Plan Review Details - Permit 08020470
Plan Review Stops For Permit 08020470
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-14 Cont ID  
Sent By mjacobs Date 2008-05-14 Time 15:56 Rev Time 0.00
Received By mjacobs Date 2008-05-08 Time 10:31 Sent To PC
Notes
2008-05-08 10:31:34PROCESSING PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-02 Cont ID  
Sent By mjacobs Date 2008-04-02 Time 10:26 Rev Time 0.00
Received By mjacobs Date 2008-04-02 Time 09:40 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By mjacobs Date 2008-02-29 Time 07:26 Rev Time 0.00
Received By mjacobs Date 2008-02-28 Time 08:23 Sent To  
Notes
2008-02-29 07:47:34BUILDING PLAN REVIEW
 PERMIT: 08020470
 ADD: 2475 MERCER AVE #102 B
 CONT: CUSTOM QUALITY HOMES INC.
 TEL: (561)747-2620
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 2-28-08
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 11-4.13.6. MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG.25. THE FLOOR OR GROUND AREA WITHIN THE
 REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
  
 5)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. IT SEEMS AS IF
 THERE ARE DIFFERENT SUITES / UNITS AT THIS ADDRESS WITH
 DIFFERENT NUMBERS WHICH WILL REQUIRE SEPARATE PERMITS:
 THE PLANS SHOW A DOOR CONNECTING TWO UNITS. INDICATE
 CLEARLY IF THESE TWO SUITES WILL BE OWNED AND OPERATED
 BY ONE TENANT: IF NOT THE DOOR SHALL BE ELIMINATED, AND
 BE REPLACE WITH THE REQUIRED SEPARATION PARTITION PER
 FBC 708 AND TABLE 302.3.2. PLEASE BE SURE THE PLANS AND
 APPLICATION HAS THE CORRECT SUITE NUMBERS, BECAUSE
 THERE ARE TWO APPLICATIONS WITH THE SAME DRAWINGS WHICH
 SHOW THE WORK IN THE SAME LOCATION AND THE UNIT AS
 #102. FOR MORE INFORMATION ABOUT THE ADDRESSING PLEASE
 CONTACT LILLI @ 822-1239.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-08-21 Cont ID  
Sent By btrobaug Date 2008-08-21 Time 15:39 Rev Time 0.00
Received By btrobaug Date 2008-08-21 Time 14:50 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-28 Cont ID  
Sent By btrobaug Date 2008-04-28 Time 16:55 Rev Time 0.00
Received By btrobaug Date 2008-04-28 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-25 Cont ID  
Sent By btrobaug Date 2008-03-25 Time 09:43 Rev Time 0.00
Received By btrobaug Date 2008-03-25 Time 07:43 Sent To  
Notes
2008-03-25 09:41:51 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE FLA/COM VERSION 3.00 SUBMITTED HAS NOT YET BEEN
 ADOPTED BY THE FBC. PLEASE SEE 13.400.3 REFERENCES
 VERSION 2.5.
  
 2} THE CERTIFICATION OF COMPLIANCE MUST BE SIGNED BY
 THE OWNER OR OWNER AGENT. SEE 103.1 (13-103.1) AND PAGE
 #3 OF THE CERTIFICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-26 Cont ID  
Sent By btrobaug Date 2008-02-26 Time 14:04 Rev Time 0.00
Received By btrobaug Date 2008-02-26 Time 12:28 Sent To  
Notes
2008-02-26 14:04:32 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} METHOD ?A? ENERGY CALCULATIONS WERE SUBMITTED FOR
 THIS PROJECT. METHOD ?A? CAN BE USED FOR ?WHOLE
 BUILDINGS?. AS THIS IS AN ?EXISTING BUILDING ? BY
 DEFINITION?, FORM ?A? IS NEITHER REQUIRED OR ALLOWED.
 SEE 13-101.6. ALL THAT IS REQUIRED FOR THE ELECTRICAL
 REVIEW IS THE BASIC PRESCRIPTIVE REQUIREMENTS. SEE
 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES,
 GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF
 INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE
 BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION
 HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR
 LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION
 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
  
 2} 13-415.1.ABC.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-06 Cont ID  
Sent By mawillia Date 2008-05-06 Time 12:49 Rev Time 0.00
Received By mawillia Date 2008-05-06 Time 12:38 Sent To B1
Notes
2008-05-06 12:48:59*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A1, E2.01, AND FA1.01 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-04-01 Cont ID  
Sent By mawillia Date 2008-04-01 Time 14:48 Rev Time 0.00
Received By mawillia Date 2008-04-01 Time 14:18 Sent To  
Notes
2008-04-01 14:46:30*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1.THE PROJECT SITE ADDRESS, INCLUDING THE SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.HAND DRAWN MARKINGS ON SHEETS E101 THRU
 FA1.01 ARE UNACCEPTABLE
  
 6.IT IS INDICATED ON SHEET FA1.01 THAT THE BUILDING
 IS FIRE SPRINKLERED.PLEASE SHOW THE LAYOUT OF THE
 SPRINKLER HEADS IN THE TENANT SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-03 Cont ID  
Sent By mawillia Date 2008-03-03 Time 11:58 Rev Time 0.00
Received By mawillia Date 2008-03-03 Time 11:12 Sent To  
Notes
2008-03-03 11:56:19*****DENIED*****
  
 1.THE PROJECT SITE ADDRESS, INCLUDING THE SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 4.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS
 I OR CLASS II.
  
 5.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
 6.IT IS INDICATED ON SHEET FA1.01 THAT THE BUILDING
 IS FIRE SPRINKLERED.PLEASE SHOW THE LAYOUT OF THE
 SPRINKLER HEADS IN THE TENANT SPACE.
  
 7.PLEASE EXPLAIN THE DOOR BETWEEN THE TWO TENANT
 SPACES.IF THESE ARE DIFFERENT SPACES, HOW WILL TENANT
 SEPARATION BE ACCOMPLISHED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 10:53 Sent To  
Notes
2008-08-12 13:32:51TO "BOB"#7
2008-08-06 10:57:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-28 Cont ID  
Sent By adarroug Date 2008-04-28 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-04-28 Time 10:52 Sent To  
Notes
2008-04-28 10:52:59TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-24 Time 09:37 Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 09:37 Sent To  
Notes
2008-03-24 09:38:14TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-03 Cont ID  
Sent By mawillia Date 2008-03-03 Time 11:12 Rev Time 0.00
Received By mawillia Date 2008-02-22 Time 09:49 Sent To  
Notes
2008-02-22 09:49:16TO "BOB"#7

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-13 Cont ID  
Sent By tgordon Date 2008-08-13 Time 14:31 Rev Time 0.45
Received By tgordon Date 2008-08-13 Time 14:31 Sent To  
Notes
2008-08-13 14:34:10*** PROVISO ***
 1) AIR HANDLER SHALL COMPLY WITH 2004 FBC/M 306.3.
 ATTICS CONTAINING APPLIANCES REQUIRING ACCESS SHALL BE
 PROVIDED WITH AN OPENING AND UNOBSTRUCTED PASSAGEWAY
 LARGE ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE.
 THE PASSAGEWAY SHALL NOT BE LESS THAN 30 INCHES (762
 MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE THAN
 6 FEET (1829 MM) IN LENGTH MEASURED ALONG THE
 CENTERLINE OF THE PASSAGEWAY FROM THE ATTIC ACCESS
 OPENING TO THE APPLIANCE?S SERVICE PANEL. THE
 PASSAGEWAY SHALL HAVE CONTINUOUS SOLID FLOORING NOT
 LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30
 INCHES (762 MM) WIDE SHALL BE PRESENT AT THE FRONT OR
 SERVICE SIDE OF THE APPLIANCE. THE CLEAR ACCESS OPENING
 DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES
 (508 MM BY 762 MM), WHERE SUCH DIMENSIONS ARE LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE.
  
 EXCEPTION: THE PASSAGEWAY AND LEVEL SERVICE SPACE ARE
 NOT REQUIRED WHERE THE APPLIANCE IS CAPABLE OF BEING
 SERVICED AND REMOVED THROUGH THE REQUIRED OPENING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-28 Cont ID  
Sent By tgordon Date 2008-04-28 Time 11:54 Rev Time 0.30
Received By tgordon Date 2008-04-28 Time 11:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-25 Cont ID  
Sent By tgordon Date 2008-03-25 Time 10:34 Rev Time 0.30
Received By tgordon Date 2008-03-25 Time 10:34 Sent To  
Notes
2008-03-25 10:40:46PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) THE ENERGY CALCULATIONS NEED TO BE DONE WITH THE
 COMPUTER PROGRAM VERSION 2.5 NOT 3.0,PER 2004 FBC
 13-400.3.B. PLEASE CORRECT.
  
 3) THE COOLING LOAD CALCULATIONS ARE NOT WITH THE
 ENERGY CALCULATIONS, PLEASE SUBMIT COOLING LOAD
 CALCULATIONS, PER 2004 FBC 13-407.1.ACB.1
  
 4) PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3. ( REGARDING THE PRODUCT APPROVALS FOR THE
 12"X12" GREENHECK WALL LOUVERS).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-25 Cont ID  
Sent By tgordon Date 2008-02-25 Time 14:29 Rev Time 0.20
Received By tgordon Date 2008-02-25 Time 14:29 Sent To  
Notes
2008-02-25 14:30:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE JOB ADDRESS NEEDS TO BE IN THE TITLE BLOCK ON
 EACH PAGE ON THE PLANS, SEE W.P.B. AMEND. 106.1.3 AND
 F.A.C. 61G1-16.004(3).
  
 2) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR 12X12
 WALL LOUVERS, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-15 Cont ID  
Sent By jleech Date 2008-04-30 Time 08:20 Rev Time 0.00
Received By jleech Date 2008-04-30 Time 07:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-27 Cont ID  
Sent By mperson Date 2008-03-27 Time 13:14 Rev Time 0.00
Received By mperson Date 2008-03-27 Time 13:14 Sent To  
Notes
2008-03-27 13:27:07PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1.THE DRINKING FOUNTAIN IS REQUIRED TO BE ACCESSIBLE.
 THE OASIS DRINKING FOUNTAIN MODEL #P3CP IS NOT A
 HANDICAP APPROVED FIXTURE. THE LOCATION OF THE DRINKING
 FOUNTAIN WILL ALLOW A FRONTAL. SHOW THE CLEAR FLOOR
 SPACE ON THE PLANS (SHEET P1.01) 30" X 48". PLEASE
 REVIEW FBC BUILDING CHAPTER 11, SECTIONS 11-4.15.1 THRU
 11-4.15.5.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-26 Cont ID  
Sent By jleech Date 2008-02-26 Time 09:00 Rev Time 0.00
Received By jleech Date 2008-02-26 Time 08:16 Sent To  
Notes
2008-02-26 09:16:26DENIED;
 1. DRINKING FOUNTAIN REQUIRED PER FBC PLUMBING TABLE
 403.1(2B). D/F MUST MEET ACCESSIBILITY CODE SECTIONS
 11-4.15.1 THRU 11-4.15.5. SHOW DETAIL ON PLANS.
 2. BATHROOM WALLS WITH IN TWO FEET OF THE TOILET SHALL
 HAVE A SMOOTH HARD SURFACE. PAINT CAN CHIP OR SCRATCH
 SEE FBC BUILDING SECTION 1210.2.
 3. PAGE P- 2.01 WATER RISER, A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE COLD WATER TO ICE MACHINE SEE PLUMBING
 SECTION 604.9.
 4. JOB ADDRESS REQUIRED ON EACH PAGE PER WPB AMEND.
 SECTION 106.1.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-25 Cont ID  
Sent By choops Date 2008-02-25 Time 08:54 Rev Time 0.00
Received By choops Date 2008-02-25 Time 08:54 Sent To  
Notes
2008-02-25 08:54:58*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.