Plan Review Details - Permit 08020693
Plan Review Stops For Permit 08020693
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-12-24 Cont ID  
Sent By shill Date 2008-12-24 Time 16:14 Rev Time 0.00
Received By shill Date 2008-12-24 Time 16:14 Sent To  
Notes
2008-12-24 16:15:56PROVISO
  
 1. SUBMIT AB DESIGN SITE PLAN (2ND SET) FOR RESTAMP
  
 2. SEPARATE PERMIT ACCORDIONS & ROOF (ROOF NOA
 07-1203.02)
  
 3. SUBMIT SOILS INVESTIGATION REPORT
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-12-22 Cont ID  
Sent By shill Date 2008-12-22 Time 09:36 Rev Time 0.00
Received By shill Date 2008-12-22 Time 09:20 Sent To  
Notes
2008-12-22 09:45:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-5.) ADDRESSED.
  
 6.) PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. TWO
 ORIGINALS REQUIRED.
  
 2ND REVIEW, SEE THE SOILS REPORT AND FAC61G15-23.002,
 ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED ON
 A SIGNATURE PAGE OR COVER LETTER BY EACH PROFESSIONAL
 ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF
 THE REPORT, AND IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS.
 THE SIGNATURES ARE TO BE ORIGINALS, NOT PHOTOCOPIES.
  
 3RD REVIEW, CERTIFICATE OF AUTHORIZATION NOT INCLUDED
 ON THE REPORT AND SIGNATURE IS A PHOTOCOPY,
 FAC61G15-23.002.
  
 4TH REVIEW, SAME PAPERWORK SUBMITTED. CERTIFICATE OF
 AUTHORIZATION IS TO BE INCLUDED ON THE SOILS REPORT,
 ORIGINAL SIGNATURE REQUIRED FAC61G15-23.002.
  
 7.) ADDRESSED.
  
 8.) PARKING STRIPING IS TO COMPLY WITH CITY OF WEST
 PALM BEACH STANDARD, SEE ATTACHED DETAIL. REVISE C1.
  
 ENGINEER?S RESPONSE IS THAT THE CONTRACTOR WILL
 ADDRESS. AN ACCESSIBLE ROUTE IS REQUIRED, AS WELL AS
 ACCESSIBLE PARKING. THEREFORE, IT APPEARS THAT THE SITE
 PLAN PREPARED BY AB DESIGN IS REQUIRED FOR CODE
 COMPLIANCE.
  
 SHEET 1, THE PARKING DETAIL DOES NOT MATCH THE SITE
 PLAN ON THE SAME PAGE. THE SITE PLAN SHOWS A WHEEL
 STOP, PARKING DETAIL SHOWS A VEHICLE OVERHANG.
 COMPLIANCE NOT CLEAR, SEE FBC11-4.6.3, OVERHANG SHALL
 NOT REDUCE THE CLEAR WIDTH OF ACCESSIBLE ROUTE.
  
 SEE ALSO COMMENT 23 FROM FIRST LIST; SHOW THE WIDTH OF
 THE SIDEWALK (ROUTE FROM THE ACCESSIBLE PARKING TO THE
 FRONT ENTRY), FBC11-4.6.2(1).
  
 3RD REVIEW, SIDEWALK WIDTH NOT INDICATED
 FBC11-4.6.2(1). STRIPING DETAIL NOT IN COMPLIANCE WITH
 CITY STANDARDS.
  
 4TH REVIEW, IT IS UNCLEAR WHAT YOU ARE USING FOR A SITE
 PLAN. SAME PLANS SUBMITTED, SOME PHOTOCOPY PLANS WERE
 SUBMITTED (DOCUMENTS PREPARED BY AN ENGINEER TO BE
 SIGNED,SEALED, DATED ORIGINALS FS471), COMMENTS NOT
 ADDRESSED. PLEASE VOID OUT SHEETS SUBMITTED AS
 REFERENCE AND PROVIDE PLANS WHICH SHOW COMPLIANCE WITH
 THE ACCESSIBILITY REQUIREMENTS.
  
 9-22.) ADDRESSED.
  
 23.) FROM FIRST LIST; COMMENT NOT ADDRESSED. SHOW THE
 SIDEWALK WIDTH ON THE PLAN, SIDEWALK BETWEEN ACCESSIBLE
 PARKING AND THE BUILDING. C1 SHOWS A 44INCH SIDEWALK,
 WITH A NOTE "SIDEWALK AS SHOWN ON PLAN" BUT THE
 ENGINEER'S PLAN DOESN'T SHOW ANY SIDEWALKS. THE
 LANDSCAPE ARCHITECT'S PLAN DOES NOT DIMENSION THE
 SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE ROUTE, AND THERE
 IS A CONFLICT BETWEEN THE PARKING DETAIL AND THE
 PARKING SHOWN ON THE SITE PLAN, BOTH ON AB DESIGN PAGE
 1. THE PARKING DETAIL SHOWS A VEHICLE OVERHANG, PLAN
 SHOWS A WHEEL STOP. SEE FBC11-4.6.3, VEHICLE OVERHANGS
 CANNOT REDUCE THE CLEAR WIDTH. DESIGN INTENT IS NOT
 CLEAR.
  
 2ND REVIEW, ENGINEER REMOVED SIDEWALK FROM PLAN,
 RESPONSE LETTER STATES THIS WILL BE ADDRESSED BY
 CONTRACTOR. PLEASE REVISE SITE PLAN TO SHOW CODE
 COMPLIANCE.
  
 3RD REVIEW, CIVIL SHEETS SUBMITTED AND OTHER SITE PLANS
 PREVIOUSLY SUBMITTED REMOVED. THE NEW SHEETS DO NOT
 SHOW THE SIDEWALK WIDTH, FBC11-4.6.2(1), SEE ALSO
 COMMENT 8.
  
 4TH REVIEW, SEE ITEM 8.
  
 24-39.) ADDRESSED.
  
 40.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED.
 PLEASE SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT
 GLASS AND FRONT DOOR. PRODUCT APPROVALS ARE TO BE
 REVIEWED BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FBC*106.
  
 4TH REVIEW, PLANS WERE SUBMITTED WITH A RESPONSE
 STATING THAT THE GLAZING WILL BE NON IMPACT WITH
 ACCORDIONS. THE DOOR IS AN OUTSWING DOOR SO CANNOT BE
 OPERATED FROM THE INSIDE, SEE FBC1003.6, FBC1008.1.3.5.
 PLEASE ADVISE AS TO WHERE IN THE CODE BLOCKING A
 REQUIRED EXIT IS PERMISSIBLE.
  
 41.) FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND
 SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3. THIS CAN
 BE DONE AT THE TIME OF ROOF PERMIT APPLICATION.
  
 THE PRODUCT APPROVAL FOR THE ROOF HAS BEEN REMOVED FROM
 THE PACKAGE. THIS IS REQUIRED, REVIEWED BY DESIGNER OF
 RECORD. OTHER INFORMATION (ASSEMBLY, ENHANCED
 FASTENING) CAN BE SUBMITTED WITH THE ROOF PERMIT.
  
 4TH REVIEW, ALL PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD FBC*106.
  
 42.) SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ.
 PLEASE PROVIDE LEGIBLE COPIES. THEY MAY BE AVAILABLE AT
 WWW.BUILDINGCODEONLINE.COM.
  
 PLEASE SEE THE ROLLUP DOOR PRODUCT APPROVAL. IT IS
 ILLEGIBLE AND I CANNOT FIND/READ DESIGN PRESSURES.
 PLEASE MARK ON THE FLORIDA STATE PRODUCT APPROVAL WHICH
 PRODUCT YOU ARE USING AND SUBMIT COMPLETE, LEGIBLE
 DOCUMENTS FOR THAT PRODUCT. THIS IS AVAILABLE AT
 WWW.FLORIDABUILDING.ORG
  
 3RD REVIEW, THE GARAGE DOOR PRODUCT APPROVAL HAS A
 DESIGN PRESSURE LIMITATION OF +-30PSF. +33.7/-36.7
 REQUIRED, SEE PAGE A3.
  
 4TH REVIEW, DESIGNER OF RECORD TO REVIEW ALL PRODUCT
 APPROVALS FBC*106. THE GARAGE DOOR PRODUCT APPROVAL
 SUBMITTED DOES NOT MEET THE DESIGN PRESSURE
 REQUIREMENTS. PLEASE ADDRESS.
  
 43.) ADDRESSED.
  
 44-45.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED.
  
 4TH REVIEW, THE RESPONSE LETTER STATES THAT ACCORDIONS
 WILL BE USED. A SEPARATE PERMIT WILL BE REQUIRED. THE
 EXIT DOORS ARE TO BE IMPACT, FBC1003.6, FBC1008.1.3.5.
  
 46-51.) ADDRESSED.
  
 NEW COMMENT:
  
 THE CONTRACTOR MAY CONTACT ME TO DISCUSS HOW THESE
 ITEMS COULD BE RESOLVED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 08:18 Rev Time 0.00
Received By shill Date 2008-11-18 Time 11:28 Sent To  
Notes
2008-11-19 08:54:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-5.) ADDRESSED.
  
 6.) PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. TWO
 ORIGINALS REQUIRED.
  
 2ND REVIEW, SEE THE SOILS REPORT AND FAC61G15-23.002,
 ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED ON
 A SIGNATURE PAGE OR COVER LETTER BY EACH PROFESSIONAL
 ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF
 THE REPORT, AND IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS.
 THE SIGNATURES ARE TO BE ORIGINALS, NOT PHOTOCOPIES.
  
 3RD REVIEW, CERTIFICATE OF AUTHORIZATION NOT INCLUDED
 ON THE REPORT AND SIGNATURE IS A PHOTOCOPY,
 FAC61G15-23.002.
  
 7.) ADDRESSED.
  
 8.) PARKING STRIPING IS TO COMPLY WITH CITY OF WEST
 PALM BEACH STANDARD, SEE ATTACHED DETAIL. REVISE C1.
  
