOWN AS 1.5AMPS, 1.2 AMPS ETC. IS THIS NOT KVA? | | PLEASE SEE PANEL *A* FOR EXAMPLE: | | PLEASE SEE THE LOAD FOR THE WATER HEATER WHICH STATES | | 20.0AMPS PER PHASE. WHAT SIZE OF WATER HEATER IS THIS? | | PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH HAS BEEN | | REVISED TO CONSIDER STORAGE TYPE WATER HEATERS AS | | CONTINUOUS LOADS. THIS WOULD REQUIRE LOAD CALCULATIONS | | TO SHOW 125% FOR THIS UNIT. | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-08 |
Time |
13:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-08 |
Time |
13:31 |
Sent To |
|
|
Notes |
2008-07-08 13:31:41 | ** DENIED2ND REVIEW ** | | | | ** PLEASE KNOW THERE ARE SOME ITEMS FROM PREVIOUS | | REVIEW IN NEED OF ADDRESSING. | | | | ** PLEASE SEE THERE ARE SOME NEW ITEMS FROM THIS REVIEW | | WHICH ARE NEW BASED ON REVISED PLANS AND DOCUMENTS SUCH | | AS ENERGY CALCULATIONS ONLY NOW BEING SUBMITTED FOR THE | | FIRST TIME. | | | | 1) NOTE: PLEASE REVISED AND VERIFY CODE LISTED ON E-3. | | PLANS SHOULD READ FBC 2004 W/ 2007 REVISIONS HOWEVER | | PLANS SHOW FBC 2004/2007. THIS COULD MISLEAD TO AN | | UNDERSTANDING THAT THE 2007 FBC MAY BE USED OR IS PART | | OF THE DESIGN. | | PLEASE REVISE. IF THIS WERE THE ONLY ITEMS PLANS COULD | | HAVE BEEN REDLINED. | | | | 2) NOTE: PLEASE SEE ELECTRICAL NOTES ADDED TO SHEET E-1 | | STATES LIGHTING CONTROLS TO BE INSTALLED HOWEVER PLANS | | DO NOT SHOW ANY LIGHTING CONTROLS. MAY NOT QUOTE THE | | CODE IN LIEU OF DESIGN. | | PLEASE CALL TO GO OVER LIGHTING CONTROLS FOR AREAS | | WHICH ARE REQUIRED. SQ FT IS NOW BEING SHOWN LESS THAN | | 5K SQ FT HOWEVER THERE ARE SOME AREAS WHICH STILL | | REQUIRE AUTOMATED CONTROLS. | | 13-415.1.ABC.1.1, .1.2, .1.3. | | | | ** THE INPUT DATA REPORT SHOWS OCCUPANCY SENSORS AS THE | | METHOD OF CONTROLS. | | | | 3) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS | | ALONG WITH THE INPUT DATA REPORT WHICH IS PART OF THE | | CALCULATIONS DO NOT COORDINATE WITH THE PLANS | | SUBMITTED. THE INPUT DATA REPORT WILL BE NOTED AS IDR | | IN THE REMAINDER OF THIS COMMENT. THERE WILL BE SEVERAL | | EXAMPLES GIVEN AS A BENEFIT HOWEVER THESE EXAMPLES ARE | | NOT AN EXHAUSTED LIST OF ALL POSSIBLE ITEMS. | | ** PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND | | .1.3. | | PLEASE KEEP IN MIND THE FIXTURE WATTAGE IS REQUIRED TO | | BE USED NOT THE BULB WATTAGE. | | | | FOR EXAMPLE: | | PLEASE SEE THE LIGHTING SHOWN ON THE IDR FOR EXTERIOR | | LIGHTING. PLANS SHOW AS MANY AS 6 75WATT EXTERIOR | | FIXTURES YET THE IDR SHOW ONLY 4. | | | | FOR EXAMPLE: | | THE IDR DOES NOT SHOW ANY OF THE 175W FIXTURES AS SHOWN | | ON PLANS FOR FLOODS YET THE PLANS SHOW AS MANY AS 8 TWO | | HEADED FLOODS. | | | | FOR EXAMPLE: | | THERE IS HOT WATER PIPING IN BUILDING YET THE IDR IS | | BLANK. (NOTED FOR OTHER TRADES AS FYI) | | | | FOR EXAMPLE: | | PLEASE SEE THE IDR FOR THE AMOUNT OF DOORS FROM | | CONDITIONED SPACE TO UNCONDITIONED SPACE. ( NOTED FOR | | OTHER TRADES AS FYI) | | | | FOR EXAMPLE: | | PLEASE TAKE A LOOK AT THE SQUARE FOOTAGE SHOWN FOR | | CONDITIONED AND UNCONDITIONED SPACE. THE SUBMITTED | | ENERGY CALCULATIONS INDICATE A TOTAL OF 1986 SQ FT YET | | THE PLANS SHOW OVER 4K SQ FT. | | PLEASE CORRELATE ALL. | | | | FOR EXAMPLE: | | PLEASE SEE THE INTERIOR LIGHTING AS ONLY SOME OF THE | | 128W FIXTURES ARE SHOWN IN THE IDR. IN FACT ONLY 6 OF | | THESE FIXTURES ARE SHOWN WHEN THE PLANS SHOW MORE THAN | | TWO DOZEN. | | | | | | ** THE ABOVE ARE SOME EXAMPLES. | | | | 4) NOTE: PLEASE COORDINATE THE PANELS ON THE RISER WITH | | THE PANELS ON THE PANEL SCHEDULE. THE PANELS ARE BEING | | SHOWN AS 100AMPS ON RISER AND 200AMPS ON SCHEDULES. | | 408, 310, | | FBC 106.1.1 FOR CLARITY AND COORDINATION. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-03-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-11 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-11 |
Time |
12:59 |
Sent To |
|
|
Notes |
