Plan Review Details - Permit 08020629
Plan Review Stops For Permit 08020629
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-05-27 Cont ID  
Sent By rmcdouga Date 2009-05-27 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2009-05-27 Time 11:16 Sent To  
Notes
2009-05-27 11:17:10TRUSS DRAWINGS WERE SUBMITTED AND REVIEWED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-04-23 Cont ID  
Sent By rmcdouga Date 2009-04-23 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2009-04-23 Time 10:55 Sent To  
Notes
2009-04-23 10:59:31TRUSS SUBMITTAL DENIED
  
 1) TRUSS DRAWINGS SUBMITTED ARE FOR TWO STORY ADDITION.
 THE REVISION THAT WAS APPROVED WAS TO CONVERT THE
 ADDITION TO ONE STORY.
  
 2) TWO COPIES ARE REQUIRED.
  
 3) THE ARCHITECT OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE TRUSS DRAWINGS. (SHOP DRAWING REVIEW).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-04-06 Cont ID  
Sent By rmcdouga Date 2009-04-06 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2009-04-06 Time 10:25 Sent To  
Notes
2009-04-06 10:37:53REVISED ADDITION FROM TWO STORY TO ONE STORY (4 REVISED
 PLAN SHEETS)
  
 BUILDING PROVISO
  
 1) SUBMIT TWO (2) COPIES OF PRODUCT APPROVALS FOR THE
 FLAT ROOF. SPECIFY THE APPROVED ASSEMBLY, FASTENING
 OPTION AND DESIGN PRESSURE FOR THE SYSTEM THAT WILL BE
 INSTALLED. SUBMIT RAS 117 CALCULATIONS FOR THE ENHANCED
 FASTENING AT THE CORNER AND PERIMETER AREAS. FAC RULE
 9B-72
  
 2) SUBMIT (2) COPIES REVISED ENERGY CALCULATIONS FOR
 THE REVISION TO A ONE STORY ADDITION.
  
 3) SUBMIT SIGNED AND SEALED REVISED TRUSS DRAWINGS FOR
 THE FLAT ROOF THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE ADDITION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-02-09 Cont ID  
Sent By rmcdouga Date 2009-02-03 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2009-02-03 Time 14:35 Sent To  
Notes
2009-02-09 16:13:44ZONING COMMENTS MUST BE ADDRESSED BEFORE REVISION CAN
 BE APPROVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-16 Cont ID  
Sent By rmcdouga Date 2008-10-16 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2008-10-16 Time 08:16 Sent To  
Notes
2008-10-16 08:17:38PROCESS PLANS AFTER LANDSCAPE REVIEW WAS COMPLETED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-14 Cont ID  
Sent By rmcdouga Date 2008-10-14 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2008-10-14 Time 10:25 Sent To L
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-18 Cont ID  
Sent By rmcdouga Date 2008-08-18 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2008-08-18 Time 09:06 Sent To Z
Notes
2008-08-18 10:05:272004FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION AND ADDITION
  
 DENIED BY BUILDING
  
 1) THE NOTICE OF COMMENCEMENT IS REQUIRED TO BE
 RECORDED AT THE COUNTY COURTHOUSE. A COPY OF THE
 RECORDED NOC WILL BE REQUIRED. FS 713
  
 2) SUBMIT A KEY PLAN INDICATING THE LOCATIONS OF THE
 OPENINGS LISTED ON THE STORM PANEL SCHEDULE. THE STORM
 PANEL SCHEDULE IS INCORRECTAND INCOMPLETE. THE
 CONNECTION TYPES ARE C1,C2,C3,C4 AND C5. FOR MINIMUM
 GLASS SEPARATION SEE TABLE 2 ON SHEET 4 OF THE PRODUCT
 APPROVAL NOA. IF THE HEIGHT OF THE WINDOW IS 52"AND
 THE PANELS ARE INSTALLED VERTICAL THE SPAN IS 56" NOT
 37".SPECIFY THE TOP AND BOTTOM ANCHOR SPACING.
 SPECIFY THE SUBSTRATE TO WHICH THE ANCHORS WILL BE
 ATTACHED.
 FBC R301.2.1.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By rmcdouga Date 2008-03-10 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2008-03-07 Time 16:44 Sent To  
Notes
2008-03-10 10:52:372004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATIONS AND ADDITION
  
 DENIED BY BUILDING
  
 1) A COPY OF THE RECORDED NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SURVEY/SITE PLAN SPECIFYING THE DISTANCES
 OF THE ADDITION TO PROPERTY LINES.
  