 ENGINEER?S RESPONSE IS THAT THE CONTRACTOR WILL
 ADDRESS. AN ACCESSIBLE ROUTE IS REQUIRED, AS WELL AS
 ACCESSIBLE PARKING. THEREFORE, IT APPEARS THAT THE SITE
 PLAN PREPARED BY AB DESIGN IS REQUIRED FOR CODE
 COMPLIANCE.
  
 SHEET 1, THE PARKING DETAIL DOES NOT MATCH THE SITE
 PLAN ON THE SAME PAGE. THE SITE PLAN SHOWS A WHEEL
 STOP, PARKING DETAIL SHOWS A VEHICLE OVERHANG.
 COMPLIANCE NOT CLEAR, SEE FBC11-4.6.3, OVERHANG SHALL
 NOT REDUCE THE CLEAR WIDTH OF ACCESSIBLE ROUTE.
  
 SEE ALSO COMMENT 23 FROM FIRST LIST; SHOW THE WIDTH OF
 THE SIDEWALK (ROUTE FROM THE ACCESSIBLE PARKING TO THE
 FRONT ENTRY), FBC11-4.6.2(1).
  
 3RD REVIEW, SIDEWALK WIDTH NOT INDICATED
 FBC11-4.6.2(1). STRIPING DETAIL NOT IN COMPLIANCE WITH
 CITY STANDARDS.
  
 9-22.) ADDRESSED.
  
 23.) FROM FIRST LIST; COMMENT NOT ADDRESSED. SHOW THE
 SIDEWALK WIDTH ON THE PLAN, SIDEWALK BETWEEN ACCESSIBLE
 PARKING AND THE BUILDING. C1 SHOWS A 44INCH SIDEWALK,
 WITH A NOTE "SIDEWALK AS SHOWN ON PLAN" BUT THE
 ENGINEER'S PLAN DOESN'T SHOW ANY SIDEWALKS. THE
 LANDSCAPE ARCHITECT'S PLAN DOES NOT DIMENSION THE
 SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE ROUTE, AND THERE
 IS A CONFLICT BETWEEN THE PARKING DETAIL AND THE
 PARKING SHOWN ON THE SITE PLAN, BOTH ON AB DESIGN PAGE
 1. THE PARKING DETAIL SHOWS A VEHICLE OVERHANG, PLAN
 SHOWS A WHEEL STOP. SEE FBC11-4.6.3, VEHICLE OVERHANGS
 CANNOT REDUCE THE CLEAR WIDTH. DESIGN INTENT IS NOT
 CLEAR.
  
 2ND REVIEW, ENGINEER REMOVED SIDEWALK FROM PLAN,
 RESPONSE LETTER STATES THIS WILL BE ADDRESSED BY
 CONTRACTOR. PLEASE REVISE SITE PLAN TO SHOW CODE
 COMPLIANCE.
  
 3RD REVIEW, CIVIL SHEETS SUBMITTED AND OTHER SITE PLANS
 PREVIOUSLY SUBMITTED REMOVED. THE NEW SHEETS DO NOT
 SHOW THE SIDEWALK WIDTH, FBC11-4.6.2(1), SEE ALSO
 COMMENT 8.
  
 24-29.) ADDRESSED.
  
 30.) THE PREVIOUS LISTS STATED THAT THE SHOWER BATHROOM
 MUST BE ACCESSIBLE, NOT ADAPTABLE. THE PLANS HAVE BEEN
 REVISED TO MAKE THIS ROOM ACCESSIBLE, BUT THE NOTE
 STATING THIS IS ADAPTABLE IS STILL ON THE PLAN. PLEASE
 REVISE TO REMOVE THIS NOTE.
  
 31.) PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB
 BARS, MIRRORS, FBC 11.
  
 2ND REVIEW, SEE PLUMBING COMMENTS.
  
 3RD REVIEW, THE W/C IS SHOWN AS 1'4" FROM WALL, 18"
 REQUIRED, FBC11-4.16.2. PLEASE REVISE.
  
 32-39.) ADDRESSED.
  
 40.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED.
 PLEASE SUBMIT PRODUCT APPROVALS FOR THE STOREFRONT
 GLASS AND FRONT DOOR. PRODUCT APPROVALS ARE TO BE
 REVIEWED BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FBC*106.
  
 41.) FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND
 SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3. THIS CAN
 BE DONE AT THE TIME OF ROOF PERMIT APPLICATION.
  
 THE PRODUCT APPROVAL FOR THE ROOF HAS BEEN REMOVED FROM
 THE PACKAGE. THIS IS REQUIRED, REVIEWED BY DESIGNER OF
 RECORD. OTHER INFORMATION (ASSEMBLY, ENHANCED
 FASTENING) CAN BE SUBMITTED WITH THE ROOF PERMIT.
  
 42.) SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ.
 PLEASE PROVIDE LEGIBLE COPIES. THEY MAY BE AVAILABLE AT
 WWW.BUILDINGCODEONLINE.COM.
  
 PLEASE SEE THE ROLLUP DOOR PRODUCT APPROVAL. IT IS
 ILLEGIBLE AND I CANNOT FIND/READ DESIGN PRESSURES.
 PLEASE MARK ON THE FLORIDA STATE PRODUCT APPROVAL WHICH
 PRODUCT YOU ARE USING AND SUBMIT COMPLETE, LEGIBLE
 DOCUMENTS FOR THAT PRODUCT. THIS IS AVAILABLE AT
 WWW.FLORIDABUILDING.ORG
  
 3RD REVIEW, THE GARAGE DOOR PRODUCT APPROVAL HAS A
 DESIGN PRESSURE LIMITATION OF +-30PSF. +33.7/-36.7
 REQUIRED, SEE PAGE A3.
  
 43.) ADDRESSED.
  
 44-45.) AS DISCUSSED, ALL GLAZING WILL BE IMPACT RATED.
  
 46-51.) ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-01 Cont ID  
Sent By shill Date 2008-08-01 Time 09:01 Rev Time 0.00
Received By shill Date 2008-08-01 Time 09:01 Sent To  
Notes
2008-08-01 09:02:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)WHEN RESUBMITTING, ALL CHANGES TO THE PLAN ARE TO
 BE CLOUDED AND INDICATED WITH REVISION MARKERS, REMOVE
 AND REPLACE REVISED SHEETS AS NECESSARY.INCLUDE A
 RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED.
  
 2.)ADDRESSED.
  
 3.)PLEASE PROVIDE A BREAKDOWN OF COST FOR THE
 RENOVATION AREA AND NEW AREAS.
  
 2ND REVIEW, PLEASE PROVIDE A REASONABLE VALUE FOR THIS
 JOB OR AN ESTIMATE WILL BE DONE USING MARSHALL & SWIFT
 OR MEANS.
  
 4.)ALL CODE REFERENCES WERE REVISED TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS WITH THE EXCEPTION OF C1,
 PROPOSED, STILL REFERS TO 06 REVISIONS.
  
 5.)PROVIDE A SURVEY FOR THIS PARCEL.THE SITE PLANS
 PROVIDED ARE NOT CONSISTENT.
  
 2ND REVIEW, SEE SITE PLAN PREPARED BY AB DESIGN.THE
 EXISTING WAREHOUSE DOES NOT MATCH THE SURVEY OR C1.
 ONLY ONE SET OF THE SITE PLAN PREPARED BY AB DESIGN WAS
 SUBMITTED.TWO SETS NEEDED FOR PERMIT ISSUANCE.ONE
 SET HAS BEEN RETAINED.THEREFORE, IF THESE SHEETS ARE
 REQUIRED, SUBMIT TWO NEW ORIGINAL SETS.
  
 6.)PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2.
 TWO ORIGINALS REQUIRED.
  
 2ND REVIEW, SEE THE SOILS REPORT AND FAC61G15-23.002,
 ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED ON
 A SIGNATURE PAGE OR COVER LETTER BY EACH PROFESSIONAL
 ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF
 THE REPORT, AND IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS.
 THE SIGNATURES ARE TO BE ORIGINALS, NOT PHOTOCOPIES.
  
 7.)ADDRESSED.
  
 8.)PARKING STRIPING IS TO COMPLY WITH CITY OF WEST
 PALM BEACH STANDARD, SEE ATTACHED DETAIL.REVISE C1.
  
 ENGINEER?S RESPONSE IS THAT THE CONTRACTOR WILL
 ADDRESS.AN ACCESSIBLE ROUTE IS REQUIRED, AS WELL AS
 ACCESSIBLE PARKING.THEREFORE, IT APPEARS THAT THE
 SITE PLAN PREPARED BY AB DESIGN IS REQUIRED FOR CODE
 COMPLIANCE.
  
 SHEET 1, THE PARKING DETAIL DOES NOT MATCH THE SITE
 PLAN ON THE SAME PAGE.THE SITE PLAN SHOWS A WHEEL
 STOP, PARKING DETAIL SHOWS A VEHICLE OVERHANG.
 COMPLIANCE NOT CLEAR, SEE FBC11-4.6.3, OVERHANG SHALL
 NOT REDUCE THE CLEAR WIDTH OF ACCESSIBLE ROUTE.
  
 SEE ALSO COMMENT 23 FROM FIRST LIST; SHOW THE WIDTH OF
 THE SIDEWALK (ROUTE FROM THE ACCESSIBLE PARKING TO THE
 FRONT ENTRY), FBC11-4.6.2(1).
  
 9.)ACCESSIBLE PARKING SIGNAGE IS TO COMPLY WITH
 FBC11-4.6.4; THE SIGN IS TO ALSO INCLUDE THE PENALTY.
 REVISE C1 AND AB DESIGN SHEET 1 OF 3.
  
 2ND REVIEW, NOT ADDRESSED.SHEET 1 WAS NOT REVISED,
 AND ENGINEER?S RESPONSE IS THAT CONTRACTOR IS TO
 ADDRESS ACCESSIBLE PARKING.
  
 SHOW ACCESSIBLE PARKING SIGN LOCATION.
  