2008-03-11 12:59:34 | ** DENIED** | | | | FIRST REVIEW UNDER NEW PERMIT APPLICATION FOR THIS | | ADDRESS. | | PREVIOUS REVIEW WAS DONE UNDER APPLIED # 07030453 WHICH | | HAS NOW EXPIRED. | | | | | | | | 1) NOTE:PLEASE SEE THE FOLLOWING CODES SHALL BE | | STATED ON PLANS. NEEDS TO BE ON ELECTRICAL PLANS AS | | WELL AS COVER SHEET. | | 2004 FBC W/2007 REVISIONS. | | 2005 NFPA-70 | | 2003 NFPA-101 | | 2002 NFPA-72 (PLANS SHOW 2004) | | | | 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUESTED | | ON PREVIOUS REVIEW. AS THESE WERE NOT SUBMITTED NO | | REVIEW OF THESE ITEMS COULD BE DONE AT THIS TIME. | | PLEASE SEE 13-101.1.2, 13-400.3.B, 13-400.3.C, | | 13-415.2.ABC.1.1, .1.2 AND .1.3. | | | | 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 AND .1.4 FOR | | MISSING LIGHTING CONTROLS. | | PLEASE BE SURE TO SEE AUTOMATED CONTROLS REQUIRED IN | | .1.2 FOR INTERIOR LOCATIONS AS NOTED IN THE CODE. | | PLEASE BE SURE TO PROVIDE THE INFORMATION FOR EXTERIOR | | CONTROLS AS REQUIRED IN .1.4 AS NOTED ABOVE. | | | | 4) NOTE: PLEASE SEE E-2 AS THIS WAS PRINTED AND MUCH OF | | THE INFORMATION ON PANEL SCHEDULE FOR LOADS, CIRCUITING | | ETC IS BLURRY AND NOT EASILY READ. | | PLEASE REPRINT WITH MORE CLARITY. | | FBC 106.1 | | | | 5) NOTE: PLEASE SEE SERVICE RISER ONLY SHOWS ONE RISER | | AND ONLY ONE SET OF CONDUCTORS. THERE IS PART OF THE | | CONDUCTORS WHICH NOTES *EACH* HOWEVER NO INFORMATION ON | | IF THERE ARE PARALLEL RISERS. | | PLEASE SHOW FOR PARALLEL CONDITIONS AS REQUIRED. | | 240.4, 310.16 | | FBC 106.3.5.1.2, 106.1.2 | | | | 6) NOTE: PLEASE SEE THE GROUNDING ELECTRODE IS NOTED TO | | STRUCTURAL STEEL HOWEVER IS ALSO REQUIRED TO FOOTER | | STEEL PER 250.50 | | | | 7) NOTE: PLEASE SEE RISER IS MISSING ANY METERING | | DEVICE? METER CAN, CT ETC. | | PLEASE CONTACT FPL FOR SERVICE REQUIREMENTS AND SEE FPL | | MINIMUM SERVICE SPECIFICATIONS. THIS INFORMATION CAN BE | | FOUND AT FPL WEBSITE. | | HTTP://WWW.FPL.COM/DOINGBUSINESS/BUILDER/B1_INDEX.SHTML | | | | | | 8) NOTE: PLEASE PROVIDE THE ACTUAL AIC RATING OF THE | | EQUIPMENT. THE PLANS INDICATE THE AVAILABLE FAULT | | CURRENT AT SERVICE ETC HOWEVER DOES NOT PROVIDE RATINGS | | ON EQUIPMENT. | | 110.9, 110.3, 90.7 | | FBC 106.1.2 | | | | 9) NOTE: PLEASE PLACE THE REQUIRED DISCONNECTS FOR ANY | | ROOF-TOP A/C EQUIPMENT ON ELECTRICAL PLANS. | | 440.11 | | | | 10) NOTE: PLEASE SEE 210.63 AND 210.8B FOR GFI REQUIRED | | FOR ANY ROOF-TOP AC EQUIPMENT. | | | | 11) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL | | FIXTURES ON PLANS. | | PLEASE BE SURE TO SEE NOTE #2 FOR COORDINATION WITH THE | | ENERGY CALCULATIONS TO BE SUBMITTED. | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. | | | | 12) NOTE: PLEASE SEE SEVERAL NOTES ON E-3 STATES THERE | | MAY BE SOME SORT OF FIRE ALARM SYSTEM HOWEVER NO SYSTEM | | COULD BE LOCATED ON PLANS. | | THERE ARE ALSO NOTES WHICH STATES THE HORN AND STROBE | | LEVELS SHALL MEET NFPA-72, HOWEVER PLEASE SEE FBC | | 11?4.28.1, .2 AND .3(4) FOR MINIMUM LOCATIONS AND | | LEVELS FOR FBC ADA. | | | | 13) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET | | NEC 220. | | PLEASE SEE PANEL *A* FOR EXAMPLE*: HOW ARE THE | | APPLIANCE LOADS BEING FIGURED? | | PLEASE SEE 220.12, 220.14, 220.42, 220.44 ETC. | | CONTINUOUSLOADS WERE SHOWN AT 125%. | | | | 14) NOTE: PLEASE SEE THE PLANS NEED TO IDENTIFY THE | | LOCATION OF PANEL *A* AS AN ELECTRICAL ROOM. THIS MAY | | NOT BE A CLOSET. | | SIGNAGE WILL ALSO BE REQUIRED. | | 110.26, 240.24, 408.17 ETC | | FBC 106.1.2 | | | | *** AS NOTED, AS THERE SOME ITEMS NOT YET SUBMITTED A | | FULL AND COMPLETE REVIEW CAN NOT BE DONE.PLEASE KNOW | | THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS | | TIME. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2008-12-23 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2008-12-23 |
Time |
08:03 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2008-12-23 |
Time |
08:01 |
Sent To |
ENG |
|
Notes |
2008-12-23 08:03:40 | PASSED | | | | ADDITIONAL INFORMATION WAS REQUESTED BY THE CITY'S | | STORMWATER ENGINEER JEFF RENAULT, | | IT WAS RESPONDED TO AND SATIFIED. HIS STATEMENT: "I | | HAVE REVIEWED THE REVISED GRADING AND DRAINAGE PLAN AND | | DRAINAGE CALCULATIONS FOR THE SUBJECT PROJECT AS | | SUBMITTED BY BKGES ,ENGINEERING , INC AND RECOMMEND | | APPROVAL OF THE SITE DRAINAGE FEATURES AS SUBMITTED. | | SHOULD YOU HAVE ANY QUESTIONS , PLEASE CONTACT ME." | | | | | | MANNY GONZALEZ | | PROJECT COORDINATOR | | ENGINEERING SERVICES. | | (561) 494-1085 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2008-11-18 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2008-11-18 |
Time |
|
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2008-11-18 |
Time |
|
Sent To |
ENG |
|
Notes |