 4) IF LESS THAN 6 FEET TO THE PROPERTY LINES, THE SITE
 PLAN WILL NEED TO SPECIFY THAT THE DISTANCE TO ANY
 STRUCTURES ON THE ADJACENT PROPERTY IS MORE THAN 6 FEET
 OR SHOW COMPLIANCE WITH R302.1 AND R302.2. R302.1
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. R302.2 OPENINGS SHALL
 NOT BE PERMITTED IN THE EXTERIOR WALL OF A DWELLING OR
 ACCESSORY BUILDING THAT IS SEPARATED FROM AN ADJACENT
 BUILDING BY A DISTANCE OF LESS THAN 6 FEET (1828 MM).
 THIS DISTANCE SHALL BE MEASURED PERPENDICULAR TO THE
 LINE USED TO DETERMINE THE SEPARATION DISTANCE.
  
 5) THE DESIGN DATA ON SHEET 1 INCORRECTLY SPECIFIES
 ASCE 7-98. THE EDITION REFERENCED BY THE 2004 FBC IS
 ASCE 7-02. PLEASE CORRECT.
  
 6) THE ROOF PITCH ON SHEET 1 SPECIFIES A FLAT ROOF AND
 THE PLANS INDICATE A SLOPED ROOF. SPECIFY THE ROOF
 SLOPE ON THE PLANS. FBC 106.1.1* CITY AMENDMENTS.
  
 7) SPECIFY THE REQUIRED SOIL BEARING CAPACITY OF THE
 SOIL ON THE PLANS. FBC 106.1.1* CITY AMENDMENTS.
  
 8) REVISE THE ROOF SHEATHING FASTENING NOTES ON THE
 TYPICAL WALL SECTION ON SHEET 5 TO COMPLY WITH
 R803.2.3.1 WHICH REQUIRES 8D RING-SHANK NAILS.
  
 9) SUBMIT TWO (2) COPIES OF THE PRODUCT APPROVALS
 REQUIRED BY DCA RULE 9B-72. FBC 106.1* CITY
 AMENDMENTS.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW
 MULLIONS. DCA RULE 9B-72.
  
 11)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 12) THE PRESSURES SPECIFIED IN THE NOA FOR THE SINGLE
 HUNG WINDOWS WITH DSB ANNEALED GLASS ARE TOO LOW FOR
 THE SH34 WINDOWS. ONE OF THE OTHER TYPE OF GLAZING
 LISTED IN THE CHART ON PAGE 1 OF THE NOA MUST BE USED.
  
 13)SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 FASTENER TYPE AND SPACING, EDGE DISTANCE, GLASS
 SEPARATION, ETC. SEE SAMPLE OF SCHEDULE ATTACHED. FBC
 106.1.1* CITY AMENDMENTS.
  
 14) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORMS. SUBMIT TWO COPIES OF ENERGY CALCS.
 FBC 13-600.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-03-24 Cont ID  
Sent By btrobaug Date 2009-03-24 Time 10:07 Rev Time 0.00
Received By btrobaug Date 2009-03-24 Time 09:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-01-27 Cont ID  
Sent By btrobaug Date 2009-01-27 Time 14:42 Rev Time 0.00
Received By btrobaug Date 2009-01-27 Time 13:55 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-07 Cont ID  
Sent By btrobaug Date 2008-10-07 Time 16:10 Rev Time 0.00
Received By btrobaug Date 2008-10-07 Time 16:04 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-08-05 Cont ID  
Sent By btrobaug Date 2008-08-05 Time 12:14 Rev Time 0.00
Received By btrobaug Date 2008-08-05 Time 11:30 Sent To M
Notes
2008-08-05 12:14:48 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} ONE NEW DRAWING AND ONE OLD (FAILED) DRAWING OF
 SHEET 3-5 WAS SUBMITTED FOR REVIEW.106.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By btrobaug Date 2008-02-29 Time 13:07 Rev Time 0.00
Received By btrobaug Date 2008-02-29 Time 06:54 Sent To M
Notes
2008-02-29 12:41:38 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 ALL COMMENTS REFER TO SHEET 3-5 UNLESS OTHERWISE
 NOTED.
  
 1} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER
 ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THE 20 AMP OCP AND #14 CONDUCTORS FOR CIRCUIT #13 DO
 NOT COMPLY WITH 310.16.
  
 3} THE LOADS GIVEN IN THE PANEL SCHEDULE FOR THE TWO
 AHU' ARE SHOW AT 15500VA, BUT CALCULATED AT 10000 IN
 THE CALCULATED LOAD TABLE, CORRELATE SAME. 220.
  