 10-14.) ADDRESSED.
  
 15.) TENANT SEPARATIONS SHOWN, BUT THE 1 HOUR REQUIRED
 DETAIL IS NOT COMPLETE.DETAIL 1 A5 WAS PROVIDED, BUT
 NOTHING ON THE FLOOR PLAN CORRELATES WITH THIS WALL
 DETAIL. PLEASE PROVIDE A DETAIL MARKER ON THE FLOOR
 PLAN TO SHOW COMPLIANCE WITH FBC703.2.
  
 PLEASE NOTE ALL REQUIRED FIRE RESISTIVE RATED
 CONSTRUCTION REQUIREMENTS ON THE PLAN.FOR INSTANCE,
 WALL BETWEEN OFFICE 1/MENS BATHROOM/BREAK ROOM/CLOSET
 AND WAREHOUSE BAY 2.ALTHOUGH BLOCK WOULD BY DESIGN BE
 A 1 HOUR WALL, UNLESS REQUIREMENTS ARE CLARIFIED, IT
 WOULD NOT BE CLEAR WHETHER FIRE DAMPERS, PENETRATION
 PROTECTION, SIGNAGE ABOVE DROPPED CEILINGS, ETC. WOULD
 BE REQUIRED.IF DESIGNING WITH OCCUPANCY SEPARATION, A
 3 HOUR IS REQUIRED, SEE OTHER COMMENTS.
  
 16-18.) ADDRESSED.
  
 19.)SEE FBC TABLES 601, 602, 704.8.COMPLIANCE IS TO
 BE SHOWN ON THE PLAN.
  
 2ND REVIEW, NORTH WALL IS SHOWN AS >30FEET.THE
 SERVICE ROAD IS 40FEET; DIMENSION SHOULD BE FROM THE
 EXTERIOR WALL TO CENTERLINE OF THE ROAD, 26FEET. PLEASE
 REVISE AND CHECK ALL.
  
 20.) ADDRESSED.
  
 21.)AB DESIGN LLC HAS AN APPLICATION PENDING FOR THE
 BUSINESS LICENSE.UNTIL THIS IS ISSUED, THIS COMPANY
 NAME CANNOT BE USED ON PLANS.
  
 A SET HAS BEEN RETAINED.PLEASE SEE OTHER COMMENTS,
 REVISE TO ADDRESS COMMENTS, AND SUBMIT TWO NEW ORIGINAL
 SIGNED, SEALED, DATED SETS.AB DESIGN, LLC IS TO BE
 REMOVED FROM THE TITLE BLOCK UNLESS A CERTIFICATE OF
 AUTHORIZATION HAS BEEN OBTAINED.
  
 22.)SHOW ALL REQUIRED DETECTABLE WARNINGS,
 FBC11-4.29.
  
 23.)FROM FIRST LIST; COMMENT NOT ADDRESSED.SHOW THE
 SIDEWALK WIDTH ON THE PLAN, SIDEWALK BETWEEN ACCESSIBLE
 PARKING AND THE BUILDING.C1 SHOWS A 44INCH SIDEWALK,
 WITH A NOTE "SIDEWALK AS SHOWN ON PLAN" BUT THE
 ENGINEER'S PLAN DOESN'T SHOW ANY SIDEWALKS.THE
 LANDSCAPE ARCHITECT'S PLAN DOES NOT DIMENSION THE
 SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE ROUTE, AND THERE
 IS A CONFLICT BETWEEN THE PARKING DETAIL AND THE
 PARKING SHOWN ON THE SITE PLAN, BOTH ON AB DESIGN PAGE
 1.THE PARKING DETAIL SHOWS A VEHICLE OVERHANG, PLAN
 SHOWS A WHEEL STOP.SEE FBC11-4.6.3, VEHICLE OVERHANGS
 CANNOT REDUCE THE CLEAR WIDTH. DESIGN INTENT IS NOT
 CLEAR.
  
 2ND REVIEW, ENGINEER REMOVED SIDEWALK FROM PLAN,
 RESPONSE LETTER STATES THIS WILL BE ADDRESSED BY
 CONTRACTOR.PLEASE REVISE SITE PLAN TO SHOW CODE
 COMPLIANCE.
  
 24-25.) ADDRESSED.
  
 26.)SEE FIGURE 11-7(6), TURNS AROUND AN OBSTRUCTION,
 AND DOOR 3 INTO THE GARAGE, FBC11-4.3.3.
  
 27.)LABEL EACH ROOM AS TO USE, AREAS BEHIND THE
 BIFOLD DOORS 9 AND 10.
  
 28.)SHOW THE ELEVATION ON EACH SIDE OF THE EXTERIOR
 DOORS, FBC11-4.13.8.
  
 29.)IF 9 AND 10 ARE CLOSETS, THESE AREAS ARE TO BE
 ACCESSIBLE, SEE FBC11-4.25.
  
 2ND REVIEW, PLEASE NOTE REQUIREMENT OF ACCESSIBLE DOORS
 AND HARDWARE ON THE PLAN.
  
 30.)THE SHOWER IS TO COMPLY WITH FBC 11-4.23,
 FBC11-4.1.2(6).PROVIDE A DETAIL AND SHOW TURNING
 RADIUS.
  
 RESPONSE LETTER STATES THAT THE SHOWER IS ADAPTABLE AS
 NOTED ON THE PLAN.THIS BATHROOM MUST BE FULLY
 ACCESSIBLE FBC11-4.2(6); ADAPTABLE APPLIES ONLY TO
 PRIVATE TOILET ROOM (SUCH AS PRIVATE BATHROOM IN AN
 OFFICE), FBC11-4.1.3(11).PROVIDE A DETAIL FOR THE
 SHOWER FBC11-4.21.
  
 31.)PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB
 BARS, MIRRORS, FBC 11.
  
 SEE PLUMBING COMMENTS.
  
 32.)ADDRESSED.
  
 33.)PROVIDE A DETAIL FOR THE BREAK ROOM SINK SHOWING
 COMPLIANCE WITH ALL REQUIREMENTS OF FBC11-4.24.
  
 I WAS UNABLE TO LOCATE A DETAIL.ALSO PLEASE NOTE THAT
 THERE IS NOT ENOUGH SPACE FOR TURNING RADIUS
 FBC11-4.2.3.
  
 34-36.) ADDRESSED.
  
 37.)BUILDING INFORMATION, C1, ITEM 8 NEW ADDITION
 STATES NON RATED, TABLE 302.3.2.THIS CODE SECTION IS
 FOR SEPARATED USE WHICH WOULD REQUIRE A FIRE RATED
 SEPARATION.SEE FBC 302.3.1, CORRELATE INFORMATION AND
 REVISE PLAN AS NECESSARY.
  
 NOT ADDRESSED; IF YOU ARE DESIGNING TO FBC 302.3.2 AS
 INDICATED ON PROPOSED, OCCUPANCY SEPARATION, 3 HOUR
 REQUIRED BETWEEN S1 AND B, FBC TABLE 302.3.2.NO
 OCCUPANCY SEPARATION IS REQUIRED IF DESIGNING USING NON
 SEPARATED USE FBC30.3.1 AND THE BUILDING COMPLIES WITH
 THE MOST STRINGENT OCCUPANCY REQUIREMENT OF FBC TABLE
 501.A TENANT SEPARATION OF 1 HOUR WOULD STILL BE
 REQUIRED, SEE OTHER COMMENTS.PLEASE CONTACT ME IF YOU
 WOULD LIKE FURTHER CLARIFICATION.
  
 38-39.) ADDRESSED.
  
 40.)A NON IMPACT GLASS DOOR PRODUCT APPROVAL WAS
 SUBMITTED.SEE FBC10 FBC1003.6, MEANS OF EGRESS
 CONTINUITY.THE PATH OF EGRESS TRAVEL ALONG A MEANS OF
 EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT
 OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN
 CHAPTER 10.YOU CANNOT BLOCK EXIT DOORS WITH A
 HURRICANE PANELS.
  
 2ND REVIEW, ENGINEER HAS SPECIFIED AN IMPACT GLASS DOOR
 BUT THE PRODUCT APPROVAL FOR IMPACT RATED GLASS DOOR
 WAS NOT SUBMITTED. THE NON IMPACT GLASS DOORS CAN BE
 USED WITH ACCORDION SHUTTERS FBC1008.1.3.6.AN
 ACCORDION PRODUCT APPROVAL WAS SUBMITTED, BUT THE
 INSTALLATION SCHEDULE WAS NOT COMPLETED SO IT CANNOT BE
 DETERMINED WHERE THE ACCORDIONS ARE PROPOSED.
  
 41.)FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND
 SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3.THIS CAN
 BE DONE AT THE TIME OF ROOF PERMIT APPLICATION.
  
 THE PRODUCT APPROVAL FOR THE ROOF HAS BEEN REMOVED FROM
 THE PACKAGE.THIS IS REQUIRED, REVIEWED BY DESIGNER OF
 RECORD.OTHER INFORMATION (ASSEMBLY, ENHANCED
 FASTENING) CAN BE SUBMITTED WITH THE ROOF PERMIT.
  
 42.)SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ.
 PLEASE PROVIDE LEGIBLE COPIES.THEY MAY BE AVAILABLE
 AT WWW.BUILDINGCODEONLINE.COM.
  
 PLEASE SEE THE ROLLUP DOOR PRODUCT APPROVAL.IT IS
 ILLEGIBLE AND I CANNOT FIND/READ DESIGN PRESSURES.
 PLEASE MARK ON THE FLORIDA STATE PRODUCT APPROVAL WHICH
 PRODUCT YOU ARE USING AND SUBMIT COMPLETE, LEGIBLE
 DOCUMENTS FOR THAT PRODUCT.THIS IS AVAILABLE AT
 WWW.FLORIDABUILDING.ORG
  
 43.)ADDRESSED.
  
 44.)SEE ATTACHED INSTALLATION SCHEDULE AND COMPLETE
 THIS FORM (REQUIRED FOR HURRICANE SHUTTERS).
  