2008-11-18 15:35:24 | - PASSED - | | | | REVIEW AT ENGINEERING DEPT WAS PERFORM AND APPROVED | | AS-NOTED. ANY QUESTIONS PLEASE CONTACT: | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR 561-494-1085 | | LOCATION ADDRESS: | | CITY OF WEST PALM BEACH | | ENGINEERING SERVICES DEPARTMENT | | 1000 - 45TH STREET, SUITE 15 | | WEST PALM BEACH FL 33407 | | MAILING ADDRESS: | | CITY OF WEST PALM BEACH | | ENGINEERING SERVICES DEPARTMENT | | P.O. BOX 3506 | | WEST PALM BEACH FL 33401 | | TELEPHONE: | | 45TH STREET OFFICE : 561-494-1040 | | 45TH DIRECT: 561-494-1085 | | FAX: 561-494-1117 | | CITY HALL OFFICE: (561) 805-6723 | | CITY HALL DIRECT: (561) 805-6327 | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | NEXTEL: 561-644-7301 | | NEXTEL DIRECT CONNECT: 159*28165*38 | | EMERGENCIES: | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | E-MAIL: | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2008-06-27 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2008-06-27 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2008-06-27 |
Time |
13:45 |
Sent To |
|
|
Notes |
2008-06-27 13:52:11 | FAILED | | | | MR. S. M. SINCLAIR, P.E. WROTE IN HIS RESPOND, DATED | | JUNE 9, 08 THAT"CONTRACTOR TO ADDRESS ALL ENG-RELATED | | COMMENTS".WE LOOKED IN YOUR WHOLE PACKAGE, WE DID NOT | | FIND CONTRACTOR'S RESPOND FOR OUR ENG COMMENTS. | | THEREFORE, PLEASE RESPOND TO ENG REVIEW COMMENT FOR REV | | 1, 3-18-08 AS FOLLOWS. | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | NOI. | | YOU CAN GET NOI INFO FROM | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | EFFECTIVE MAY 1, 2003 | | | | IF THE TOTAL AREA IS LESS THAN AN ACRE,NOI NOT | | REQUIRED. | | | | 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS & | | TURBIDITY DETAILS OFPOLLUTION PREVENTION , CLOTHES | | USED FOR SILT FENCE ETC., PLANS SHOWING SILT FENCE | | AROUND THE SITE & TURBIDITY AROUND STORM CATCH BASIN | | DRAINS DURING CONSTRUCTION AND ALL DEMOLITION PHASE. | | HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP | | DUST PARTICLES. | | | | 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO. | | 4060-07: | | | | ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH | | EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY | | APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE | | FOLLOWING: | | | | 1. EROSION CONTROL, AND | | 2. LAND STABILIZATION | | | | THE AMOUNT OF THE EROSION CONTROL AND LAND | | STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER | | OF RECORD USING THE CURRENT CITY COST SCHEDULE AND | | VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT. | | PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION | | SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION. | | | | UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN | | FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL | | TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE | | MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS. | | | | A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM | | THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR. | | | | 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL | | CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING | | SERVICES, PHONE# 494-1040 | | | | 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED | | FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA | | AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST | | FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE | | ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD. | | | | 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA, | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU | | ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE | | PROVIDE A COPY OF THESE CALCULATIONS. | | | | 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM | | ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL | | ENVRONMENTAL REPORT. | | | | 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | FLOODED AND HAVE ENOUGH DRAINS. | | | | 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH | | REPORT&STORM WATER QUALITY CALCULATIONS. STORM | | WATER CALS MUST BE APPROVED FROM 100045TH STREET | | ENGINEERING SERVICES BEFORE WE APPROVE. | | | | 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G. | | OF 1000 45TH STREET BEFORE WE ISSUE PERMIT. | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | PERMITTING PROCESS | | | | RASIK CHOKSHI805-6723 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2008-03-18 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2008-03-18 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2008-03-18 |
Time |
13:36 |
Sent To |
|
|
Notes |
2008-03-18 13:40:48 | FAILED FOR FOLLOWING REASONS: | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | NOI. | | YOU CAN GET NOI INFO FROM | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | EFFECTIVE MAY 1, 2003 | | | | IF THE TOTAL AREA IS LESS THAN AN ACRE,NOI NOT | | REQUIRED. | | | | 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS & | | TURBIDITY DETAILS OFPOLLUTION PREVENTION , CLOTHES | | USED FOR SILT FENCE ETC., PLANS SHOWING SILT FENCE | | AROUND THE SITE & TURBIDITY AROUND STORM CATCH BASIN | | DRAINS DURING CONSTRUCTION AND ALL DEMOLITION PHASE. | | HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP | | DUST PARTICLES. | | | | 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO. | | 4060-07: | | | | ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH | | EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY | | APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE | | FOLLOWING: | | | | 1. EROSION CONTROL, AND | | 2. LAND STABILIZATION | | | | THE AMOUNT OF THE EROSION CONTROL AND LAND | | STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER | | OF RECORD USING THE CURRENT CITY COST SCHEDULE AND | | VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT. | | PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION | | SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION. | | | | UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN | | FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL | | TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE | | MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS. | | | | A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM | | THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR. | | | | 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL | | CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING | | SERVICES, PHONE# 494-1040 | | | | 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED | | FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA | | AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST | | FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE | | ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD. | | | | 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA, | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU | | ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE | | PROVIDE A COPY OF THESE CALCULATIONS. | | | | 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM | | ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL | | ENVRONMENTAL REPORT. | | | | 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | FLOODED AND HAVE ENOUGH DRAINS. | | | | 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH | | REPORT&STORM WATER QUALITY CALCULATIONS. STORM | | WATER CALS MUST BE APPROVED FROM 100045TH STREET | | ENGINEERING SERVICES BEFORE WE APPROVE. | | | | 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G. | | OF 1000 45TH STREET BEFORE WE ISSUE PERMIT. | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | PERMITTING PROCESS | | | | RASIK CHOKSHI805-6723 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-12-12 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-12-12 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-12-12 |
Time |
14:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-11-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-11-14 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-11-14 |
Time |
14:22 |
Sent To |
|
|
Notes |
2008-11-14 14:23:15 | *****FIRE STAMPING NEEDED***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED; THE APPROPIATE PLAN SHEETS TO BE | | FIRE-STAMPED WHEN ALL PLAN EXAMINERS' COMMENTS HAVE | | BEEN SATISFIED. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2008-07-21 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-07-21 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-07-21 |
Time |
10:52 |
Sent To |
|
|
Notes |
