Plan Review Details - Permit 08020561
Plan Review Stops For Permit 08020561
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By btrobaug Date 2008-03-10 Time 13:33 Rev Time 0.00
Received By shill Date 2008-03-10 Time 13:33 Sent To  
Notes
2008-03-10 14:07:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PROVIDE A REASONABLE VALUATION FOR THIS JOB.
  
 2.PROVIDE A PLAN SHOWING WHERE THE PANELS WILL BE
 INSTALLED.
  
 3.PROVIDE STRUCTURAL INFORMATION REGARDING
 ATTACHMENT.SPECS WERE PROVIDED BUT WERE INCOMPLETE.
 FOR INSTANCE, HOW MANY ANCHORS PER PANEL?
  
 4.DECLARE GOVERNING CODE AND WIND DESIGN CRITERIA
 FBC1603.1.4, FBC R 301.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-03-06 Cont ID  
Sent By btrobaug Date 2008-03-06 Time 08:47 Rev Time 0.00
Received By btrobaug Date 2008-03-06 Time 08:33 Sent To Z
Notes
2008-03-06 08:47:00 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE,2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} PROVIDE ELECTRICAL SPECIFICATIONS FOR THE PUMP THAT
 IS TO BE INSTALLED IN THIS SYSTEM.
  
 3} SUBMIT A SITE OR FLOOR PLAN LOCATING ALL THE
 EQUIPMENT FOR THIS SYSTEM. INDICATE HOW THE PUMP IS TO
 BE FED ELECTRICALLY
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-10 Cont ID  
Sent By shill Date 2008-03-10 Time 14:07 Rev Time 0.00
Received By shill Date 2008-02-26 Time 09:37 Sent To  
Notes
2008-02-26 09:37:24TO "P" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By mperson Date 2008-03-04 Time 10:46 Rev Time 0.00
Received By mperson Date 2008-03-04 Time 10:45 Sent To E
Notes
2008-03-04 11:40:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE PERMIT APPLICATION IS CONFUSING. THE SUBMITTED
 INFORMATION IS INDICATING A SOLAR WATER HEATER HOWEVER
 PERMIT APPLICATION DOES NOT INDICATE THIS OR HOW MANY
 PANELS ARE TO BE INSTALLED OR THE SIZE OF THE SOLAR
 STORAGE TANK. PLEASE CLAIFY AND CORRECT PERMIT
 APPLICATION. NOTE: DESCRIBE PROJECT IN DETAIL (FAILURE
 TO DO SO MAY RESULT IN DELAYS). PER CITY OF WPB
 AMENDMENTS TO CHAPTER 1, SECTION 105 PERMITS.
  
 2. CLEARLY IDENTIFY ALL COMPONENTS, PIPE SIZES, AND
 SHUT OFF VALVES (PER FBC PLUMBING SECTION 606.1
 FULL-OPEN VALVES SHALL BE INSTALLED ON THE WATER SUPPLY
 PIPE TO EVERY WATER HEATER) ON THE GUARDIAN'S SELF
 SUFFICIENCY SHEET. DIAGRAM APPEARS TO BE INDICATING A T
 & P RELIEF VALVE AND VACUUM RELIEF VALVE HOWEVER THEY
 ARE NOT CLEARLY IDENTIFIED. PER CITY OF WPB AMENDMENTS
 TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. CLEARLY INDICATE THE POTABLE COLD WATER SIZE AND
 MAKEUP LOCATION TO THE SOLAR WATER HEATER AND THE
 POTABLE HOT WATER SIZE AND DISCHARGE LOCATION TO THE
 HOUSE ON THE GAURDIAN'S SELF SUFFICIENCY SHEET. PER FBC
 PLUMBING SECTION 601.1 SCOPE.
  
 4. WHAT IS THE SIZE OF THE SOLAR STORAGE TANK ON THE
 GAURDIAN'S SELF SUFFICIENCY SHEET? PER FBC PLUMBING
 SECTION 501.1 SCOPE.
  
 5. THE VALUE ON THE PERMIT APPLICATION APPEARS TO BE
 LOW.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 6. PROVIDE TWO COPIES OF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR ALL POTABLE SOLAR WATER HEATER
 EQUIPMENT. PER CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1, SECTION 106.1.2 ADDITIONAL DATA.
  
 7.PER FS 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED.
  
  
 ****IMPORTANT INFORMATION******
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-03-06 Cont ID  
Sent By choops Date 2008-03-06 Time 10:43 Rev Time 0.00
Received By choops Date 2008-03-06 Time 10:43 Sent To B
Notes
2008-03-06 10:43:44N/R
  
  
  
  
 SENT TO "B" - MISC. 3