 2ND REVIEW, RETURNED BLANK.UPON REQUEST, THIS
 INFORMATION CAN BE PROVIDED WITH A SEPARATE PERMIT FOR
 SHUTTERS.HOWEVER, THE PLAN IS REQUIRED TO ADDRESS
 ITEM 40.EITHER SUBMIT AN IMPACT RATED PRODUCT
 APPROVAL FOR THIS DOOR, OR NOTE ON THE PLAN THAT IT
 WILL BE IMPACT WITH AN ACCORDION SHUTTER (CANNOT USE
 PANELS FOR THIS OPENING).
  
 SEE OTHER COMMENTS.THIS CAN, UPON REQUEST, BE
 PROVIDED WITH AN APPLICATION FOR SHUTTERS ON A SEPARATE
 PERMIT IF OTHER ISSUES ARE ADDRESSED ? PRESTORM
 PREPARATION PLAN (ITEM 45) AND EXITING ISSUE (ITEM
 40).
  
 45.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL
 PROPERTIES REQUIRES APPROVAL FROM THE BUILDING
 OFFICIAL.IF YOU ARE PROPOSING TO USE REMOVABLE
 SHUTTERS, SUBMIT A PRE STORM PREPARATION PLAN, SEE
 ATTACHED POLICY, ITEM 13.PROVIDE PRODUCT APPROVALS
 AND COMPLETE AN INSTALLATION SCHEDULE.
  
 THE INSTALLATION PLAN MAY BE SENT VIA EMAIL PRIOR TO
 RESUBMITTAL OF THE PLANS.CONTRACTOR IS ENCOURAGED TO
 GET THIS ISSUE RESOLVED PRIOR TO RESUBMITTAL TO AVOID
 DELAYS IN PERMITTING.
  
 2ND REVIEW, NOT ADDRESSED.THIS IS REQUIRED FOR
 REMOVABLE PANELS BUT NOT FOR ACCORDIONS.BOTH PRODUCT
 APPROVALS WERE SUBMITTED.PLEASE CLARIFY DESIGN
 INTENT.
  
 46-47.) ADDRESSED.
  
 NEW COMMENTS:
  
 48.) SEE ENERGY CALCS SUBMITTED, SQUARE FOOT AREA IS TO
 MATCH THE PLAN; CONDITIONED AND UNCONDITIONED AREA IS
 TO BE INCLUDED. FBC13-101.
  
 49.)WALL SECTIONS TO BE NOTED ON THE FLOOR PLAN.AN
 INSULATED WALL IS REQUIRED BETWEEN THE GARAGE AND
 CONDITIONED SPACE.
  
 50.)ALL REQUIRED FIRE RESISTANCE IS TO BE SHOWN ON
 THE PLAN AS PENETRATIONS WILL BE REQUIRED TO BE
 PROTECTED.FOR INSTANCE, THE WALL BETWEEN BAY 2 AND
 THE GARAGE IS TO HAVE A 1 HOUR FIRE RESISTIVE RATING,
 FBC708.1(5).IF USING AN EXCEPTION, NOTE ON THE PLAN
 AND SHOW FIRE AREA.
  
 51.)PLEASE NOTE THAT SOME COMMENTS WOULD HAVE BEEN
 REDLINE OR PROVISO ITEMS; HOWEVER, AS PLANS NEED TO BE
 CHANGED DUE TO COMMENTS FROM OTHER REVIEWERS, PLEASE
 REVISE AT THIS TIME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-21 Cont ID  
Sent By shill Date 2008-03-21 Time 18:50 Rev Time 0.00
Received By shill Date 2008-03-21 Time 18:50 Sent To  
Notes
2008-03-21 18:52:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)WHEN RESUBMITTING, ALL CHANGES TO THE PLAN ARE TO
 BE CLOUDED AND INDICATED WITH REVISION MARKERS, REMOVE
 AND REPLACE REVISED SHEETS AS NECESSARY.INCLUDE A
 RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE
 STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 3.)PLEASE PROVIDE A BREAKDOWN OF COST FOR THE
 RENOVATION AREA AND NEW AREAS.
  
 4.)GOVERNING CODE SHOULD INCLUDE 2007
 REVISIONS/SUPPLEMENTS, FS553.ALSO SEE MP4, REFERS TO
 COUNTY AMENDMENTS TO THE STANDARD BUILDING CODE.OTHER
 CODE REFERENCES ON THIS PAGE ARE INCORRECT OR OUTDATED.
 CHECK ALL.
  
 5.)PROVIDE A SURVEY FOR THIS PARCEL.THE SITE PLANS
 PROVIDED ARE NOT CONSISTENT.
  
 6.)PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2.
 TWO ORIGINALS REQUIRED.
  
 7.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 8.)PARKING STRIPING IS TO COMPLY WITH CITY OF WEST
 PALM BEACH STANDARD, SEE ATTACHED DETAIL.REVISE C1.
  
 9.)ACCESSIBLE PARKING SIGNAGE IS TO COMPLY WITH
 FBC11-4.6.4; THE SIGN IS TO ALSO INCLUDE THE PENALTY.
 REVISE C1 AND AB DESIGN SHEET 1 OF 3.
  
 10.)BUILDING INFORMATION IS TO STATE WHETHER THE
 BUILDING IS SPRINKLERED OR UN SPRINKLERED.
  
 11.)BUILDING INFORMATION STATES THAT THE EXISTING
 BUILDING IS F1, NEW USE IS SHOWN AS WAREHOUSE WHICH
 WOULD BE STORAGE OCCUPANCY,FBC 311.NOTE CHANGE OF
 OCCUPANCY ON THE PLAN; THIS JOB WILL BE REQUIRED TO
 COMPLY WITH FBC EB CHAPTER 8.
  
 12.)OCCUPANCY CALCULATIONS SHEET C1 STATE THAT THIS
 IS M, OTHER PLACES DECLARE THIS AS B BUT ALSO STATE
 THAT THIS IS STORAGE, GARAGE, AND WAREHOUSE.SEE FBC
 302.1, PORTIONS OF BUILDINGS TO BE CLASSIFIED WITH
 RESPECT TO OCCUPANCY.DECLARE OCCUPANCY CLASSIFICATION
 AND SUB CLASSIFICATION FOR EACH AREA AS WELL AS SQUARE
 FOOT AREA FOR EACH OCCUPANCY.
  
 13.)FOR THE STORAGE OCCUPANCIES (WAREHOUSE, STORAGE,
 GARAGE), DECLARE S1 AND S2 WITH SQUARE FOOT AREAS FOR
 EACH, SEE FBC311.2, FBC406.
  
 14.)DECLARE OCCUPANT LOAD FOR EACH AREA, FBC1004.
  
 15.)IS THIS BUILDING FOR ONE TENANT OR MULTIPLE
 TENANTS?NOTE THIS INFORMATION ON THE PLAN AND SHOW
 TENANT SEPARATION IF REQUIRED.NO SEPARATION SHOWN
 BETWEEN THE OFFICE, BAY 1, AND BAY 2.
  
 16.)PROPERTY APPRAISER WEBSITE AND AB DESIGN SHOWS
 THE EXISTING BUILDING AS 1710 SF, ENGINEER SHOWS THIS
 BUILDING AS 1438 ON C1.EITHER REVISE OR PROVIDE
 INFORMATION TO SHOW WHY ENGINEER?S SQUARE FOOT TOTAL
 CONFLICTS WITH PAPA AND LANDSCAPE ARCHITECT.
  
 17.)THIS BUILDING APPEARS TO BE A MIXED OCCUPANCY
 FBC302, PLEASE DECLARE AS SUCH AND DECLARE AS EITHER
 SEPARATED OR NON SEPARATED USE.
  
 18.)EXISTING BUILDING DECLARES THIS AS BUILDING TYPE
 IIB, BUT A1 SHOWS FIRE DAMAGED WOOD GIRDER, OTHER WOOD
 STRUCTURAL ELEMENTS, AND S4 SHOWS PT WOOD BUCKS.TYPE
 II IS NONCOMBUSTIBLE CONSTRUCTION; SEE ALSO FBC603.
  
 19.)SEE FBC TABLES 601, 602, 704.8.COMPLIANCE IS TO
 BE SHOWN ON THE PLAN.
  
 20.)EE-S3, F-S3, ANY OTHER APPLICABLE DETAILS,
 SPECIFY THE WELDS.
  
 21.)AB DESIGN LLC HAS AN APPLICATION PENDING FOR THE
 BUSINESS LICENSE.UNTIL THIS IS ISSUED, THIS COMPANY
 NAME CANNOT BE USED ON PLANS.
  
 22.)SHOW ALL REQUIRED DETECTABLE WARNINGS,
 FBC11-4.29.
  
 23.)SHOW THE SIDEWALK WIDTH ON THE PLAN, SIDEWALK
 BETWEEN ACCESSIBLE PARKING AND THE BUILDING.C1 SHOWS
 A 44INCH SIDEWALK, WITH A NOTE ?SIDEWALK AS SHOWN ON
 PLAN? BUT THE ENGINEER?S PLAN DOESN?T SHOW ANY
 SIDEWALKS.THE LANDSCAPE ARCHITECT?S PLAN DOES NOT
 DIMENSION THE SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE
 ROUTE, AND THERE IS A CONFLICT BETWEEN THE PARKING
 DETAIL AND THE PARKING SHOWN ON THE SITE PLAN, BOTH ON
 AB DESIGN PAGE 1.THE PARKING DETAIL SHOWS A VEHICLE
 OVERHANG, PLAN SHOWS A WHEEL STOP.SEE FBC11-4.6.3,
 VEHICLE OVERHANGS CANNOT REDUCE THE CLEAR WIDTH. DESIGN
 INTENT IS NOT CLEAR.
  