2008-07-21 11:07:50 | ***DENIED*** | | | | 1) RESPONSE LETTER INDICATES DEMOLITION ONLY. NFPA 241 | | IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION, | | ALTERATION AND DEMOLITION OPERATIONS. PLEASE CORRECT | | ELECTRICAL NOTE ON SHEET E-3 NEXT TO NFPA 241. | | | | 2) OK | | | | 3) OK | | | | 4) RESPONSE LETTER INDICATES MULTIPLE TENANTS. PLEASE | | CLEARLY ILLUSTRATE OR CLARIFY (1) HOUR SEPARATION | | REQUIREMENTS BETWEEN TENANTS. | | | | 5) OK | | | | 6) OK | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-03-31 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-31 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-31 |
Time |
14:21 |
Sent To |
|
|
Notes |
2008-03-31 15:10:16 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2. CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE | | PROPERTY OR VICINITY THEREOF (INCLUDING ROADS, STREETS, | | FIRE LANES) | | | | 3. ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS | | EAST TAMARIND AVENUE, DISPLAY THE NUMERICAL ADDRESS OF | | THE BUILDING. AS PER WEST PALM BEACH CODE, ADDRESS | | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS | | THAN 1" IN WIDTH. | | | | 4. PROVIDE THE FOLLOWING INFORMATION: * WILL THE | | BUILDING BE OCCUPIED BY A SINGLE TENANT OR MULTIPLE | | TENANTS, * OCCUPANCY TYPE FOR EACH TENANT SPACE, * | | OCCUPANT LOAD FOR EACH TENANT SPACE, * IS THE BUILDING | | FIRE SPRINKLERED OR NOT? | | | | 5. IT IS NOTED ON SHEET C1 OF "FIRE ALARM PERMIT BY | | OTHERS". DOES THE BUILDING HAVE A FIRE ALARM SYSTEM? IF | | SO, PROVIDE A LAYOUT OF THE SYSTEM. | | | | 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL | | DISTANCE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2010-01-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2010-01-12 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2010-01-12 |
Time |
12:59 |
Sent To |
|
|
Notes |
2010-01-12 13:19:02 | THIS REVISION WAS SUBITTED FOR BUILDING ONLY. THERE ARE | | 4 REVISIONS ON THESE PAGES THAT HAVE NOT BEEN REVIEWED, | | FIRE, ELECTRICAL, PLUMBING AND MECHANICAL NCALLED EZRA | | AND INFORMED HIM AND AM WAITING FOR A CALL BACK./WRT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-11-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-25 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-25 |
Time |
10:11 |
Sent To |
|
|
Notes |
2008-11-25 10:15:04 | TO "COMM" BD#37 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-10-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-15 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-15 |
Time |
16:58 |
Sent To |
|
|
Notes |
2008-10-17 10:09:45 | TO "COMM" BD#54 | 2008-10-15 16:59:25 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-06-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-13 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-13 |
Time |
13:48 |
Sent To |
|
|
Notes |
2008-06-13 13:48:30 | TO "COMM" BD#30 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-03-31 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-31 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-11 |
Time |
13:02 |
Sent To |
|
|
Notes |
2008-03-11 13:02:47 | TO "COMM" BD#60 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2008-12-13 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-12-13 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-12-13 |
Time |
16:10 |
Sent To |
|
|
Notes |
2008-12-13 16:10:47 | NEW CLACS OK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-10-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-10-24 |
Time |
09:01 |
Rev Time |
0.40 |
Received By |
tgordon |
Date |
2008-10-24 |
Time |
09:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2008-07-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-17 |
Time |
09:18 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2008-07-17 |
Time |
09:18 |
Sent To |
|
|
Notes |
2008-07-17 09:26:05 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLEASE SHOW ON MECHANICAL PLAN THE OUTDOOR AIR | | CALCULATION AND PROVIDE OUTDOOR AIR, PER 2004 FBC/M | | 403.2. | | | | 2)A/C SYSTEM MODEL NUMBER TCY060G100A LISTED ON THE | | A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI | | DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI | | CERTIFICATE, SEE 2004 FBC 13-407.1.ABC.3.1.1 OR | | 13-607.1.ABC.3.1.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-03-20 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2008-03-20 |
Time |
17:18 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2008-03-20 |
Time |
17:18 |
Sent To |
|
|
Notes |
