Plan Review Details - Permit 08020639
Plan Review Stops For Permit 08020639
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-28 Cont ID  
Sent By jgomez Date 2008-03-28 Time 14:37 Rev Time 0.00
Received By jgomez Date 2008-03-28 Time 14:37 Sent To PC
Notes
2008-03-28 14:39:07BUILDING REVIEW PROVISO:
  
 1- USE ATTACHED COPY FROM THE FAIR HOUSING ACTAS A
 GUIDE FOR GRAB BARS INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-07 Cont ID  
Sent By jgomez Date 2008-03-07 Time 11:14 Rev Time 0.00
Received By jgomez Date 2008-03-07 Time 11:13 Sent To PC
Notes
2008-03-07 11:25:40RESIDENTIAL BATHROOM RENOVATION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-HANDICAP GRAB BARS ARE NOT REQUIREDBY CODE FOR
 THIS TYPE OF OCCUPANCY.HOWEVER, IF INSTALLING GRAB
 BARS, THEN TECHNICAL INFORMATION NEED TO BE PROVIDED TO
 VERIFY COMPLIANCE WITH PROPOSED INSTALLATION.
 SEE ATTACHEDINFORMATION TAKEN FROM THE FAIR HOUSING
 ACT AND CLEARLY SPECIFY GRAB BARS DIMENSIONS,MOUNTING
 HEIGHTS AND HOW IS THE WALL REINFORCED TO RECEIVE THE
 GRAB BARS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH FAIR HOUSING ACT GUIDELINES.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2008-03-25 Cont ID  
Sent By btrobaug Date 2008-03-25 Time 11:09 Rev Time 0.00
Received By btrobaug Date 2008-03-25 Time 11:06 Sent To P
Notes
2008-03-25 11:09:03 
  
 ALL ELECTICAL WORK IS EXISTING PER BILL MARTIN,
 CONTRACTOR./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By btrobaug Date 2008-03-06 Time 09:25 Rev Time 0.00
Received By btrobaug Date 2008-03-06 Time 09:21 Sent To M
Notes
2008-03-06 09:25:05 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2004 FBC AS AMENDED, CHAPTER
 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE LOCATION ON THE
 PLAN
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-24 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 11:18 Sent To I
Notes
2008-03-24 11:18:48TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-07 Cont ID  
Sent By jgomez Date 2008-03-07 Time 11:25 Rev Time 0.00
Received By jgomez Date 2008-02-27 Time 12:51 Sent To  
Notes
2008-02-27 12:55:10TO "P" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-03-25 Cont ID  
Sent By tgordon Date 2008-03-25 Time 14:19 Rev Time 0.20
Received By tgordon Date 2008-03-25 Time 14:19 Sent To B
Notes
2008-03-25 14:20:54EXISTING BATHROOM EXHAUST FAN.
 NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By tgordon Date 2008-03-06 Time 10:24 Rev Time 0.20
Received By tgordon Date 2008-03-06 Time 10:24 Sent To B
Notes
2008-03-06 10:28:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW ON PLAN IF THE BATHROOM HAS A WINDOW OR
 AN EXHAUST FAN TO BE IN COMPLIANCE WITH 2004 FBC/R
 R303.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-03-25 Cont ID  
Sent By mperson Date 2008-03-25 Time 13:24 Rev Time 0.00
Received By mperson Date 2008-03-25 Time 13:24 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-05 Cont ID  
Sent By mperson Date 2008-03-05 Time 11:49 Rev Time 0.00
Received By mperson Date 2008-03-05 Time 11:49 Sent To E
Notes
2008-03-05 11:59:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1.SCOPE OF WORK SERVICES, SPECIFICATIONS STATES BILL
 MARTIN RENOVATIONS, INC. WILL PROVIDE ALL LABOR, TO
 PERFORM THE FOLLOWING WORK. REMOVE OLD TUB AND VANITY,
 REMOVE AND INSTALL NEW DRAIN AND SHOWER PAN, INSTALL
 NEW COPPER PLUMBING TO WALL CONNECTIONS, INSTALL NEW
 HANDICAP WATER CLOSET, VANITY, FAUCET, VALVES AND
 SHOWER FIXTURES. THE ABOVE STATED WORK IS THAT OF A
 PLUMBING CONTRACTOR PER FS 489.105 (3)(M) NOT A GENERAL
 CONTRACTOR AND A PLUMBING PERMIT IS REQUIRED.
 **EXCEPTION** PER FS489.113 QUALIFICATIONS FOR
 PRACTICE; RESTRICTIONS.--(3) A CONTRACTOR SHALL
 SUBCONTRACT ALL PLUMBINGWORK, UNLESS SUCH CONTRACTOR
 HOLDS A STATE CERTIFICATE OR REGISTRATION IN THE
 RESPECTIVE TRADE CATEGORY.
  
 2. CLEARLY INDICATE ALL SCOPE OF PROPOSED PLUMBING
 WORK ON SUBMITTED PLANS. PER CITY OF WPB AMENDMENTS TO
 CHAPTER 1, SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. PROVIDE AN EXISTING FLOOR PLAN LAYOUT OF THE
 BATHROOM PROPOSED TO BE RENOVATED. PER CITY OF WPB
 AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 5. PER FS 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2):
 IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF
 NO FURTHER EFFECT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]