 24.)N/A
  
 25.)IS THE LANDSCAPE ARCHITECT TAKING RESPONSIBILITY
 FOR COMPLIANCE WITH FBC CHAPTER 11, FBC TABLE 601, 602,
 704.8 AS THE ENGINEER HAS NOT PROVIDED A SITE PLAN
 SHOWING THE INFORMATION REQUIRED TO DETERMINE CODE
 COMPLIANCE?ON THE SITE PLAN, DECLARE GOVERNING CODE
 FS553.
  
 26.)SEE FIGURE 11-7(6), TURNS AROUND AN OBSTRUCTION,
 AND DOOR 3 INTO THE GARAGE, FBC11-4.3.3.
  
 27.)LABEL EACH ROOM AS TO USE, AREAS BEHIND THE
 BIFOLD DOORS 9 AND 10.
  
 28.)SHOW THE ELEVATION ON EACH SIDE OF THE EXTERIOR
 DOORS, FBC11-4.13.8.
  
 29.)IF 9 AND 10 ARE CLOSETS, THESE AREAS ARE TO BE
 ACCESSIBLE, SEE FBC11-4.25.
  
 30.)THE SHOWER IS TO COMPLY WITH FBC 11-4.23,
 FBC11-4.1.2(6).PROVIDE A DETAIL AND SHOW TURNING
 RADIUS.
  
 31.)PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB
 BARS, MIRRORS, FBC 11.
  
 32.)SHOW CLEAR FLOOR SPACE FOR ALL FIXTURES AND
 CLOSETS.
  
 33.)PROVIDE A DETAIL FOR THE BREAK ROOM SINK SHOWING
 COMPLIANCE WITH ALL REQUIREMENTS OF FBC11-4.24.
  
 34.)THE BATHROOM AT DOOR 4 IS TO BE ACCESSIBLE,
 FBC11-4.1.2(6).
  
 35.)SHOW MANEUVERING CLEARANCE, PULL SIDE, FBC FIGURE
 11-25 DOORS 3, 6, 7.
  
 36.)INTERIOR FINISHES TO COMPLY WITH FBC TABLE 803.5.
 IT APPEARS TO BE COMPLIANT BUT CANNOT BE CONFIRMED
 UNTIL SPRINKLER AND OCCUPANCY INFORMATION HAS BEEN
 CONFIRMED.
  
 37.)BUILDING INFORMATION, C1, ITEM 8 NEW ADDITION
 STATES NON RATED, TABLE 302.3.2.THIS CODE SECTION IS
 FOR SEPARATED USE WHICH WOULD REQUIRE A FIRE RATED
 SEPARATION.SEE FBC 302.3.1, CORRELATE INFORMATION AND
 REVISE PLAN AS NECESSARY.
  
 38.)SPECIFY COMPONENTS AND CLADDING PRESSURES FOR THE
 ROOF.
  
 39.)PROVIDE A DETAIL FOR THE AC UNIT CURB, FBC1609.
  
 40.)A NON IMPACT GLASS DOOR PRODUCT APPROVAL WAS
 SUBMITTED.SEE FBC10 FBC1003.6, MEANS OF EGRESS
 CONTINUITY.THE PATH OF EGRESS TRAVEL ALONG A MEANS OF
 EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT
 OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN
 CHAPTER 10.YOU CANNOT BLOCK EXIT DOORS WITH A
 HURRICANE SHUTTERS.
  
 41.)FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND
 SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3.THIS CAN
 BE DONE AT THE TIME OF ROOF PERMIT APPLICATION.
  
 42.)SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ.
 PLEASE PROVIDE LEGIBLE COPIES.THEY MAY BE AVAILABLE
 AT WWW.BUILDINGCODEONLINE.COM.
  
 43.)THE EASTERN METAL PRODUCT APPROVAL IS ILLEGIBLE.
 PROVIDE LEGIBLE COPIES.
  
 44.)SEE ATTACHED INSTALLATION SCHEDULE AND COMPLETE
 THIS FORM (REQUIRED FOR HURRICANE SHUTTERS).
  
 45.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL
 PROPERTIES REQUIRES APPROVAL FROM THE BUILDING
 OFFICIAL.IF YOU ARE PROPOSING TO USE REMOVABLE
 SHUTTERS, SUBMIT A HURRICANE INSTALLATION PLAN, SEE
 ATTACHED POLICY, ITEM 13.PROVIDE PRODUCT APPROVALS
 AND COMPLETE AN INSTALLATION SCHEDULE.
  
 THE INSTALLATION PLAN MAY BE SENT VIA EMAIL PRIOR TO
 RESUBMITTAL OF THE PLANS.CONTRACTOR IS ENCOURAGED TO
 GET THIS ISSUE RESOLVED PRIOR TO RESUBMITTAL TO AVOID
 DELAYS IN PERMITTING.
  
 46.)THE PRODUCT APPROVALS FOR THE STORM PANELS ARE
 EXPIRED, FBC2001 RATHER THAN FBC2004.CURRENT
 APPROVALS REQUIRED FAC9B72.
  
 47.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-12-05 Cont ID  
Sent By dpalmer Date 2008-12-05 Time 09:04 Rev Time 0.00
Received By dpalmer Date 2008-12-05 Time 09:04 Sent To  
Notes
2008-12-05 09:05:16** PROVISO**
  
  
  
 1) NOTE: WATER HEATER LOAD IN AMPERAGE NOT SHOWN
 CORRECTLY. LOAD IS ALSO A CONTINUOUS LOAD UNDER 2005
 NEC 422.13.
  
 REVISE CALCULATIONS AND LOADS ALONG ON WATER HEATER.
 THIS WILL BE NEEDED ALONG WITH ANY OTHER REVISIONS MADE
 TO PLANS.
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-12-01 Cont ID  
Sent By dpalmer Date 2008-12-01 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2008-12-01 Time 14:48 Sent To  
Notes
2008-12-01 15:00:47** TEMP FAILED**
  
  
 1) NOTE: THE PLANS SUBMITTED IN THE TWO SETS ARE THE
 SAME EXACT SHEETS SIGNED, DATED AND SEALED OCTOBER 3RD,
 2008. THE LAST ELECTRICAL REVIEW WAS DONE ON OCTOBER
 21ST, 2008.
 THE SUBMITTED ENERGY CALCULATIONS ARE THE SAME FROM THE
 PREVIOUS REVIEW ALSO.
  
 CALLED AND LEFT MESSAGE WITH CONTRACTOR TO FIND OUT
 WHERE NEW SHEETS AND PLANS ARE?
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-30 Cont ID  
Sent By dpalmer Date 2008-10-30 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2008-10-30 Time 16:55 Sent To  
Notes
2008-10-30 16:55:32 
  
 ** DENIED REVIEW**
  
 ** A CALL WAS PLACED TO THE ENGINEER OF RECORD AT THE
 TIME OF THIS REVIEW HOWEVER WAS NOT IN THE OFFICE. A
 MESSAGE WAS LEFT SO THESE ITEMS BELOW COULD BE GONE
 OVER. PLANS ARE COMING BACK WITH COMMENTS FROM OTHER
 TRADES
  
 1) NOTE: THE SUBMITTED ENERGY CALCULATIONS CAN NOT BE
 STAMPED OR SIGNED OFF BY ELECTRICAL AS THERE ARE ERRORS
 WITH OTHER COMPONENTS TO THE BUILDING WHICH DO NOT
 COORDINATE WITH PLANS. SEE COMMENTS FROM OTHER TRADES.
 (BUILDING)
 EXAMPLE WOULD BE THE FLOORS WHICH ARE USING CARPET AND
 RUBBER PADDING WHERE THE FINISH SCHEDULE ON THE C SHEET
 INDICATE CONCRETE, TILE, ETC
 THE IDR NEEDS TO INDICATE THE WATER HEATER SIZE WHICH
 COORDINATES WITH PLANS. SEE NEXT COMMENT FOR LOADS.
 FBC 13-400.3A
  
 2) NOTE: PLEASE SEE THE LOADS WHICH ARE SHOWN ON THE
 PANEL SCHEDULES ARE IN QUESTION. THE PANEL INDICATES
 LOADS BY *AMPS* FOR EACH PHASE HOWEVER PLEASE SEE SMALL
 APPLIANCE(S), MICROWAVE AND OTHER SIMILAR ITEMS WHICH
 ARE SHOWN AS 1.5AMPS, 1.2 AMPS ETC. IS THIS NOT KVA?
 PLEASE SEE PANEL *A* FOR EXAMPLE:
 PLEASE SEE THE LOAD FOR THE WATER HEATER WHICH STATES
 20.0AMPS PER PHASE. WHAT SIZE OF WATER HEATER IS THIS?
 PLEASE SEE 422.13 UNDER THE 2005 NEC WHICH HAS BEEN
 REVISED TO CONSIDER STORAGE TYPE WATER HEATERS AS
 CONTINUOUS LOADS. THIS WOULD REQUIRE LOAD CALCULATIONS
 TO SHOW 125% FOR THIS UNIT.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-08 Cont ID  
Sent By dpalmer Date 2008-07-08 Time 13:31 Rev Time 0.00
Received By dpalmer Date 2008-07-08 Time 13:31 Sent To  
Notes
2008-07-08 13:31:41** DENIED2ND REVIEW **
  
 ** PLEASE KNOW THERE ARE SOME ITEMS FROM PREVIOUS
 REVIEW IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW ITEMS FROM THIS REVIEW
 WHICH ARE NEW BASED ON REVISED PLANS AND DOCUMENTS SUCH
 AS ENERGY CALCULATIONS ONLY NOW BEING SUBMITTED FOR THE
 FIRST TIME.
  
 1) NOTE: PLEASE REVISED AND VERIFY CODE LISTED ON E-3.
 PLANS SHOULD READ FBC 2004 W/ 2007 REVISIONS HOWEVER
 PLANS SHOW FBC 2004/2007. THIS COULD MISLEAD TO AN
 UNDERSTANDING THAT THE 2007 FBC MAY BE USED OR IS PART
 OF THE DESIGN.
 PLEASE REVISE. IF THIS WERE THE ONLY ITEMS PLANS COULD
 HAVE BEEN REDLINED.
  
