Plan Review Stops For Permit 08020636 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-08-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-08-18 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-08-18 |
Time |
15:56 |
Sent To |
Z |
|
Notes |
2008-08-18 16:47:02 | REVISION DATED 7/28/8 SHEETS A1.1.1, A4.1.0, A4.1.2, | | A4.2.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-06-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-06-10 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-06-10 |
Time |
14:38 |
Sent To |
|
|
Notes |
2008-06-10 14:43:52 | REVISION SHEETS A1.1.1, A4.1.0, A4.1.1 DATED 5/28/8 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-06-02 |
Time |
12:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-06-02 |
Time |
12:21 |
Sent To |
|
|
Notes |
2008-06-02 12:26:26 | REVISION DATED 4/29/8SHEETS A0.1.1,A4.1.0, A4.1.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-04-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-04-17 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-04-17 |
Time |
15:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-04-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-04-04 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-04-04 |
Time |
15:15 |
Sent To |
|
|
Notes |
2008-04-04 15:15:36 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1-2. INFORMATIONAL OR ADDRESSED. | | | | 3. SEE PREVIOUS LIST; SHEET A4.1.1 INDICATES THE USE OF | | ATMS AND DRAWINGS ARE TO BE SUBMITTED BY THE TENANT?S | | SECURITY CONSULTANT.PLEASE REVIEW THE REQUIRMENTS OF | | 11-4.34 AUTOMATED TELLER MACHINES (1-5).SUBMIT | | ADDITIONAL INFORMATION INDICATING CODE COMPLIANCE. | | | | THE ARCHITECT?S RESPONSE THAT THE WALK UP ATM IS UNDER | | SEPARATE PERMIT AND THAT THIS ATM IS CAR ACCESS ONLY IS | | NOTED.HOWEVER, DRIVE UP ATMS ARE NOT EXEMPTED FROM | | THE FEDERAL REQUIREMENT OF ACCESSIBILITY; PERSONS WITH | | VISION IMPAIRMENT MAY WISH TO USE THE ATM.PLEASE | | PROVIDE INFORMATION REQUESTED TO SHOW COMPLIANCE WITH | | FBC11-4.34. | | | | 4-5. ADDRESSED. | | | | 6. THE INFORMATION REQUESTED WAS PROVIDED, BUT I CANNOT | | DETERMINE WHETHER OR NOT THIS COLUMN IS STRUCTURAL | | (SUPPORTING THE BUILDING).PLEASE NOTE ON THE PLAN AS | | THRESHOLD REQUIREMENTS MAY APPLY. | | | | NEW COMMENT: | | | | 7.CITY PLACE MANAGEMENT STAMP IS REQUIRED ON THE | | PLAN. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-02-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-02-29 |
Time |
13:17 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2008-02-29 |
Time |
13:17 |
Sent To |
|
|
Notes |
2008-02-29 15:08:26 | | | BUILDING PLAN REVIEW | | PERMIT: 08020636 | | ADD: 525 OKEECHOBEE BLVD | | CONT: PASS INTERNATIONAL | | TEL: (954)421-9000 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A | | RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD | | BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE | | SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT | | ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM | | BEACH ADMINISTRATIVE CODE. | | | | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN | | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY | | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE | | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS | | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. | | | | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE2007 SUPPLEMENTS. | | | | 2) THE PERMIT APPLICATION LIST THE WORK TO BE COMPLETED | | UNDER THIS PERMIT AS 525 OKEECHOBEE BLVD. | | (74-43-43-21-13-003-0020) BUT THE PROJECT IS LOCATED AT | | 530 HIBISCUS ST | | (74-43-43-21-13-003-0030) THE B-BLOCK PARKING GARAGE. | | 2A) PLEASE CORRECT THE ADDRESS AND PROPERTY CONTROL | | NUMBER ON THE PERMIT APPLICATION. | | 2B) PLEASE CORRECT THE TITLEBLOCK AS TO THE LOCATION OF | | THE JOB, IT IS NOT ON OKEECHOBEE BLVD BUT 503 HIBISCUS | | ST. | | 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A | | REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH | | MUST: | | - STATE THE FIRM NAME, ADDRESS AND TELEPHONE | | NUMBER | | - STATE THE FIRM LICENSE NUMBER | | XX - STATE PROJECT NAME OR IDENTIFICATION, LOCATION | | - STATE DATE PREPARED | | - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL | | - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING | | THE | | PLANS | | | | 3)SHEET A-4.1.1 INDICATES THE USE OF ATM'S OR | | AUTOMATED TELLER MACHINES AND DRAWINGS ARE TO BE | | SUBMITTED BY THE TENANTS SECURITY CONSULTANT. PLEASE | | REVIEW | | THE REQUIREMENTS OF 11-4.34 AUTOMATED TELLER MACHINES | | (1-5). SUBMIT ADDITIONAL INFORMATION INDICATING CODE | | COMPLIANCE. | | | | 4)SHEET A-4.1.1 INDICATES THERE IS A SIGNTO FOR | | VALET ONLY WHERE IS THE DROP OFF ZONE LOCATED? SEE | | 11-4.6.6. | | | | 5) ON SHEET A-1.1.1 PLEASE INDICATE THE LOCATION OF | | GENERATORS AND THE LOCATION OF FUEL TANKS . 106.1.2 | | ADDITIONAL INFORMATION REQUIRED. | | | | 6)SHEET A-4.1.1 INDICATES ANEW SECTION ON SHEET | | A-1.1.1 DETAIL 4& 5 WHERE A BEAM AND COLUMN ARE TO BE | | CUT AND DELETED AND A NEW POURED IN PLACE CONCRETE | | COLUMN. THERE IS NO | | INFORMATION ON THIS NEW COLUMN, AS TO SIZE OF REBARS, | | QAUNITY AND OR SIZE OF COLUMN. THIS MAY INACT THRESHOLD | | LAWS SINCE THIS IS A 5 STORY BUILDING. ADDITIONAL | | INFORMATION IS REQUIRED ABOUT | | THIS COLUMN.106.1.2. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2008-07-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-14 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-14 |
Time |
09:52 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2008-05-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-05-22 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-22 |
Time |
16:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2008-05-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-05-04 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-04 |
Time |
11:34 |
Sent To |
|
|
Notes |
2008-05-04 11:35:06 | ** DENIED** | | | | 1) NOTE: PLANS ARE REQUIRED TO CONTAIN *CITY PLACE | | MANAGEMENT* STAMPS. THIS IS REQUIRED PER CITY PLACE. | | PLEASE OBTAIN AND RESUBMIT REVISIONS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2008-04-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-04-16 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-04-16 |
Time |
16:47 |
Sent To |
|
|
Notes |
2008-04-16 16:49:00 | CITY PLACE REP CAME INTO OFFICE AND STAMPED ALL SHEETS | | IN THREE SETS WHICH DID NOT CONTAIN REQUIRED STAMPS. | | ELECTRICAL SHEETS WERE STAMPED OK> |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2008-04-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-04-14 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-04-14 |
Time |
16:38 |
Sent To |
|
|
Notes |
2008-04-14 16:38:36 | ** TEMPORARY DENIED REVIEW** | | | | 1) NOTE: REVISED AND UPDATED PLANS DO NOT CONTAIN THE | | REQUIRED CITY PLACE MANAGEMENT STAMP. | | PLEASE COMPLETE. | | | | ** PLEASE ALSO SEE ANY OTHER COMMENTS FROM OTHER TRADES | | WHICH MAY AFFECT THE SUBMITTED PLANS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-04-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-04-01 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-04-01 |
Time |
09:01 |
Sent To |
|
|
Notes |
2008-04-01 09:01:42 | ** DENIED** | | | | | | 1) NOTE: PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE | | STILL IN NEED OF COMPLETING. | | PLEASE SEE THAT ALL CIRCUITING NEEDS TO BE COMPLETE AND | | COORDINATE WITH THE PANEL SCHEDULES SUBMITTED OR TO BE | | SUBMITTED. | | FOR EXAMPLE: PLEASE SEE PLANS NOTE CIRCUIT 34 ON PANEL | | PH, YET NO PANEL PH WAS SUBMITTED. | | PLEASE SEE SHEET E2.1.2, THIS SHEET ALSO NOTES THE SAME | | *D* FIXTURES TO BE CONTINUED ON E2.1.1, HOWEVER WHEN | | YOU LOOK AT THE OTHER SHEET THE *D* FIXTURES ARE ON | | PANEL PH-2. PLEASE SEE THE LOAD ON THIS CIRCUIT IS | | SHOWN HIGHER THAN THE LOAD FOR THE THREE *D* FIXTURES | | SHOWN. | | PLEASE SEE THE FIXTURES WHICH ARE NOTED TO GO TO | | EXISTING EMERGENCY CIRCUIT DOES NOT INCLUDE LOAD, | | CIRCUIT, PANEL, LOCATION ETC? | | | | 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND. FOR EXAMPLE: | | FIXTURE *B* WHICH DOES NOT SHOW ANY WATTAGE FOR BULB TO | | BE USED. LOAD CAN NOT BE DETERMINED FOR THIS CIRCUIT. | | ALMOST ALL LIGHTING IN DRIVE-THRU AREA IS SHOWN ON ONE | | CIRCUIT AND WITH OUT THIS INFORMATION THE CIRCUIT | | SIZING CAN NOT BE DETERMINED. | | THIS FIXTURE WAS LOOKED UP ON THE COMPANY?S WEB-SITE | | AND THIS FIXTURE HAS A WIDE RANGE OF WATTAGE. IF USING | | SOME OF THE HIGHER WATTAGE OF BULBS, THIS WOULD OVER | | LOAD THE CIRCUIT. | | PLEASE COMPLETE. | | NEC 220, 240.4, 310.16, ETC | | FBC 106.1.2 | | | | 3) NOTE: PLEASE COMPLETE THE LOCATIONS OF NEW | | EQUIPMENT. PLEASE SEE THE ELECTRICAL ROOM AS SHOWN | | SHOWS TWO -2 TRANSFORMERS AND BOTH ARE SHOWN AS | | EXISTING. PLEASE ALSO SEE OTHER EQUIPMENT ON PLANS ALSO | | SHOWS OTHER EQUIPMENT AS EXISTING ALSO. | | PLEASE CLEARLY LABEL ALL EQUIPMENT AND SHOW LOCATIONS. | | 110.26, 240.24, ETC | | FBC 106.1.2 | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-03-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-25 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-25 |
Time |
|
Sent To |
PC |
|
Notes |
2008-03-25 16:19:26 | *** NO REVIEW DONE, THE NOTE BELOW IS THE NOTE PLACED | | IN FRONT SCREEN OF THIS PERMIT NUMBER. | | | | | | | | | | 3/25/08 PLANS REMOVED FROM PROCESSING AND PLACED | | OUTFRONT FOR ALL OLD/VOIDED SHEETS TO BE REMOVED AND TO | | SUBMIT TWO COMPLETE SETS WITH NO OLD PLANS. NEEDS | | PERMIT APPLICATION TO BE REVISED ALONG WITH RESUB SHEET | | AS PROJECT IS ACTUALLY LOCATED AT 530 HIBISCUS | | ST.CALLED AND LEFT MESSAGE ON PERMIT EXPEDITOR'S CELL | | VM ON WHAT IS NEEDED. DV PALMER |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-03-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
20:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-04 |
Time |
20:06 |
Sent To |
|
|
Notes |
2008-03-04 20:06:18 | ** DENIEDREVIEW ** | | | | 1) NOTE: PLEASE SEE THE LOCATION IN WHICH THE SCOPE OF | | WORK HAS BEEN APPLIED FOR IS NOT CORRECT. THE LOCATION | | FOR SCOPE OF WORK IS 530 HIBISCUS. PERMIT APPLICATION | | SUBMITTED SHOWS 525 OKEECHOBEE BLVD ANDBASED ON THE | | PCN PLACED ON PERMIT APPLICATION AND AS APPLIED IN OUR | | SYSTEM THE APPLIED ADDRESS WAS 550 S. ROSEMARY | | PLEASE ADJUST PERMIT APPLICATION AND WHEN RESUBMITTING | | PLANS PLEASE BE SURE TO LET THE PERMIT COUNTER | | TECHNICIAN KNOW SO THAT ALL RELEVANT INFORMATION IN THE | | SYSTEM MAY BE CHANGED ACCORDINGLY. THIS WILL BE NOTED | | IN OTHER TRADE REVIEWS. | | PLEASE BE SURE ALL TITLE BLOCKS ON PLANS ARE ALSO | | ADJUSTED. | | FBC 106.5, FAC 61G1-16.004 ETC | | | | 2) NOTE: PLANS ARE NOT COMPLETE AT THIS TIME FOR REVIEW | | OF APPLIED SCOPE OF WORK. PLEASE SEE THE FOLLOWING | | ITEMS. | | A) NO PANEL SCHEDULES WERE SUBMITTED. SIZE OF PANELS, | | LOADS ON PANELS EXISTING AND NEW ETC | | B) NO OVER CURRENT PROTECTION OF CIRCUITS WAS SHOWN | | C) STAIR TOWERS SHOW NEW FIXTURES WITH NO CIRCUITING | | FOR EMERGENCY AND EXIT LIGHTS | | D) PLEASE COMPLETE ALL CIRCUITING. | | 408.4, 310.16, 220, 240.4, ETC | | | | 3) NOTE: PLEASE SEE NO LIGHTING PERFORMANCE | | CALCULATIONS FOR EXISTING AREA LIGHTING IN ORDER FOR | | ALLOWANCE OF NEW LIGHTING PER 13-415.2. | | PLEASE SUBMIT LIGHTING FIXTURE LEGEND AND COORDINATE | | WITH PLANS. | | | | 4) NOTE: PLANS DO NOT SHOW ANY LIGHTING CONTROLS | | REQUIRED PER 13-415.1.ABC.1.4 | | | | 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR LIGHTING | | LEVELS AS REQUIRED UNDER FLORIDA STATUES FOR ATM | | LOCATIONS AND OTHER LIGHTING REQUIRED. | | FS 655.962. | | | | 6) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIRS FOR | | MINIMUM COMPLIANCE WITH NFPA-101 2003 7.8.1.3, 7.9.2.2 | | | | *** PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS | | NOT ON PLANS FOR REVIEW AND THERE MAY VERY WELL BE NEW | | COMMENTS ONCE PLANS ARE SUBMITTED COMPLETED FOR | | REVIEW. | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-06-04 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-06-04 |
Time |
13:02 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-06-04 |
Time |
13:02 |
Sent To |
|
|
Notes |
2008-06-04 13:03:28 | REVISION DATED 4/29/08 STAMPED SHEET A0.1.1 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-04-03 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-04-03 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-04-03 |
Time |
13:29 |
Sent To |
|
|
Notes |
2008-04-03 13:38:26 | *****APPROVED***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED;PLAN SHEET A-4.1.0 STAMPED, INITIALED, | | AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-03-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-12 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-12 |
Time |
14:05 |
Sent To |
|
|
Notes |
2008-03-12 14:38:54 | *****DENIED***** | | | | | | 1.THE ADDRESS OF THE SCOPE OF WORK SITE SHALL BE IN | | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL | | DISTANCE. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2008-07-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-30 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-30 |
Time |
13:56 |
Sent To |
B |
|
Notes |
2008-07-30 13:56:52 | TO "SHILL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2008-06-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-09 |
Time |
16:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-09 |
Time |
16:47 |
Sent To |
E |
|
Notes |
2008-06-09 16:47:35 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-06-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-03 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-03 |
Time |
10:54 |
Sent To |
B |
|
Notes |
2008-06-03 10:55:11 | TO "SHILL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-05-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-15 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-15 |
Time |
10:12 |
Sent To |
|
|
Notes |
2008-05-15 10:12:22 | TO "COMM" BD#62 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-02 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-02 |
Time |
11:36 |
Sent To |
|
|
Notes |
2008-05-02 11:39:02 | TO "COMM" BD#27--PLANS PULLED FROM REVIEW PER CUSTOMER. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-04-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-11 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-11 |
Time |
10:54 |
Sent To |
|
|
Notes |
2008-04-11 10:59:47 | TO "COMM" BD#24 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-03-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-27 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-27 |
Time |
09:26 |
Sent To |
|
|
Notes |
2008-03-27 09:26:36 | PLANS BACK IN FOR REVIEW--TO "COMM" BD#48 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-03-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-24 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-24 |
Time |
11:28 |
Sent To |
|
|
Notes |
2008-03-24 11:33:33 | TO "COMM" BD#25--EXPEDITED-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-03-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-12 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-02-27 |
Time |
15:46 |
Sent To |
|
|
Notes |
2008-02-27 15:46:38 | TO "COMM" BD#46 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
6 |
Status |
P |
Date |
2008-08-21 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-08-21 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-08-21 |
Time |
17:25 |
Sent To |
B |
|
Notes |
2008-08-21 17:27:37 | PASSED W/PROVISO | | | | THE DRIVE AISLE SHALL BE 24 FEET IN WIDTH AND THE | | EASTERN ROW OF PARKING SPACES SHALL BE STRIPED AT 16 | | FEET DEEP AND MARKED "COMPACT." |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2008-05-20 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-05-20 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-05-20 |
Time |
13:14 |
Sent To |
|
|
Notes |
2008-05-20 13:15:10 | RE-STAMP |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-05-05 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-05-05 |
Time |
17:41 |
Sent To |
|
|
Notes |
2008-05-05 17:41:51 | FAILED - CITYPLACE STAMP REQUIRED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-04-15 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-04-15 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-04-15 |
Time |
15:46 |
Sent To |
|
|
Notes |
2008-04-15 15:46:59 | PASSED - RESTAMP 2 SHEETS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2008-03-27 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-03-27 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-03-27 |
Time |
17:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-03-03 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-03-03 |
Time |
11:12 |
Sent To |
|
|
Notes |
2008-03-03 11:17:40 | PASSED W/PROVISOS | | | | 1) A LANDSCAPE PLAN SHOWING WHAT WILL GO IN THE | | PLANTERS SHALL BE SUBMITTED AS A REVISION, OR AS A | | SEPARATE PERMIT. | | | | 2) THE SOUTHEASTERN MOST PARKING SPACE IS REQUIRED TO | | BE STRIPED AS A TURN AROUND AREA.THIS SHALL BE SHOWN | | IF PLANS ARE RESUBMITTED. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|