2008-03-20 17:17:22 | PLAN DENIED | | PAGE A4 ON PLANS SHOW ROOF TOP UNIT DETAIL, R19 | | INSULATION SEE SECTION 13.406.1ABC.1.4 FLORIDA ENERGY | | CODE . | | PAGE A 4 ON ROOR TOP UNIT DETAIL PLEASE SHOW CURB TO | | ROOF TIEDOWN AND UNIT TO CURB TIEDOWN . | | PAGE MP1 PLEASE PROVIDE RETURN AIR GRILL SIZE IN OFFICE | | 1,3 AND RECIPITION AREA. | | PLEASE PROVIDE SUPLY TRUNK LINE SIZE AND RETURN AIR | | TRUNKLINE SIZE ON THE PLANS | | PLEASE REFER TO SECTION 606 AND 606.4.1 FBC(M) 2004 | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2009-01-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-06 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-06 |
Time |
16:20 |
Sent To |
|
|
Notes |
2009-01-06 16:20:30 | | | | | | | PASSED/PROVISO: | | A REVISION FOR SHEET MP2 IS REQUIRED PRIOR TO FIRST | | INSPECTION SHOWING THE SERVICE SINKS ON THE SANITARY | | RISER DIAGRAM AND THE SANITARY PLUMBING PLAN TO REFLECT | | THE FLOOR PLAN A2 AND THE WATER PLAN AND THE WATER | | RISER DIAGRAMS SHEET MP3. SECTION 106.1.1. | | | | A REVISION FOR SHEET A2 IS REQUIRED SHOWING THE CLEAR | | FLOOR SPACE FOR THE DRINKING FOUNTAINS AS FORWARD | | APPROACH, NOT PARALLEL APPROACH AS SHOWN. SECTION | | 11-4.15.5. | | | | | | | | . | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2008-10-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-10-29 |
Time |
07:01 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-10-29 |
Time |
07:01 |
Sent To |
|
|
Notes |
2008-10-29 07:20:51 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FBC-2004 BUILDING | | | | ****FROM PREVIOUS REVIEW: | | | | ******FROM PREVIOUS REVIEWS: | | | | A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS | | REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS | | EXPIRED. | | | | 1. OK | | | | 2. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES. | | SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE | | STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE | | REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER | | RISER DIAGRAMS. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE SERVICE SINKS WERE NOT | | ADDRESSED. | | | | 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING | | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS | | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | ******RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) WAS | | NOT ADDRESSED. ALSO SHOW THE CLEAR FLOOR SPACE REQUIRED | | FOR THE DRINKING FOUNTAINS PER SECTION 11-4.15.5. | | | | 4. OK | | | | 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19, | | 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR | | THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF | | ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW | | COMPLIANCE. | | ****COMMENT NOT ADDRESSED FOR THE SHOWER. -- SEE | | COMMENT 4 FOR REQUIREMENTS FOR W/C & LAV. -- SHOW | | COMPLIANCE FOR THE FOLLOWING: | | ___FOR SHOWER | | A. 11-4.21.4 GRAB BARS | | B. 11-4.21.5 CONTROLS | | C. 11-4.21.6 SHOWER UNIT | | ******RESPONSE NOTED, BUT THE W/C SHALL BE 18" OFF THE | | WALL. MY MISTAKE ON THE SPACING FOR THE WATER CLOSET. A | | MINIMUM 36" IS REQUIRED FROM THE WALL TO THE LAV. SEE | | FIGURE 28. THERE IS A NOTE STATING "BATH TO BE HANDICAP | | ADAPTABLE". THIS IS NOT CORRECT. PER SECTION | | 11-4.1.3(11), IF BATHING ROOMS ARE PROVIDED, THEN EACH | | PUBLIC AND COMMON USE BATHROOM SHALL COMPLY WITH | | SECTION 11-4.23. PLEASE DELETE NOTE AND MAKE THE | | BATHROOM ACCESSIBLE. SHOW THE GRAB BARS FOR THE W/C. | | | | 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE. | | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE | | BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE | | SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE. | | FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT | | ALLOWED IN THE CLEAR FLOOR SPACE. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE | | REQUIRED FOR THE SINK SHALL BE SHOWN ON THE FLOOR PLAN. | | SECTION 11-4.24.5. FORWARD APPROACH REQUIRED MAXIMUM | | 19" UNDERNEATH THE SINK. | | | | 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION | | CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE | | INDICATE METHOD ON DETAIL. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE RELIEF VALVE, (P&T), | | SHALL NOT BE USED AS A MEANS OF CONTROLLING THERMAL | | EXPANSION. SECTION 504.4. PLEASE INDICATE METHOD OF | | CONTROL. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | ******NO RESPONSE, ONE SET OF VOIDED SHEETS HAS NOT | | BEEN SUBMITTED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-07-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-07-15 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-07-14 |
Time |
15:40 |
Sent To |
|
|
Notes |
2008-07-15 08:18:29 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FBC-2004 BUILDING | | | | ****FROM PREVIOUS REVIEW: | | | | A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS | | REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS | | EXPIRED. | | | | 1. OK | | | | 2. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES. | | SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE | | STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE | | REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER | | RISER DIAGRAMS. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING | | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS | | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | 4. SUBMIT DETAILS FOR ALL TOILET ROOMS SHOWING | | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11.4-22 | | WITH ALL SUBSECTIONS. THE LAV SHALL BE A MINIMUM 15" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO CENTER | | ON THE 30" WIDTH OF THE 30"X48" CLEAR FLOOR SPACE. | | ****NO RESPONSE, SHOW COMPLIANCE WITH THE FOLLOWING: | | ___FOR W/C'S | | A. 11-4.16.5 FLUSH CONTROLS (WIDE SIDE) | | ___FOR LAVS | | A. 11-4.19.4 EXPOSED PIPES & SURFACES | | B. 11-4.19.6 FAUCETS | | | | 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19, | | 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR | | THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF | | ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW | | COMPLIANCE. | | ****COMMENT NOT ADDRESSED FOR THE SHOWER. -- SEE | | COMMENT 4 FOR REQUIREMENTS FOR W/C & LAV. -- SHOW | | COMPLIANCE FOR THE FOLLOWING: | | ___FOR SHOWER | | A. 11-4.21.4 GRAB BARS | | B. 11-4.21.5 CONTROLS | | C. 11-4.21.6 SHOWER UNIT | | | | 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE. | | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE | | BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE | | SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE. | | FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT | | ALLOWED IN THE CLEAR FLOOR SPACE. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION | | CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE | | INDICATE METHOD ON DETAIL. | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-03-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-03-29 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-03-28 |
Time |
17:54 |
Sent To |
|
|
Notes |
2008-03-29 10:12:58 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FBC-2004 BUILDING | | | | A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS | | REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS | | EXPIRED. | | | | 1. SHT A4 ROOF DRAINAGE CALCULATIONS DO NOT APPEAR TO | | INCLUDE THE VERTICAL CONTRIBUTION OF THE PARAPET WALLS. | | PLEASE INDICATE THE HEIGHT OF THE PARAPET WALLS. ALSO | | SHOW THE HEIGHT OF THE ROOF AT BOTH THE HIGH END AND | | THE LOW END TO VERIFY VERTICAL CONTRIBUTION. SECTIONS | | 1101.1, 1106 & 1107.--SECONDARY DRAINAGE IS | | REQUIRED PER SECTION 1107.1. PLEASE SHOW THE LOCATION | | OF ALL SECONDARY ROOF DRAINAGE, (EMERGENCY OVERFLOW | | SCUPPERS PER SECTION 1503.4.3).--GUTTERS WITH | | DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF | | LESS THAN 6 INCHES HORIZONATL PROJECTION EXCEPT FOR | | GABLE END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. A | | COLLECTOR HEAD AT THE TOP OF THE DOWNSPOUT WILL BE | | APPROVED IN PLACE OF THE GUTTER. SECTION 1503.6. (SHOW | | THE DISCHARGE OF THE DOWNSPOUT A MINIMUM 1FT FROM | | STRUCTURE SIDEWALL). SUBMIT A DETAIL FOR THE COLLECTOR | | HEAD SHOWING LENGTH, WIDTH & HEIGHT. ALSO INDICATE THE | | SIZE OF THE DOWNSPOUTS. | | | | 2.DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES. | | SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE | | STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE | | REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER | | RISER DIAGRAMS. | | | | 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING | | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS | | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE | | WHO HAVE DIFFICULTY BENDING OR STOOPING. | | | | 4. SUBMIT DETAILS FOR ALL TOILET ROOMS SHOWING | | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11.4-22 | | WITH ALL SUBSECTIONS. THE LAV SHALL BE A MINIMUM 15" | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO CENTER | | ON THE 30" WIDTH OF THE 30"X48" CLEAR FLOOR SPACE. | | | | 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19, | | 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR | | THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF | | ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW | | COMPLIANCE. | | | | 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE. | | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE | | BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE | | SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE. | | FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT | | ALLOWED IN THE CLEAR FLOOR SPACE. | | | | 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION | | CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE | | INDICATE METHOD ON DETAIL. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2008-11-26 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2008-11-26 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2008-11-26 |
Time |
13:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2008-10-29 |
|
|
Cont ID |
|
Sent By |
bpowell |
Date |
2008-10-29 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
bpowell |
Date |
2008-10-29 |
Time |
17:40 |
Sent To |
|
|
Notes |
2008-10-29 17:46:25 | 1. PLEASE PROVIDE TWO (2) COPIES OF THE APPROVED | | LANDSCAPE AND PLANTING PLANS WITHIN THE APPLICATION | | PACKET. | | 2. PLEASE UPDATE, AND CORRECT THE PARKING DETAIL. | | PURSUANT TO SECTION 94-485(G) ALL PARKING SPACES SHALL | | BE DOUBLE STRIPED. | | | | IF YOU HAVE ANY QUESTIONS OR COMMENTS PLEASE CONTACT; | | BOBBY POWELL JR. (561) 822-1401, [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2008-06-24 |
|
|
Cont ID |
|
Sent By |
bpowell |
Date |
2008-06-24 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
bpowell |
Date |
2008-06-24 |
Time |
16:12 |
Sent To |
|
|
Notes |
2008-06-24 16:19:32 | 1. THE DATA TABLE INDICATING THE SQUARE FOOTAGES ON THE | | SITE PLAN DOES NOT MATCHES WHAT IS SHOWN ON DRAWING | | SITE PLANS. FOR EXAMPLE PROPOSED GARAGE =738 SF, THE | | DRAWING INDICATES 750 SF. | | | | 2. WHEN THE SITE PLAN AND LANDSCAPE PLAN ARE | | RESUBMITTED BE SURE THAT THE SQUARE FOOTAGE MATCH ON | | ALL PLANS THAT ARE SUBMITTED FOR THE PERMIT.ALSO, BE | | SURE THESE PLANS ARE CONSISTENT WITH ALL OTHER PLANS. | | | | FOR QUESTIONS OR COMMENTS, PLEASE CONTACT: BOBBY POWELL | | JR., PLANNER, AT (561) 822-1401, [email protected]. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
N |
Date |
2008-06-18 |
|
|
Cont ID |
|
Sent By |
bpowell |
Date |
2008-06-18 |
Time |
17:11 |
Rev Time |
0.00 |
Received By |
bpowell |
Date |
2008-06-18 |
Time |
17:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-03-05 |
|
|
Cont ID |
|
Sent By |
bpowell |
Date |
2008-03-05 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
bpowell |
Date |
2008-03-05 |
Time |
16:55 |
Sent To |
|
|
Notes |
2008-03-05 17:00:17 | 1. PLEASE INCLUDE TWO (2) COPIES OF A SIGNED AND SEALED | | SURVEY ALONG WITH THE PERMIT APPLICATION. | | | | 2. AT LEAST TWO (2) COPIES OF A SITE PLAN SHALL BE | | SUBMITTED WITH THE PERMIT APPLICATION. | | | | 3. AT LEAST TWO (2) COPIES OF A LANDSCAPE PLAN SHALL BE | | SUBMITTED. | | | | 4. THE STRIPPING DETAIL NEEDS TO INDICATE THAT PARKING | | WILL BE DOUBLE STRIPPED WITH 4 INCH WHITE LINES AND AT | | LEAST 12 INCHES IN BETWEEN THE STRIPPING FOR STANDARD | | SPACES. | | | | 5. DISABLED SPACES SHALL MEET THE ADA REQUIREMENTS AS | | SHOWN IN THE ATTACHED DRAWING. | | | | 6. WHEN THE SITE PLAN AND LANDSCAPE PLAN ARE SUBMITTED | | BE SURE THAT THE SQUARE FOOTAGES MATCH ON ALL PLANS | | THAT ARE SUBMITTED FOR THE PERMIT.THE FLOOR PLAN THAT | | WAS APPROVED DURING SITE PLAN REVIEW SLIGHTLY DIFFERS | | FROM WHAT IS SHOWN FOR THIS PERMIT. | | | | FOR ANY QUESTIONS OR COMMENTS PLEASE CONTACT BOBBY | | POWELL JR., PLANNER, (561) 822-1401, [email protected] | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |