Plan Review Details - Permit 08020636
Plan Review Stops For Permit 08020636
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-08-18 Cont ID  
Sent By shill Date 2008-08-18 Time 15:56 Rev Time 0.00
Received By shill Date 2008-08-18 Time 15:56 Sent To Z
Notes
2008-08-18 16:47:02REVISION DATED 7/28/8 SHEETS A1.1.1, A4.1.0, A4.1.2,
 A4.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-06-10 Cont ID  
Sent By shill Date 2008-06-10 Time 14:38 Rev Time 0.00
Received By shill Date 2008-06-10 Time 14:38 Sent To  
Notes
2008-06-10 14:43:52REVISION SHEETS A1.1.1, A4.1.0, A4.1.1 DATED 5/28/8

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-02 Cont ID  
Sent By shill Date 2008-06-02 Time 12:21 Rev Time 0.00
Received By shill Date 2008-06-02 Time 12:21 Sent To  
Notes
2008-06-02 12:26:26REVISION DATED 4/29/8SHEETS A0.1.1,A4.1.0, A4.1.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-17 Cont ID  
Sent By shill Date 2008-04-17 Time 15:45 Rev Time 0.00
Received By shill Date 2008-04-17 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-04 Cont ID  
Sent By shill Date 2008-04-04 Time 15:15 Rev Time 0.00
Received By shill Date 2008-04-04 Time 15:15 Sent To  
Notes
2008-04-04 15:15:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1-2. INFORMATIONAL OR ADDRESSED.
  
 3. SEE PREVIOUS LIST; SHEET A4.1.1 INDICATES THE USE OF
 ATMS AND DRAWINGS ARE TO BE SUBMITTED BY THE TENANT?S
 SECURITY CONSULTANT.PLEASE REVIEW THE REQUIRMENTS OF
 11-4.34 AUTOMATED TELLER MACHINES (1-5).SUBMIT
 ADDITIONAL INFORMATION INDICATING CODE COMPLIANCE.
  
 THE ARCHITECT?S RESPONSE THAT THE WALK UP ATM IS UNDER
 SEPARATE PERMIT AND THAT THIS ATM IS CAR ACCESS ONLY IS
 NOTED.HOWEVER, DRIVE UP ATMS ARE NOT EXEMPTED FROM
 THE FEDERAL REQUIREMENT OF ACCESSIBILITY; PERSONS WITH
 VISION IMPAIRMENT MAY WISH TO USE THE ATM.PLEASE
 PROVIDE INFORMATION REQUESTED TO SHOW COMPLIANCE WITH
 FBC11-4.34.
  
 4-5. ADDRESSED.
  
 6. THE INFORMATION REQUESTED WAS PROVIDED, BUT I CANNOT
 DETERMINE WHETHER OR NOT THIS COLUMN IS STRUCTURAL
 (SUPPORTING THE BUILDING).PLEASE NOTE ON THE PLAN AS
 THRESHOLD REQUIREMENTS MAY APPLY.
  
 NEW COMMENT:
  
 7.CITY PLACE MANAGEMENT STAMP IS REQUIRED ON THE
 PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By jwitmer Date 2008-02-29 Time 13:17 Rev Time 3.33
Received By jwitmer Date 2008-02-29 Time 13:17 Sent To  
Notes
2008-02-29 15:08:26 
 BUILDING PLAN REVIEW
 PERMIT: 08020636
 ADD: 525 OKEECHOBEE BLVD
 CONT: PASS INTERNATIONAL
 TEL: (954)421-9000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THE PERMIT APPLICATION LIST THE WORK TO BE COMPLETED
 UNDER THIS PERMIT AS 525 OKEECHOBEE BLVD.
 (74-43-43-21-13-003-0020) BUT THE PROJECT IS LOCATED AT
 530 HIBISCUS ST
 (74-43-43-21-13-003-0030) THE B-BLOCK PARKING GARAGE.
 2A) PLEASE CORRECT THE ADDRESS AND PROPERTY CONTROL
 NUMBER ON THE PERMIT APPLICATION.
 2B) PLEASE CORRECT THE TITLEBLOCK AS TO THE LOCATION OF
 THE JOB, IT IS NOT ON OKEECHOBEE BLVD BUT 503 HIBISCUS
 ST.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 XX - STATE PROJECT NAME OR IDENTIFICATION, LOCATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING
 THE
 PLANS
  
 3)SHEET A-4.1.1 INDICATES THE USE OF ATM'S OR
 AUTOMATED TELLER MACHINES AND DRAWINGS ARE TO BE
 SUBMITTED BY THE TENANTS SECURITY CONSULTANT. PLEASE
 REVIEW
 THE REQUIREMENTS OF 11-4.34 AUTOMATED TELLER MACHINES
 (1-5). SUBMIT ADDITIONAL INFORMATION INDICATING CODE
 COMPLIANCE.
  
 4)SHEET A-4.1.1 INDICATES THERE IS A SIGNTO FOR
 VALET ONLY WHERE IS THE DROP OFF ZONE LOCATED? SEE
 11-4.6.6.
  
 5) ON SHEET A-1.1.1 PLEASE INDICATE THE LOCATION OF
 GENERATORS AND THE LOCATION OF FUEL TANKS . 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 6)SHEET A-4.1.1 INDICATES ANEW SECTION ON SHEET
 A-1.1.1 DETAIL 4& 5 WHERE A BEAM AND COLUMN ARE TO BE
 CUT AND DELETED AND A NEW POURED IN PLACE CONCRETE
 COLUMN. THERE IS NO
 INFORMATION ON THIS NEW COLUMN, AS TO SIZE OF REBARS,
 QAUNITY AND OR SIZE OF COLUMN. THIS MAY INACT THRESHOLD
 LAWS SINCE THIS IS A 5 STORY BUILDING. ADDITIONAL
 INFORMATION IS REQUIRED ABOUT
 THIS COLUMN.106.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-07-14 Cont ID  
Sent By dpalmer Date 2008-07-14 Time 10:20 Rev Time 0.00
Received By dpalmer Date 2008-07-14 Time 09:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-05-22 Cont ID  
Sent By dpalmer Date 2008-05-22 Time 16:11 Rev Time 0.00
Received By dpalmer Date 2008-05-22 Time 16:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-05-04 Cont ID  
Sent By dpalmer Date 2008-05-04 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2008-05-04 Time 11:34 Sent To  
Notes
2008-05-04 11:35:06** DENIED**
  
 1) NOTE: PLANS ARE REQUIRED TO CONTAIN *CITY PLACE
 MANAGEMENT* STAMPS. THIS IS REQUIRED PER CITY PLACE.
 PLEASE OBTAIN AND RESUBMIT REVISIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-04-16 Cont ID  
Sent By dpalmer Date 2008-04-16 Time 16:48 Rev Time 0.00
Received By dpalmer Date 2008-04-16 Time 16:47 Sent To  
Notes
2008-04-16 16:49:00CITY PLACE REP CAME INTO OFFICE AND STAMPED ALL SHEETS
 IN THREE SETS WHICH DID NOT CONTAIN REQUIRED STAMPS.
 ELECTRICAL SHEETS WERE STAMPED OK>

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-04-14 Cont ID  
Sent By dpalmer Date 2008-04-14 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2008-04-14 Time 16:38 Sent To  
Notes
2008-04-14 16:38:36** TEMPORARY DENIED REVIEW**
  
 1) NOTE: REVISED AND UPDATED PLANS DO NOT CONTAIN THE
 REQUIRED CITY PLACE MANAGEMENT STAMP.
 PLEASE COMPLETE.
  
 ** PLEASE ALSO SEE ANY OTHER COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE SUBMITTED PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-01 Cont ID  
Sent By dpalmer Date 2008-04-01 Time 09:01 Rev Time 0.00
Received By dpalmer Date 2008-04-01 Time 09:01 Sent To  
Notes
2008-04-01 09:01:42** DENIED**
  
  
 1) NOTE: PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF COMPLETING.
 PLEASE SEE THAT ALL CIRCUITING NEEDS TO BE COMPLETE AND
 COORDINATE WITH THE PANEL SCHEDULES SUBMITTED OR TO BE
 SUBMITTED.
 FOR EXAMPLE: PLEASE SEE PLANS NOTE CIRCUIT 34 ON PANEL
 PH, YET NO PANEL PH WAS SUBMITTED.
 PLEASE SEE SHEET E2.1.2, THIS SHEET ALSO NOTES THE SAME
 *D* FIXTURES TO BE CONTINUED ON E2.1.1, HOWEVER WHEN
 YOU LOOK AT THE OTHER SHEET THE *D* FIXTURES ARE ON
 PANEL PH-2. PLEASE SEE THE LOAD ON THIS CIRCUIT IS
 SHOWN HIGHER THAN THE LOAD FOR THE THREE *D* FIXTURES
 SHOWN.
 PLEASE SEE THE FIXTURES WHICH ARE NOTED TO GO TO
 EXISTING EMERGENCY CIRCUIT DOES NOT INCLUDE LOAD,
 CIRCUIT, PANEL, LOCATION ETC?
  
 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND. FOR EXAMPLE:
 FIXTURE *B* WHICH DOES NOT SHOW ANY WATTAGE FOR BULB TO
 BE USED. LOAD CAN NOT BE DETERMINED FOR THIS CIRCUIT.
 ALMOST ALL LIGHTING IN DRIVE-THRU AREA IS SHOWN ON ONE
 CIRCUIT AND WITH OUT THIS INFORMATION THE CIRCUIT
 SIZING CAN NOT BE DETERMINED.
 THIS FIXTURE WAS LOOKED UP ON THE COMPANY?S WEB-SITE
 AND THIS FIXTURE HAS A WIDE RANGE OF WATTAGE. IF USING
 SOME OF THE HIGHER WATTAGE OF BULBS, THIS WOULD OVER
 LOAD THE CIRCUIT.
 PLEASE COMPLETE.
 NEC 220, 240.4, 310.16, ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE COMPLETE THE LOCATIONS OF NEW
 EQUIPMENT. PLEASE SEE THE ELECTRICAL ROOM AS SHOWN
 SHOWS TWO -2 TRANSFORMERS AND BOTH ARE SHOWN AS
 EXISTING. PLEASE ALSO SEE OTHER EQUIPMENT ON PLANS ALSO
 SHOWS OTHER EQUIPMENT AS EXISTING ALSO.
 PLEASE CLEARLY LABEL ALL EQUIPMENT AND SHOW LOCATIONS.
 110.26, 240.24, ETC
 FBC 106.1.2
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-25 Cont ID  
Sent By dpalmer Date 2008-03-25 Time 16:19 Rev Time 0.00
Received By dpalmer Date 2008-03-25 Time   Sent To PC
Notes
2008-03-25 16:19:26*** NO REVIEW DONE, THE NOTE BELOW IS THE NOTE PLACED
 IN FRONT SCREEN OF THIS PERMIT NUMBER.
  
  
  
  
 3/25/08 PLANS REMOVED FROM PROCESSING AND PLACED
 OUTFRONT FOR ALL OLD/VOIDED SHEETS TO BE REMOVED AND TO
 SUBMIT TWO COMPLETE SETS WITH NO OLD PLANS. NEEDS
 PERMIT APPLICATION TO BE REVISED ALONG WITH RESUB SHEET
 AS PROJECT IS ACTUALLY LOCATED AT 530 HIBISCUS
 ST.CALLED AND LEFT MESSAGE ON PERMIT EXPEDITOR'S CELL
 VM ON WHAT IS NEEDED. DV PALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 20:06 Sent To  
Notes
2008-03-04 20:06:18** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE LOCATION IN WHICH THE SCOPE OF
 WORK HAS BEEN APPLIED FOR IS NOT CORRECT. THE LOCATION
 FOR SCOPE OF WORK IS 530 HIBISCUS. PERMIT APPLICATION
 SUBMITTED SHOWS 525 OKEECHOBEE BLVD ANDBASED ON THE
 PCN PLACED ON PERMIT APPLICATION AND AS APPLIED IN OUR
 SYSTEM THE APPLIED ADDRESS WAS 550 S. ROSEMARY
 PLEASE ADJUST PERMIT APPLICATION AND WHEN RESUBMITTING
 PLANS PLEASE BE SURE TO LET THE PERMIT COUNTER
 TECHNICIAN KNOW SO THAT ALL RELEVANT INFORMATION IN THE
 SYSTEM MAY BE CHANGED ACCORDINGLY. THIS WILL BE NOTED
 IN OTHER TRADE REVIEWS.
 PLEASE BE SURE ALL TITLE BLOCKS ON PLANS ARE ALSO
 ADJUSTED.
 FBC 106.5, FAC 61G1-16.004 ETC
  
 2) NOTE: PLANS ARE NOT COMPLETE AT THIS TIME FOR REVIEW
 OF APPLIED SCOPE OF WORK. PLEASE SEE THE FOLLOWING
 ITEMS.
 A) NO PANEL SCHEDULES WERE SUBMITTED. SIZE OF PANELS,
 LOADS ON PANELS EXISTING AND NEW ETC
 B) NO OVER CURRENT PROTECTION OF CIRCUITS WAS SHOWN
 C) STAIR TOWERS SHOW NEW FIXTURES WITH NO CIRCUITING
 FOR EMERGENCY AND EXIT LIGHTS
 D) PLEASE COMPLETE ALL CIRCUITING.
 408.4, 310.16, 220, 240.4, ETC
  
 3) NOTE: PLEASE SEE NO LIGHTING PERFORMANCE
 CALCULATIONS FOR EXISTING AREA LIGHTING IN ORDER FOR
 ALLOWANCE OF NEW LIGHTING PER 13-415.2.
 PLEASE SUBMIT LIGHTING FIXTURE LEGEND AND COORDINATE
 WITH PLANS.
  
 4) NOTE: PLANS DO NOT SHOW ANY LIGHTING CONTROLS
 REQUIRED PER 13-415.1.ABC.1.4
  
 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR LIGHTING
 LEVELS AS REQUIRED UNDER FLORIDA STATUES FOR ATM
 LOCATIONS AND OTHER LIGHTING REQUIRED.
 FS 655.962.
  
 6) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIRS FOR
 MINIMUM COMPLIANCE WITH NFPA-101 2003 7.8.1.3, 7.9.2.2
  
 *** PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS
 NOT ON PLANS FOR REVIEW AND THERE MAY VERY WELL BE NEW
 COMMENTS ONCE PLANS ARE SUBMITTED COMPLETED FOR
 REVIEW.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-06-04 Cont ID  
Sent By mwennerg Date 2008-06-04 Time 13:02 Rev Time 0.00
Received By mwennerg Date 2008-06-04 Time 13:02 Sent To  
Notes
2008-06-04 13:03:28REVISION DATED 4/29/08 STAMPED SHEET A0.1.1

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-03 Cont ID  
Sent By mawillia Date 2008-04-03 Time 13:46 Rev Time 0.00
Received By mawillia Date 2008-04-03 Time 13:29 Sent To  
Notes
2008-04-03 13:38:26*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET A-4.1.0 STAMPED, INITIALED,
 AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-12 Cont ID  
Sent By mawillia Date 2008-03-12 Time 14:41 Rev Time 0.00
Received By mawillia Date 2008-03-12 Time 14:05 Sent To  
Notes
2008-03-12 14:38:54*****DENIED*****
  
  
 1.THE ADDRESS OF THE SCOPE OF WORK SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 13:56 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 13:56 Sent To B
Notes
2008-07-30 13:56:52TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 16:47 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 16:47 Sent To E
Notes
2008-06-09 16:47:35TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 10:54 Sent To B
Notes
2008-06-03 10:55:11TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 10:12 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 10:12 Sent To  
Notes
2008-05-15 10:12:22TO "COMM" BD#62

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 11:36 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 11:36 Sent To  
Notes
2008-05-02 11:39:02TO "COMM" BD#27--PLANS PULLED FROM REVIEW PER CUSTOMER.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 10:54 Sent To  
Notes
2008-04-11 10:59:47TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 09:26 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 09:26 Sent To  
Notes
2008-03-27 09:26:36PLANS BACK IN FOR REVIEW--TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-24 Time 11:29 Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 11:28 Sent To  
Notes
2008-03-24 11:33:33TO "COMM" BD#25--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-12 Cont ID  
Sent By mawillia Date 2008-03-12 Time 14:05 Rev Time 0.00
Received By mawillia Date 2008-02-27 Time 15:46 Sent To  
Notes
2008-02-27 15:46:38TO "COMM" BD#46

Review Stop Z ZONING
Rev No 6 Status P Date 2008-08-21 Cont ID  
Sent By eschneid Date 2008-08-21 Time 17:25 Rev Time 0.00
Received By eschneid Date 2008-08-21 Time 17:25 Sent To B
Notes
2008-08-21 17:27:37PASSED W/PROVISO
  
 THE DRIVE AISLE SHALL BE 24 FEET IN WIDTH AND THE
 EASTERN ROW OF PARKING SPACES SHALL BE STRIPED AT 16
 FEET DEEP AND MARKED "COMPACT."

Review Stop Z ZONING
Rev No 5 Status P Date 2008-05-20 Cont ID  
Sent By eschneid Date 2008-05-20 Time 13:14 Rev Time 0.00
Received By eschneid Date 2008-05-20 Time 13:14 Sent To  
Notes
2008-05-20 13:15:10RE-STAMP

Review Stop Z ZONING
Rev No 4 Status F Date 2008-05-05 Cont ID  
Sent By eschneid Date 2008-05-05 Time 17:42 Rev Time 0.00
Received By eschneid Date 2008-05-05 Time 17:41 Sent To  
Notes
2008-05-05 17:41:51FAILED - CITYPLACE STAMP REQUIRED.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By eschneid Date 2008-04-15 Time 15:46 Rev Time 0.00
Received By eschneid Date 2008-04-15 Time 15:46 Sent To  
Notes
2008-04-15 15:46:59PASSED - RESTAMP 2 SHEETS.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-27 Cont ID  
Sent By eschneid Date 2008-03-27 Time 17:52 Rev Time 0.00
Received By eschneid Date 2008-03-27 Time 17:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-05 Cont ID  
Sent By eschneid Date 2008-03-03 Time 11:12 Rev Time 0.00
Received By eschneid Date 2008-03-03 Time 11:12 Sent To  
Notes
2008-03-03 11:17:40PASSED W/PROVISOS
  
 1) A LANDSCAPE PLAN SHOWING WHAT WILL GO IN THE
 PLANTERS SHALL BE SUBMITTED AS A REVISION, OR AS A
 SEPARATE PERMIT.
  
 2) THE SOUTHEASTERN MOST PARKING SPACE IS REQUIRED TO
 BE STRIPED AS A TURN AROUND AREA.THIS SHALL BE SHOWN
 IF PLANS ARE RESUBMITTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.