Plan Review Details - Permit 08020666
Plan Review Stops For Permit 08020666
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-09 Cont ID  
Sent By mjacobs Date 2008-05-09 Time 10:17 Rev Time 0.00
Received By mjacobs Date 2008-05-09 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-11 Cont ID  
Sent By mjacobs Date 2008-04-11 Time 08:28 Rev Time 0.00
Received By mjacobs Date 2008-04-11 Time 06:11 Sent To  
Notes
2008-04-11 11:00:39 
  
 BUILDING PLAN REVIEW
 PERMIT: 08020666
 ADD: 1335 OLD OKEECHOBEE RD
 CONT: MAURO BROTHERS LLC
 TEL: (561)738-4713
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-11-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **THIS INFORMATION SHALL BE SHOWN ON PLANS.**
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)OK
 5)OK
  
 6)CLEARLY INDICATE THE TOTAL SQUARE FOOT OF THE AREA
 WHERE THE MEZZANINE WILL BE CONSTRUCTED, AND SHOW THE
 ENTIRE FLOOR PLAN ON THE STRUCTURAL DRAWINGS. THE
 BUILDING TYPE SHALL BE INDICATED ON THE DRAWINGS PER
 TABLE 601.
  
 **THE 8X11 SHEET ATTACHED TO THE DRAWINGS SHOWS THE
 AREA OF THE MEZZANINE HOWEVER, THE TOTAL SQUARE FOOT OF
 THE SUITE IS NOT INDICATED AS REQUESTED AND THE ENTIRE
 FLOOR PLAN IS NOT SHOWN. ARE THERE ANY OFFICES BELOW
 THE MEZZANINE? IF SO PLEASE SHOW THE FLOOR PLAN FOR THE
 OFFICE AREA AND ELEVATION DRAWINGS OF THE OFFICES. WHAT
 IS THE FIRE RATING OF THE PARTITION WALLS SEPARATING
 EACH SUITE? **
  
 **THE BUILDING TYPE NOTED ON THE PLANS IS TYPE 1. TYPE
 1 BUILDINGS ARE CONSTRUCTED WITH NONCOMBUSTIBLE
 MATERIALS. FBC 602.2 AND TABLE 601. SEE SECTION 603
 WHERE FIRE-RETARDANT- TREATED WOOD IS PERMITTED IN SOME
 SITUATIONS. STATE THE HEIGHT OF THE BUILDING ON THE
 PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561)805-6676
 [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By mjacobs Date 2008-03-06 Time 12:26 Rev Time 0.00
Received By mjacobs Date 2008-03-06 Time 09:35 Sent To  
Notes
2008-03-06 12:26:25 
 BUILDING PLAN REVIEW
 PERMIT: 08020666
 ADD: 1335 OLD OKEECHOBEE RD
 CONT: MAURO BROTHERS LLC
 TEL: (561)738-4713
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3-6-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)THE ENGINEER NEEDS TO INDICATE WHAT METHOD HE IS
 USING TO DESIGN THE MEZZANINE. THE DESIGN, FABRICATION
 AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS AND
 STRUCTURES SHALL BE IN ACCORDANCE WITH EITHER THE
 AISC-LRFD, AISC 335 OR AISC-HSS. FBC 2205.1. THE OPEN
 WEB JOIST SHALL BE IN ACCORDANCE WITH ONE OF THE
 FOLLOWING STEEL JOIST INSTITUTE SPECIFICATIONS: FBC
 2206.1
 1.STANDARD SPECIFICATIONS FOR OPEN WEB STEEL
 JOISTS, K SERIES.
 2.STANDARD SPECIFICATIONS FOR LONG SPAN STEEL
 JOISTS, LH SERIES AND DEEP LONG SPAN STEEL
 JOISTS, DLH SERIES.
 3.STANDARD SPECIFICATIONS FOR JOIST GIRDERS.
  
 5)F.A.C. 61G15-23.002 THE ENGINEER NEEDS TO SIGN,
 SEAL AND DATE PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER.
  
 6)CLEARLY INDICATE THE TOTAL SQUARE FOOT OF THE AREA
 WHERE THE MEZZANINE WILL BE CONSTRUCTED, AND SHOW THE
 ENTIRE FLOOR PLAN ON THE STRUCTURAL DRAWINGS. THE
 BUILDING TYPE SHALL BE INDICATED ON THE DRAWINGS PER
 TABLE 601.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561)805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By btrobaug Date 2008-04-08 Time 14:30 Rev Time 0.00
Received By btrobaug Date 2008-04-08 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By btrobaug Date 2008-03-04 Time 11:04 Rev Time 0.00
Received By btrobaug Date 2008-03-04 Time 08:30 Sent To  
Notes
2008-03-04 09:24:03 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-2 HAS THE "POWER DENSITY" AT 1.70 W/FT
 SQUARE. PER TABLE 13-415.2.C.1, THE MAXIMUM ALLOWABLE
 DENSITY WOULD BE 0.8, IN WHICH CASE THESE FIXTURES DO
 NOT COMPLY.
  
 2} INDICATE THE POWER SOURCE FOR THE EMERGENCY LIGHT ,
 UNDER POWER LOSS.
  
 3} THE DESCRIPTION OF WORK ON THEAPPLICATION
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-09 Cont ID  
Sent By mwennerg Date 2008-05-09 Time 14:57 Rev Time 0.00
Received By mwennerg Date 2008-05-09 Time 14:57 Sent To  
Notes
2008-05-09 14:57:55SENT TO L. MARTINEZ

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-04-11 Cont ID  
Sent By mawillia Date 2008-04-11 Time 16:10 Rev Time 0.00
Received By mawillia Date 2008-04-11 Time 15:21 Sent To  
Notes
2008-04-11 15:54:38*****UNSAT*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW COMMENTS STILL NEED TO BE ADDRESSED:
  
  
 5.THE OCCUPANT LOAD (0) LISTED IN THE GENERAL NOTES
 ON THE STRUCTURAL SHEET IS INCORRECT.BASED UPON
 OCCUPANCY TYPE,LIST THE OCCUPANT LOAD AS PER NFPA
 101, LIFE SAFETY CODE
  
 7.HOW WILL FIRE SPRINKLER PROTECTION ABOVE AND
 UNDERNEATH THE MEZZANINE BE ACHIEVED?
  
 *NEW COMMENT:
  
 A.ANY LOOSE PLAN SHEET(S) SHALL BE ATTACHED TO THE
 SUBMITTED PLAN SET(S).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By mawillia Date 2008-03-10 Time 15:08 Rev Time 0.00
Received By mawillia Date 2008-03-10 Time 14:34 Sent To  
Notes
2008-03-10 15:08:32*****DENIED*****
  
  
 1.THE CORRECT ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE LISTED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.PLEASE BE ADVISED OF THE FOLLOWING:(A)
 SUITE 200 IS SHOWN ON PLAN SHEET FP-1 INSTEAD OF SUITE
 600(B) THE JOB SITE ADDRESS IS IN WEST PALM BEACH AND
 NOT PALM BEACH AS LISTED IN THE TITLE BLOCK ON SHEETS
 E-1 AND E-2.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED
 DURING THE SCOPE OF WORK.IF SO, MEANS OF EGRESS AND
 AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN
 PLACE AND CONTINUOUSLY MAINTAINED.
  
 5.PLEASE LIST THE FOLLOWING FOR THE BUILDING:
 OCCUPANCY TYPE,OCCUPANT LOAD,FIRE ALARM AND/OR FIRE
 SPRINKLER DEVICES, AND ANY OTHER PERTINENT
 INFORMATION.
  
 6.PLEASE PROVIDE A CLEAR REPRENSENTATION OF THE
 MEZZANINE IN RELATION TO THE FLOOR PLAN INCLUDING EXIT
 LIGHTS/DOORS, EMERGENCY LIGHTS, ETC.
  
 7.HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE
 ALARM DEVICES, IF SO EQUIPPED.IN ADDITION. HOW WILL
 FIRE SPRINKLER PROTECTION UNDERNEATH THE MEZZANINE BE
 ACHIEVED?
  
 8.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 14:31 Sent To  
Notes
2008-04-29 14:35:11TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 09:25 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 09:25 Sent To  
Notes
2008-04-07 09:28:39TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-12 Cont ID  
Sent By btrobaug Date 2008-03-12 Time 12:10 Rev Time 0.00
Received By btrobaug Date 2008-02-27 Time 14:50 Sent To PC
Notes
2008-02-27 14:51:12TO "BOB"#4

Review Stop Z ZONING
Rev No 4 Status P Date 2008-05-05 Cont ID  
Sent By eschneid Date 2008-05-05 Time 15:23 Rev Time 0.00
Received By eschneid Date 2008-05-05 Time 15:23 Sent To  
Notes
2008-05-05 15:23:37PASSED - RESTAMP, 515 SQ. FT. STORAGE MEZZANINE.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By eschneid Date 2008-04-15 Time 15:45 Rev Time 0.00
Received By eschneid Date 2008-04-15 Time 15:45 Sent To  
Notes
2008-04-15 15:45:43PASSED - 515 SQUARE FEET OF STORAGE MEZZANINE.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-12 Cont ID  
Sent By eschneid Date 2008-03-12 Time 11:26 Rev Time 0.00
Received By eschneid Date 2008-03-12 Time 11:26 Sent To  
Notes
2008-03-12 11:26:48MEZZANINE FOR STORAGE USE ONLY.

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-28 Cont ID  
Sent By choops Date 2008-02-28 Time 10:55 Rev Time 0.00
Received By choops Date 2008-02-28 Time 10:55 Sent To  
Notes
2008-02-28 10:55:41*ZONING REVIEW NOT REQUIRED; INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.