 4} THE TWO BEDROOM CIRCUITS ARE LABELED AS GFCI ON THE
 SCHEDULE, AND ARC FAULT IN THE NOTES. SEE 210.12.
  
 5} THE DISCONNECT LOCATION AT THE CONDENSER DOES NOT
 COMPLY WITH THE CLEARANCE REQUIREMENTS OF 110.26. ALSO
 THERE WAS NO PLANS SUBMITTED FOR THE MECHANICAL WORK
 THAT'S INTENDED, MORE COMMENTS MAY COME AT THAT TIME.
  
 6} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. SHOW LOCATIONS
 AND ADD A NOTE TO INDICATE COMPLIANCE WITH THIS
 ARTICLE.
  
 7} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-05-22 Cont ID  
Sent By dpalmer Date 2009-05-22 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2009-05-22 Time 14:59 Sent To  
Notes
2009-05-22 14:59:32TO RMCD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-04-22 Cont ID  
Sent By swurafti Date 2009-04-22 Time 13:04 Rev Time 0.00
Received By swurafti Date 2009-04-22 Time 13:04 Sent To B
Notes
2009-04-22 13:05:01TO "RMCDOUGAL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-03-06 Cont ID  
Sent By adarroug Date 2009-03-06 Time 09:41 Rev Time 0.00
Received By adarroug Date 2009-03-06 Time 09:41 Sent To Z
Notes
2009-03-06 09:41:47TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-01-14 Cont ID  
Sent By adarroug Date 2009-01-14 Time 15:50 Rev Time 0.00
Received By adarroug Date 2009-01-14 Time 15:50 Sent To Z
Notes
2009-01-14 15:50:45TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 16:40 Sent To E
Notes
2008-09-26 16:40:49TO "BTROBUAG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 14:54 Sent To Z
Notes
2008-07-28 14:57:28TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 14:53 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 14:53 Sent To Z
Notes
2008-07-28 14:53:26TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-10 Cont ID  
Sent By rmcdouga Date 2008-03-10 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2008-02-28 Time 09:13 Sent To  
Notes
2008-02-28 09:13:28TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-10-14 Cont ID  
Sent By rkussner Date 2008-10-14 Time 16:32 Rev Time 0.00
Received By rkussner Date 2008-10-14 Time 16:32 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-08-04 Cont ID  
Sent By rkussner Date 2008-08-04 Time 13:47 Rev Time 0.00
Received By rkussner Date 2008-08-04 Time 13:47 Sent To  
Notes
2008-08-04 14:14:49LANDSCAPE CALCULATIONS FOR SINGLE FAMILY HOMES, BASED
 UPON ARTICLE XIV OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, SHALL BE ADDED TO THE LANDSCAPE PLAN.ALL
 EXISTING PROPOSED TREES, SHRUBS AND GROUND COVER SHALL
 BE CLEARLY IDENTIFED.NOTES CONCERING PROHIBITED PLANT
 SPECIES, DEPTH OF MULCH , PLANT GRADES AND IRRIGATION
 COVERAGE SHALL BE PLACED ON THE PLAN.
  
 ALL EXISTING TREES, SHRUBS, GROUND COVER AND SOD SHALL
 BE FLORIDA #1 GRADE OR IT WILL NEED TO BE REPLACED.
  
 SOD AND IRRIGATION IS REQUIRED IN THE RIGHT-OF-WAY
 BETWEEN THE PROPERTY LINE AND THE PAVED ROAD AND ALL
 LANDSCAPED AREAS THROUGHOUT THE SITE SHALL RECEIVE 100%
 IRRIGATION COVERAGE.
  
 SHOW ALL OVERHEAD LINES (ON OR OFF THE PROPERTY) ,
 OVERHANGING TREE LIMBS FROM NEIGHBORING PROPERTY AND
 OTHER UTILITIES THAT MAY INTERFERE WITH THE
 LANDSCAPING.
  
 THE ELEVATION SHOWS PLANTER BOXES BUT THESE BOXES ARE
 NOT SHOWN ON THE LANDSCAPE PLAN.ALL PLANS MUST BE
 CONSISTENT. IT WOULD HELP IF THE LANDSCAPE PLAN WERE
 DRAWN AT A LARGER SCALE.
  
 CONTACT ROBERT KUSSNER @ (561) 822-1462 IF THERE ARE
 ANY QUESTIONS CONCERNING THE LANDSCAPE REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-05-05 Cont ID  
Sent By rregueir Date 2009-05-05 Time 14:20 Rev Time 0.00
Received By rregueir Date 2009-05-05 Time 14:19 Sent To  
Notes
2009-05-05 14:20:01PLANS AND CALCS REVIEWED UNDER SUB PERMIT #09040581

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2009-04-06 Cont ID  
Sent By rmcdouga Date 2009-04-06 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2009-04-06 Time 10:38 Sent To  
Notes
2009-04-06 10:40:19REVISED PLANS FROM 2 STORY TO ONE STORY ADDITION
  
 MECHANICAL PROVISO
  
 A/C CONTRACTOR TO SUBMIT TWO SETS OF PLANS AND MANUAL J
 CALCULATIONS WHEN APPLYING FOR MECHANCIAL PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-10-08 Cont ID  
Sent By tgordon Date 2008-10-08 Time 10:36 Rev Time 0.45
Received By tgordon Date 2008-10-08 Time 10:36 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-08-05 Cont ID  
Sent By tgordon Date 2008-08-05 Time 16:27 Rev Time 0.30
Received By tgordon Date 2008-08-05 Time 16:27 Sent To B
Notes
2008-08-05 16:37:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 3-3-08. PLEASE SUBMIT
 COOLING LOAD CALCULATIONS (MANUAL J), PER 2004 FBC
 13-607.1.ABC.1 OR 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-03-03 Cont ID  
Sent By tgordon Date 2008-03-03 Time 13:33 Rev Time 0.30
Received By tgordon Date 2008-03-03 Time 13:33 Sent To P
Notes
2008-03-03 13:37:17PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS (MANUAL J),
 SEE 2004 FBC 13-607.1.ABC.1 OR 13-407.1.ABC.1.
  
 2) PLEASE SUBMIT TWO COPIES OF THE ENERGY
 CALCULATIONS.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-30 Cont ID  
Sent By lwagner Date 2009-03-30 Time 09:50 Rev Time 0.00
Received By lwagner Date 2009-03-30 Time 09:36 Sent To B
Notes
2009-03-30 09:52:02REVISION OK

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-02-03 Cont ID  
Sent By kstevens Date 2009-02-03 Time 12:09 Rev Time 0.00
Received By kstevens Date 2009-02-03 Time 12:09 Sent To B
Notes
2009-02-03 12:12:05DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. ALL REVISIONS SHALL BE INDICATED WITH CLOUDS AND
 REVISION NUMBERS ON THE FLOOR PLAN AND SHALL SHOW A
 REVISION HISTORY IN THE REVISION BOX IN THE TITLE
 BLOCKS. NO REVISIONS WERE INDICATED WITH A CLOUD OR
 REVISION NUMBER ON THE SHEETS OR IN THE REVISION INDEX
 SUBMITTED FOR REVIEW. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-03-04 Cont ID  
Sent By jleech Date 2008-03-04 Time 07:55 Rev Time 0.00
Received By jleech Date 2008-03-04 Time 07:45 Sent To B
Notes
***NONE***

Review Stop X PERMIT EXTENSION
Rev No 1 Status P Date 2009-03-13 Cont ID  
Sent By mcruz Date 2009-03-13 Time 11:01 Rev Time 0.00
Received By mcruz Date 2009-03-13 Time 11:01 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2009-01-27 Cont ID  
Sent By mcruz Date 2009-01-27 Time 12:35 Rev Time 0.00
Received By mcruz Date 2009-01-27 Time 12:22 Sent To E
Notes
2009-01-27 12:35:38PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE ON THE SURVEY THE SETBACK DIMENSIONS FROM
 ANY EXTERIOR IMPROVEMENTS TO ALL ADJACENT PROPERTY
 LINES. PURSUANT TO THE ZLDR, SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-29 Cont ID  
Sent By mcruz Date 2008-08-29 Time 16:13 Rev Time 0.00
Received By mcruz Date 2008-08-29 Time 16:13 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-28 Cont ID  
Sent By choops Date 2008-02-28 Time 11:50 Rev Time 0.00
Received By choops Date 2008-02-28 Time 11:50 Sent To E
Notes
2008-02-28 11:54:35***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITION TO ALL PROPERTY LINES.NOTE:MUST MEET
 MINIMUM SETBACK REQUIREMENTS FOUND IN SECTION 94-72 OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS).
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 3)A HEIGHT DIMENSION SHALL BE INDICATED FROM GRADE
 TO THE MIDPOINT OF THE ROOF'S PITCH (OF THE ADDITION).
  
 4)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK