Plan Review Details - Permit 08020649
Plan Review Stops For Permit 08020649
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-11 Cont ID  
Sent By shill Date 2008-06-11 Time 13:47 Rev Time 0.00
Received By shill Date 2008-06-11 Time 13:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-27 Cont ID  
Sent By shill Date 2008-05-27 Time 16:18 Rev Time 0.00
Received By shill Date 2008-05-27 Time 16:18 Sent To  
Notes
2008-05-27 16:27:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE ELECTRIC REVIEWER'S FIRST REVIEW.TWO SETS
 REQUIRED FOR PERMIT ISSUANCE, FBC*106.
  
 ONLY ONE PAGE OF THE GUARDIAN INSTALLATION GUIDE, WITH
 SETBACK INFORMATION HIGHLIGHTED, WAS SUBMITTED ALONG
 WITH THE ENTIRE BOOK.I CANNOT DETERMINE WHETHER TWO
 SETS OF THE BOOK ARE REQUIRED AS THIS WAS NOT A PART OF
 MY REVIEW.OTHER TRADES DO REQUIRE SETBACK
 INFORMATION, BUT I CANNOT DETERMINE WHETHER THE ENTIRE
 BOOK IS REQUIRED.
  
 ONLY ONE COPY OF THE INSTALLATION AND OWNER'S MANUAL
 WAS PROVIDED.I CANNOT DETERMINE WHETHER OR NOT THIS
 IS REQUIRED FOR ONE OF THE OTHER REVIEWERS; THIS WAS
 NOT REQUIRED FOR MY REVIEW.
  
 NEITHER ITEM WAS REQUIRED FOR BUILDING REVIEW BUT MAY
 HAVE BEEN REQUIRED BY ANOTHER TRADE.THE MANUAL HAS
 BEEN STAMPED BY ELECTRIC (WHICH INDICATES THAT THIS
 INFORMATION WAS REQUIRED), BUT ONLY ONE SET WAS
 INCLUDED IN THE RESUBMITTAL PACKAGE.THE ELECTRIC
 REVIEWER IS NOT IN THE OFFICE TODAY, SO I AM UNABLE TO
 ASK HIM.HOWEVER, IT IS THE CONTRACTOR'S
 RESPONSIBILITY TO ALWAYS SUBMIT TWO COMPLETE,
 IDENTICAL, COLLATED, BOUND SETS OF PERMIT DOCUMENTS.
 THIS HELPS TO EXPEDITE THE REVIEW PROCESS AND PREVENT
 DELAYS.
  
 PLEASE RESOLVE PAPERWORK ISSUES WITH OTHER TRADES.
 DETERMINE WHICH DOCUMENTS ARE REQUIRED AND PROVIDE TWO
 IDENTICAL SETS AS REQUIRED.IF YOU NEED ASSISTANCE OR
 CLARIFICATION, PLEASE FEEL FREE TO CONTACT ME.I
 APOLOGIZE FOR THE DELAY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By shill Date 2008-03-10 Time 12:27 Rev Time 0.00
Received By shill Date 2008-03-10 Time 12:27 Sent To  
Notes
2008-03-10 12:27:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 2.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 3.)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB
 SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER.
  
 2.)THE VALUE IS TOO LOW.PROVIDE A REASONABLE VALUE
 OR AN ESTIMATED VALUE WILL BE DONE FOR YOU USING
 MARSHALL & SWIFT.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-19 Cont ID  
Sent By btrobaug Date 2008-05-19 Time 16:57 Rev Time 0.00
Received By btrobaug Date 2008-05-19 Time 15:29 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-03 Cont ID  
Sent By btrobaug Date 2008-03-03 Time 09:50 Rev Time 0.00
Received By btrobaug Date 2008-03-03 Time 09:06 Sent To M
Notes
2008-03-03 09:36:16 
  
  
 1} THE VALUE ON THE APPLICATION MUSTINCLUDE THE TOTAL
 COST OF LABOR ANDMATERIAL FOR THE GENERATOR,
 EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.)AND PAD PER
 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHENRESUBMITTING, AND
 GET A RECEIPT FROM THEPERMIT CLERK.2}
  
 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005 NEC.
  
 3} INDICATE THE SETBACK OF THE GENERATOR FROM THE
 GARAGE.
  
 4} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, METER ENCLOSURE, DISCONNECTS, ATS AND
 PANELS, SO THAT COMPLIANCE WITH ARTICLES 225 AND 230
 CAN BE REVIEWED.
  
 5} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By mperson Date 2008-05-20 Time 11:44 Rev Time 0.00
Received By mperson Date 2008-05-20 Time 11:44 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By mperson Date 2008-03-06 Time 13:14 Rev Time 0.00
Received By mperson Date 2008-03-06 Time 13:14 Sent To B
Notes
2008-03-06 13:23:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PROVIDE TWO COPIES OF A SITE PLAN OR SURVEY
 INDICATING ALL DIMENSIONS OF THE PROPOSED GENERATOR
 FROM PROPERTY LINES AND ADJACENT STRUCTURES. PER FBC
 FUEL GAS SECTION 401.1 SCOPE.
  
 2. PROVIDE TWO SETS OF CONSTRUCTION DOCUMENTS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1
 SUBMITTAL DOCUMENTS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 11:06 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 11:06 Sent To B
Notes
2008-06-06 11:06:39TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 12:42 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 12:42 Sent To Z
Notes
2008-05-15 12:43:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-10 Cont ID  
Sent By shill Date 2008-03-10 Time 12:27 Rev Time 0.00
Received By shill Date 2008-02-27 Time 12:46 Sent To  
Notes
2008-02-27 12:47:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-03-03 Cont ID  
Sent By tgordon Date 2008-03-03 Time 14:04 Rev Time 0.25
Received By tgordon Date 2008-03-03 Time 14:03 Sent To G
Notes
2008-03-03 14:05:25*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop Z ZONING
Rev No 2 Status P Date 2008-05-19 Cont ID  
Sent By choops Date 2008-05-19 Time 09:04 Rev Time 0.00
Received By choops Date 2008-05-19 Time 09:04 Sent To E
Notes
2008-05-19 09:05:37***APPROVED - RESUB #1***
  
 PROVISO:GENERATOR SHALL BE SETBACK A MINIMUM OF NINE
 (9) FEET FROM THE REAR PROPERTY LINE.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-28 Cont ID  
Sent By choops Date 2008-02-28 Time 09:15 Rev Time 0.00
Received By choops Date 2008-02-28 Time 09:15 Sent To E
Notes
2008-02-28 09:16:57***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.THE GENERATOR MUST BE A MINIMUM OF NINE (9)
 FEET FROMT THE REAR PROPERTY LINE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - GEN. RES. BOX