 2) NOTE: PLEASE SEE ELECTRICAL NOTES ADDED TO SHEET E-1
 STATES LIGHTING CONTROLS TO BE INSTALLED HOWEVER PLANS
 DO NOT SHOW ANY LIGHTING CONTROLS. MAY NOT QUOTE THE
 CODE IN LIEU OF DESIGN.
 PLEASE CALL TO GO OVER LIGHTING CONTROLS FOR AREAS
 WHICH ARE REQUIRED. SQ FT IS NOW BEING SHOWN LESS THAN
 5K SQ FT HOWEVER THERE ARE SOME AREAS WHICH STILL
 REQUIRE AUTOMATED CONTROLS.
 13-415.1.ABC.1.1, .1.2, .1.3.
  
 ** THE INPUT DATA REPORT SHOWS OCCUPANCY SENSORS AS THE
 METHOD OF CONTROLS.
  
 3) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ALONG WITH THE INPUT DATA REPORT WHICH IS PART OF THE
 CALCULATIONS DO NOT COORDINATE WITH THE PLANS
 SUBMITTED. THE INPUT DATA REPORT WILL BE NOTED AS IDR
 IN THE REMAINDER OF THIS COMMENT. THERE WILL BE SEVERAL
 EXAMPLES GIVEN AS A BENEFIT HOWEVER THESE EXAMPLES ARE
 NOT AN EXHAUSTED LIST OF ALL POSSIBLE ITEMS.
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE KEEP IN MIND THE FIXTURE WATTAGE IS REQUIRED TO
 BE USED NOT THE BULB WATTAGE.
  
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING SHOWN ON THE IDR FOR EXTERIOR
 LIGHTING. PLANS SHOW AS MANY AS 6 75WATT EXTERIOR
 FIXTURES YET THE IDR SHOW ONLY 4.
  
 FOR EXAMPLE:
 THE IDR DOES NOT SHOW ANY OF THE 175W FIXTURES AS SHOWN
 ON PLANS FOR FLOODS YET THE PLANS SHOW AS MANY AS 8 TWO
 HEADED FLOODS.
  
 FOR EXAMPLE:
 THERE IS HOT WATER PIPING IN BUILDING YET THE IDR IS
 BLANK. (NOTED FOR OTHER TRADES AS FYI)
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR THE AMOUNT OF DOORS FROM
 CONDITIONED SPACE TO UNCONDITIONED SPACE. ( NOTED FOR
 OTHER TRADES AS FYI)
  
 FOR EXAMPLE:
 PLEASE TAKE A LOOK AT THE SQUARE FOOTAGE SHOWN FOR
 CONDITIONED AND UNCONDITIONED SPACE. THE SUBMITTED
 ENERGY CALCULATIONS INDICATE A TOTAL OF 1986 SQ FT YET
 THE PLANS SHOW OVER 4K SQ FT.
 PLEASE CORRELATE ALL.
  
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTING AS ONLY SOME OF THE
 128W FIXTURES ARE SHOWN IN THE IDR. IN FACT ONLY 6 OF
 THESE FIXTURES ARE SHOWN WHEN THE PLANS SHOW MORE THAN
 TWO DOZEN.
  
  
 ** THE ABOVE ARE SOME EXAMPLES.
  
 4) NOTE: PLEASE COORDINATE THE PANELS ON THE RISER WITH
 THE PANELS ON THE PANEL SCHEDULE. THE PANELS ARE BEING
 SHOWN AS 100AMPS ON RISER AND 200AMPS ON SCHEDULES.
 408, 310,
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-11 Cont ID  
Sent By dpalmer Date 2008-03-11 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2008-03-11 Time 12:59 Sent To  
Notes
2008-03-11 12:59:34** DENIED**
  
 FIRST REVIEW UNDER NEW PERMIT APPLICATION FOR THIS
 ADDRESS.
 PREVIOUS REVIEW WAS DONE UNDER APPLIED # 07030453 WHICH
 HAS NOW EXPIRED.
  
  
  
 1) NOTE:PLEASE SEE THE FOLLOWING CODES SHALL BE
 STATED ON PLANS. NEEDS TO BE ON ELECTRICAL PLANS AS
 WELL AS COVER SHEET.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (PLANS SHOW 2004)
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUESTED
 ON PREVIOUS REVIEW. AS THESE WERE NOT SUBMITTED NO
 REVIEW OF THESE ITEMS COULD BE DONE AT THIS TIME.
 PLEASE SEE 13-101.1.2, 13-400.3.B, 13-400.3.C,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 AND .1.4 FOR
 MISSING LIGHTING CONTROLS.
 PLEASE BE SURE TO SEE AUTOMATED CONTROLS REQUIRED IN
 .1.2 FOR INTERIOR LOCATIONS AS NOTED IN THE CODE.
 PLEASE BE SURE TO PROVIDE THE INFORMATION FOR EXTERIOR
 CONTROLS AS REQUIRED IN .1.4 AS NOTED ABOVE.
  
 4) NOTE: PLEASE SEE E-2 AS THIS WAS PRINTED AND MUCH OF
 THE INFORMATION ON PANEL SCHEDULE FOR LOADS, CIRCUITING
 ETC IS BLURRY AND NOT EASILY READ.
 PLEASE REPRINT WITH MORE CLARITY.
 FBC 106.1
  
 5) NOTE: PLEASE SEE SERVICE RISER ONLY SHOWS ONE RISER
 AND ONLY ONE SET OF CONDUCTORS. THERE IS PART OF THE
 CONDUCTORS WHICH NOTES *EACH* HOWEVER NO INFORMATION ON
 IF THERE ARE PARALLEL RISERS.
 PLEASE SHOW FOR PARALLEL CONDITIONS AS REQUIRED.
 240.4, 310.16
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE GROUNDING ELECTRODE IS NOTED TO
 STRUCTURAL STEEL HOWEVER IS ALSO REQUIRED TO FOOTER
 STEEL PER 250.50
  
 7) NOTE: PLEASE SEE RISER IS MISSING ANY METERING
 DEVICE? METER CAN, CT ETC.
 PLEASE CONTACT FPL FOR SERVICE REQUIREMENTS AND SEE FPL
 MINIMUM SERVICE SPECIFICATIONS. THIS INFORMATION CAN BE
 FOUND AT FPL WEBSITE.
 HTTP://WWW.FPL.COM/DOINGBUSINESS/BUILDER/B1_INDEX.SHTML
  
  
 8) NOTE: PLEASE PROVIDE THE ACTUAL AIC RATING OF THE
 EQUIPMENT. THE PLANS INDICATE THE AVAILABLE FAULT
 CURRENT AT SERVICE ETC HOWEVER DOES NOT PROVIDE RATINGS
 ON EQUIPMENT.
 110.9, 110.3, 90.7
 FBC 106.1.2
  
 9) NOTE: PLEASE PLACE THE REQUIRED DISCONNECTS FOR ANY
 ROOF-TOP A/C EQUIPMENT ON ELECTRICAL PLANS.
 440.11
  
 10) NOTE: PLEASE SEE 210.63 AND 210.8B FOR GFI REQUIRED
 FOR ANY ROOF-TOP AC EQUIPMENT.
  
 11) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL
 FIXTURES ON PLANS.
 PLEASE BE SURE TO SEE NOTE #2 FOR COORDINATION WITH THE
 ENERGY CALCULATIONS TO BE SUBMITTED.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 12) NOTE: PLEASE SEE SEVERAL NOTES ON E-3 STATES THERE
 MAY BE SOME SORT OF FIRE ALARM SYSTEM HOWEVER NO SYSTEM
 COULD BE LOCATED ON PLANS.
 THERE ARE ALSO NOTES WHICH STATES THE HORN AND STROBE
 LEVELS SHALL MEET NFPA-72, HOWEVER PLEASE SEE FBC
 11?4.28.1, .2 AND .3(4) FOR MINIMUM LOCATIONS AND
 LEVELS FOR FBC ADA.
  
 13) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET
 NEC 220.
 PLEASE SEE PANEL *A* FOR EXAMPLE*: HOW ARE THE
 APPLIANCE LOADS BEING FIGURED?
 PLEASE SEE 220.12, 220.14, 220.42, 220.44 ETC.
 CONTINUOUSLOADS WERE SHOWN AT 125%.
  
 14) NOTE: PLEASE SEE THE PLANS NEED TO IDENTIFY THE
 LOCATION OF PANEL *A* AS AN ELECTRICAL ROOM. THIS MAY
 NOT BE A CLOSET.
 SIGNAGE WILL ALSO BE REQUIRED.
 110.26, 240.24, 408.17 ETC
 FBC 106.1.2
  
 *** AS NOTED, AS THERE SOME ITEMS NOT YET SUBMITTED A
 FULL AND COMPLETE REVIEW CAN NOT BE DONE.PLEASE KNOW
 THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-12-23 Cont ID  
Sent By mgonzale Date 2008-12-23 Time 08:03 Rev Time 1.00
Received By mgonzale Date 2008-12-23 Time 08:01 Sent To ENG
Notes
2008-12-23 08:03:40PASSED
  
 ADDITIONAL INFORMATION WAS REQUESTED BY THE CITY'S
 STORMWATER ENGINEER JEFF RENAULT,
 IT WAS RESPONDED TO AND SATIFIED. HIS STATEMENT: "I
 HAVE REVIEWED THE REVISED GRADING AND DRAINAGE PLAN AND
 DRAINAGE CALCULATIONS FOR THE SUBJECT PROJECT AS
 SUBMITTED BY BKGES ,ENGINEERING , INC AND RECOMMEND
 APPROVAL OF THE SITE DRAINAGE FEATURES AS SUBMITTED.
 SHOULD YOU HAVE ANY QUESTIONS , PLEASE CONTACT ME."
  
  
 MANNY GONZALEZ
 PROJECT COORDINATOR
 ENGINEERING SERVICES.
 (561) 494-1085

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-11-18 Cont ID  
Sent By mgonzale Date 2008-11-18 Time   Rev Time 1.00
Received By mgonzale Date 2008-11-18 Time   Sent To ENG
Notes
2008-11-18 15:35:24- PASSED -
  
 REVIEW AT ENGINEERING DEPT WAS PERFORM AND APPROVED
 AS-NOTED. ANY QUESTIONS PLEASE CONTACT:
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR 561-494-1085
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-06-27 Cont ID  
Sent By rchokshi Date 2008-06-27 Time 13:56 Rev Time 0.00
Received By rchokshi Date 2008-06-27 Time 13:45 Sent To  
Notes
2008-06-27 13:52:11FAILED
  
 MR. S. M. SINCLAIR, P.E. WROTE IN HIS RESPOND, DATED
 JUNE 9, 08 THAT"CONTRACTOR TO ADDRESS ALL ENG-RELATED
 COMMENTS".WE LOOKED IN YOUR WHOLE PACKAGE, WE DID NOT
 FIND CONTRACTOR'S RESPOND FOR OUR ENG COMMENTS.
 THEREFORE, PLEASE RESPOND TO ENG REVIEW COMMENT FOR REV
 1, 3-18-08 AS FOLLOWS.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 IF THE TOTAL AREA IS LESS THAN AN ACRE,NOI NOT
 REQUIRED.
  
 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS OFPOLLUTION PREVENTION , CLOTHES
 USED FOR SILT FENCE ETC., PLANS SHOWING SILT FENCE
 AROUND THE SITE & TURBIDITY AROUND STORM CATCH BASIN
 DRAINS DURING CONSTRUCTION AND ALL DEMOLITION PHASE.
 HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP
 DUST PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS. STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BEFORE WE APPROVE.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-03-18 Cont ID  
Sent By rchokshi Date 2008-03-18 Time 13:41 Rev Time 0.00
Received By rchokshi Date 2008-03-18 Time 13:36 Sent To  
Notes
2008-03-18 13:40:48FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 IF THE TOTAL AREA IS LESS THAN AN ACRE,NOI NOT
 REQUIRED.
  
 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS OFPOLLUTION PREVENTION , CLOTHES
 USED FOR SILT FENCE ETC., PLANS SHOWING SILT FENCE
 AROUND THE SITE & TURBIDITY AROUND STORM CATCH BASIN
 DRAINS DURING CONSTRUCTION AND ALL DEMOLITION PHASE.
 HEIGHT OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP
 DUST PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT&STORM WATER QUALITY CALCULATIONS. STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BEFORE WE APPROVE.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-12-12 Cont ID  
Sent By mwennerg Date 2008-12-12 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2008-12-12 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-14 Cont ID  
Sent By mawillia Date 2008-11-14 Time 14:36 Rev Time 0.00
Received By mawillia Date 2008-11-14 Time 14:22 Sent To  
Notes
2008-11-14 14:23:15*****FIRE STAMPING NEEDED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; THE APPROPIATE PLAN SHEETS TO BE
 FIRE-STAMPED WHEN ALL PLAN EXAMINERS' COMMENTS HAVE
 BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 10:52 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 10:52 Sent To  
Notes
2008-07-21 11:07:50***DENIED***
  
 1) RESPONSE LETTER INDICATES DEMOLITION ONLY. NFPA 241
 IS THE STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION AND DEMOLITION OPERATIONS. PLEASE CORRECT
 ELECTRICAL NOTE ON SHEET E-3 NEXT TO NFPA 241.
  
 2) OK
  
 3) OK
  
 4) RESPONSE LETTER INDICATES MULTIPLE TENANTS. PLEASE
 CLEARLY ILLUSTRATE OR CLARIFY (1) HOUR SEPARATION
 REQUIREMENTS BETWEEN TENANTS.
  
 5) OK
  
 6) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 15:10 Rev Time 0.00
Received By mawillia Date 2008-03-31 Time 14:21 Sent To  
Notes
2008-03-31 15:10:16*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING ROADS, STREETS,
 FIRE LANES)
  
 3. ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 EAST TAMARIND AVENUE, DISPLAY THE NUMERICAL ADDRESS OF
 THE BUILDING. AS PER WEST PALM BEACH CODE, ADDRESS
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
 4. PROVIDE THE FOLLOWING INFORMATION: * WILL THE
 BUILDING BE OCCUPIED BY A SINGLE TENANT OR MULTIPLE
 TENANTS, * OCCUPANCY TYPE FOR EACH TENANT SPACE, *
 OCCUPANT LOAD FOR EACH TENANT SPACE, * IS THE BUILDING
 FIRE SPRINKLERED OR NOT?
  
 5. IT IS NOTED ON SHEET C1 OF "FIRE ALARM PERMIT BY
 OTHERS". DOES THE BUILDING HAVE A FIRE ALARM SYSTEM? IF
 SO, PROVIDE A LAYOUT OF THE SYSTEM.
  
 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2010-01-12 Cont ID  
Sent By btrobaug Date 2010-01-12 Time 12:59 Rev Time 0.00
Received By btrobaug Date 2010-01-12 Time 12:59 Sent To  
Notes
2010-01-12 13:19:02THIS REVISION WAS SUBITTED FOR BUILDING ONLY. THERE ARE
 4 REVISIONS ON THESE PAGES THAT HAVE NOT BEEN REVIEWED,
 FIRE, ELECTRICAL, PLUMBING AND MECHANICAL NCALLED EZRA
 AND INFORMED HIM AND AM WAITING FOR A CALL BACK./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 10:11 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 10:11 Sent To  
Notes
2008-11-25 10:15:04TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-15 Cont ID  
Sent By adarroug Date 2008-10-15 Time 16:58 Rev Time 0.00
Received By adarroug Date 2008-10-15 Time 16:58 Sent To  
Notes
2008-10-17 10:09:45TO "COMM" BD#54
2008-10-15 16:59:25WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 13:48 Rev Time 0.00
Received By adarroug Date 2008-06-13 Time 13:48 Sent To  
Notes
2008-06-13 13:48:30TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 14:22 Rev Time 0.00
Received By mawillia Date 2008-03-11 Time 13:02 Sent To  
Notes
2008-03-11 13:02:47TO "COMM" BD#60

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-12-13 Time 16:10 Rev Time 0.00
Received By rregueir Date 2008-12-13 Time 16:10 Sent To  
Notes
2008-12-13 16:10:47NEW CLACS OK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-24 Cont ID  
Sent By tgordon Date 2008-10-24 Time 09:01 Rev Time 0.40
Received By tgordon Date 2008-10-24 Time 09:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-07-17 Cont ID  
Sent By tgordon Date 2008-07-17 Time 09:18 Rev Time 0.45
Received By tgordon Date 2008-07-17 Time 09:18 Sent To  
Notes
2008-07-17 09:26:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW ON MECHANICAL PLAN THE OUTDOOR AIR
 CALCULATION AND PROVIDE OUTDOOR AIR, PER 2004 FBC/M
 403.2.
  
 2)A/C SYSTEM MODEL NUMBER TCY060G100A LISTED ON THE
 A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-407.1.ABC.3.1.1 OR
 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-20 Cont ID  
Sent By hmoser Date 2008-03-20 Time 17:18 Rev Time 0.00
Received By hmoser Date 2008-03-20 Time 17:18 Sent To  
Notes
2008-03-20 17:17:22PLAN DENIED
 PAGE A4 ON PLANS SHOW ROOF TOP UNIT DETAIL, R19
 INSULATION SEE SECTION 13.406.1ABC.1.4 FLORIDA ENERGY
 CODE .
 PAGE A 4 ON ROOR TOP UNIT DETAIL PLEASE SHOW CURB TO
 ROOF TIEDOWN AND UNIT TO CURB TIEDOWN .
 PAGE MP1 PLEASE PROVIDE RETURN AIR GRILL SIZE IN OFFICE
 1,3 AND RECIPITION AREA.
 PLEASE PROVIDE SUPLY TRUNK LINE SIZE AND RETURN AIR
 TRUNKLINE SIZE ON THE PLANS
 PLEASE REFER TO SECTION 606 AND 606.4.1 FBC(M) 2004
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-01-06 Cont ID  
Sent By kstevens Date 2009-01-06 Time 16:20 Rev Time 0.00
Received By kstevens Date 2009-01-06 Time 16:20 Sent To  
Notes
2009-01-06 16:20:30 
  
  
 PASSED/PROVISO:
 A REVISION FOR SHEET MP2 IS REQUIRED PRIOR TO FIRST
 INSPECTION SHOWING THE SERVICE SINKS ON THE SANITARY
 RISER DIAGRAM AND THE SANITARY PLUMBING PLAN TO REFLECT
 THE FLOOR PLAN A2 AND THE WATER PLAN AND THE WATER
 RISER DIAGRAMS SHEET MP3. SECTION 106.1.1.
  
 A REVISION FOR SHEET A2 IS REQUIRED SHOWING THE CLEAR
 FLOOR SPACE FOR THE DRINKING FOUNTAINS AS FORWARD
 APPROACH, NOT PARALLEL APPROACH AS SHOWN. SECTION
 11-4.15.5.
  
  
  
 .
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-10-29 Cont ID  
Sent By kstevens Date 2008-10-29 Time 07:01 Rev Time 0.00
Received By kstevens Date 2008-10-29 Time 07:01 Sent To  
Notes
2008-10-29 07:20:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS
 REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS
 EXPIRED.
  
 1. OK
  
 2. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES.
 SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE
 STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE
 REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER
 RISER DIAGRAMS.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE SERVICE SINKS WERE NOT
 ADDRESSED.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT SECTION 11-4.1.3(10)(A) WAS
 NOT ADDRESSED. ALSO SHOW THE CLEAR FLOOR SPACE REQUIRED
 FOR THE DRINKING FOUNTAINS PER SECTION 11-4.15.5.
  
 4. OK
  
 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19,
 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR
 THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF
 ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW
 COMPLIANCE.
 ****COMMENT NOT ADDRESSED FOR THE SHOWER. -- SEE
 COMMENT 4 FOR REQUIREMENTS FOR W/C & LAV. -- SHOW
 COMPLIANCE FOR THE FOLLOWING:
 ___FOR SHOWER
 A. 11-4.21.4 GRAB BARS
 B. 11-4.21.5 CONTROLS
 C. 11-4.21.6 SHOWER UNIT
 ******RESPONSE NOTED, BUT THE W/C SHALL BE 18" OFF THE
 WALL. MY MISTAKE ON THE SPACING FOR THE WATER CLOSET. A
 MINIMUM 36" IS REQUIRED FROM THE WALL TO THE LAV. SEE
 FIGURE 28. THERE IS A NOTE STATING "BATH TO BE HANDICAP
 ADAPTABLE". THIS IS NOT CORRECT. PER SECTION
 11-4.1.3(11), IF BATHING ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE BATHROOM SHALL COMPLY WITH
 SECTION 11-4.23. PLEASE DELETE NOTE AND MAKE THE
 BATHROOM ACCESSIBLE. SHOW THE GRAB BARS FOR THE W/C.
  
 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE
 BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE
 SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE.
 FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT
 ALLOWED IN THE CLEAR FLOOR SPACE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE
 REQUIRED FOR THE SINK SHALL BE SHOWN ON THE FLOOR PLAN.
 SECTION 11-4.24.5. FORWARD APPROACH REQUIRED MAXIMUM
 19" UNDERNEATH THE SINK.
  
 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD ON DETAIL.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE RELIEF VALVE, (P&T),
 SHALL NOT BE USED AS A MEANS OF CONTROLLING THERMAL
 EXPANSION. SECTION 504.4. PLEASE INDICATE METHOD OF
 CONTROL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ******NO RESPONSE, ONE SET OF VOIDED SHEETS HAS NOT
 BEEN SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-07-15 Cont ID  
Sent By kstevens Date 2008-07-15 Time 08:18 Rev Time 0.00
Received By kstevens Date 2008-07-14 Time 15:40 Sent To  
Notes
2008-07-15 08:18:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 ****FROM PREVIOUS REVIEW:
  
 A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS
 REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS
 EXPIRED.
  
 1. OK
  
 2. DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES.
 SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE
 STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE
 REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER
 RISER DIAGRAMS.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 4. SUBMIT DETAILS FOR ALL TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11.4-22
 WITH ALL SUBSECTIONS. THE LAV SHALL BE A MINIMUM 15"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO CENTER
 ON THE 30" WIDTH OF THE 30"X48" CLEAR FLOOR SPACE.
 ****NO RESPONSE, SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S
 A. 11-4.16.5 FLUSH CONTROLS (WIDE SIDE)
 ___FOR LAVS
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.6 FAUCETS
  
 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19,
 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR
 THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF
 ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW
 COMPLIANCE.
 ****COMMENT NOT ADDRESSED FOR THE SHOWER. -- SEE
 COMMENT 4 FOR REQUIREMENTS FOR W/C & LAV. -- SHOW
 COMPLIANCE FOR THE FOLLOWING:
 ___FOR SHOWER
 A. 11-4.21.4 GRAB BARS
 B. 11-4.21.5 CONTROLS
 C. 11-4.21.6 SHOWER UNIT
  
 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE
 BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE
 SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE.
 FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT
 ALLOWED IN THE CLEAR FLOOR SPACE.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD ON DETAIL.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-29 Cont ID  
Sent By kstevens Date 2008-03-29 Time 08:46 Rev Time 0.00
Received By kstevens Date 2008-03-28 Time 17:54 Sent To  
Notes
2008-03-29 10:12:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS
 REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS
 EXPIRED.
  
 1. SHT A4 ROOF DRAINAGE CALCULATIONS DO NOT APPEAR TO
 INCLUDE THE VERTICAL CONTRIBUTION OF THE PARAPET WALLS.
 PLEASE INDICATE THE HEIGHT OF THE PARAPET WALLS. ALSO
 SHOW THE HEIGHT OF THE ROOF AT BOTH THE HIGH END AND
 THE LOW END TO VERIFY VERTICAL CONTRIBUTION. SECTIONS
 1101.1, 1106 & 1107.--SECONDARY DRAINAGE IS
 REQUIRED PER SECTION 1107.1. PLEASE SHOW THE LOCATION
 OF ALL SECONDARY ROOF DRAINAGE, (EMERGENCY OVERFLOW
 SCUPPERS PER SECTION 1503.4.3).--GUTTERS WITH
 DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF
 LESS THAN 6 INCHES HORIZONATL PROJECTION EXCEPT FOR
 GABLE END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. A
 COLLECTOR HEAD AT THE TOP OF THE DOWNSPOUT WILL BE
 APPROVED IN PLACE OF THE GUTTER. SECTION 1503.6. (SHOW
 THE DISCHARGE OF THE DOWNSPOUT A MINIMUM 1FT FROM
 STRUCTURE SIDEWALL). SUBMIT A DETAIL FOR THE COLLECTOR
 HEAD SHOWING LENGTH, WIDTH & HEIGHT. ALSO INDICATE THE
 SIZE OF THE DOWNSPOUTS.
  
 2.DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES.
 SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE
 STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE
 REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER
 RISER DIAGRAMS.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 4. SUBMIT DETAILS FOR ALL TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11.4-22
 WITH ALL SUBSECTIONS. THE LAV SHALL BE A MINIMUM 15"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO CENTER
 ON THE 30" WIDTH OF THE 30"X48" CLEAR FLOOR SPACE.
  
 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19,
 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR
 THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF
 ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW
 COMPLIANCE.
  
 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE
 BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE
 SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE.
 FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT
 ALLOWED IN THE CLEAR FLOOR SPACE.
  
 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD ON DETAIL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2008-11-26 Cont ID  
Sent By kdfreema Date 2008-11-26 Time 13:18 Rev Time 0.00
Received By kdfreema Date 2008-11-26 Time 13:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2008-10-29 Cont ID  
Sent By bpowell Date 2008-10-29 Time 17:40 Rev Time 0.00
Received By bpowell Date 2008-10-29 Time 17:40 Sent To  
Notes
2008-10-29 17:46:251. PLEASE PROVIDE TWO (2) COPIES OF THE APPROVED
 LANDSCAPE AND PLANTING PLANS WITHIN THE APPLICATION
 PACKET.
 2. PLEASE UPDATE, AND CORRECT THE PARKING DETAIL.
 PURSUANT TO SECTION 94-485(G) ALL PARKING SPACES SHALL
 BE DOUBLE STRIPED.
  
 IF YOU HAVE ANY QUESTIONS OR COMMENTS PLEASE CONTACT;
 BOBBY POWELL JR. (561) 822-1401, [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2008-06-24 Cont ID  
Sent By bpowell Date 2008-06-24 Time 16:12 Rev Time 0.00
Received By bpowell Date 2008-06-24 Time 16:12 Sent To  
Notes
2008-06-24 16:19:321. THE DATA TABLE INDICATING THE SQUARE FOOTAGES ON THE
 SITE PLAN DOES NOT MATCHES WHAT IS SHOWN ON DRAWING
 SITE PLANS. FOR EXAMPLE PROPOSED GARAGE =738 SF, THE
 DRAWING INDICATES 750 SF.
  
 2. WHEN THE SITE PLAN AND LANDSCAPE PLAN ARE
 RESUBMITTED BE SURE THAT THE SQUARE FOOTAGE MATCH ON
 ALL PLANS THAT ARE SUBMITTED FOR THE PERMIT.ALSO, BE
 SURE THESE PLANS ARE CONSISTENT WITH ALL OTHER PLANS.
  
 FOR QUESTIONS OR COMMENTS, PLEASE CONTACT: BOBBY POWELL
 JR., PLANNER, AT (561) 822-1401, [email protected].

Review Stop Z ZONING
Rev No 2 Status N Date 2008-06-18 Cont ID  
Sent By bpowell Date 2008-06-18 Time 17:11 Rev Time 0.00
Received By bpowell Date 2008-06-18 Time 17:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-05 Cont ID  
Sent By bpowell Date 2008-03-05 Time 16:56 Rev Time 0.00
Received By bpowell Date 2008-03-05 Time 16:55 Sent To  
Notes
2008-03-05 17:00:171. PLEASE INCLUDE TWO (2) COPIES OF A SIGNED AND SEALED
 SURVEY ALONG WITH THE PERMIT APPLICATION.
  
 2. AT LEAST TWO (2) COPIES OF A SITE PLAN SHALL BE
 SUBMITTED WITH THE PERMIT APPLICATION.
  
 3. AT LEAST TWO (2) COPIES OF A LANDSCAPE PLAN SHALL BE
 SUBMITTED.
  
 4. THE STRIPPING DETAIL NEEDS TO INDICATE THAT PARKING
 WILL BE DOUBLE STRIPPED WITH 4 INCH WHITE LINES AND AT
 LEAST 12 INCHES IN BETWEEN THE STRIPPING FOR STANDARD
 SPACES.
  
 5. DISABLED SPACES SHALL MEET THE ADA REQUIREMENTS AS
 SHOWN IN THE ATTACHED DRAWING.
  
 6. WHEN THE SITE PLAN AND LANDSCAPE PLAN ARE SUBMITTED
 BE SURE THAT THE SQUARE FOOTAGES MATCH ON ALL PLANS
 THAT ARE SUBMITTED FOR THE PERMIT.THE FLOOR PLAN THAT
 WAS APPROVED DURING SITE PLAN REVIEW SLIGHTLY DIFFERS
 FROM WHAT IS SHOWN FOR THIS PERMIT.
  
 FOR ANY QUESTIONS OR COMMENTS PLEASE CONTACT BOBBY
 POWELL JR., PLANNER, (561) 822-1401, [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved