Plan Review Details - Permit 08020448
Plan Review Stops For Permit 08020448
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2008-05-28 Time 09:53 Sent To  
Notes
2008-05-28 09:55:37PROCESS PLANS AND PRINT PERMIT:NOTE THIS PACKAGE
 CONTAINS TWO PERMITS #08020448 AND # 08040422 :

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-26 Cont ID  
Sent By mjacobs Date 2008-04-26 Time 10:34 Rev Time 0.00
Received By mjacobs Date 2008-04-26 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-08 Cont ID  
Sent By mjacobs Date 2008-03-08 Time 10:54 Rev Time 0.00
Received By mjacobs Date 2008-03-08 Time 09:45 Sent To  
Notes
2008-03-08 10:54:34 
 BUILDING PLAN REVIEW
 PERMIT: 08020448
 ADD: 8007 OKEECHOBEE BLVD
 CONT: WEST CONST. INC.
 TEL: (561)588-2027
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.THE 2005 NFPA-70
 SHALL BE INDICATED ON THE PLANS. THIS INFORMATION SHALL
 BE CLEARLY INDICATED ON THE PLANS FOR RECORD KEEPING
 PURPOSES.
  
 3) SHEET C-501 WHICH CONTAINS STRUCTURAL DETAILS FOR
 THE METAL SWING GATE AND THE STRUCTURAL COLUMN NEEDS TO
 SHOW THE WIND DESIGN DATA IN ACCORDANCE WITH FBC
 1603.1.4
 STRUCTURAL MEMBERS AND SYSTEMS IN BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATH
 FOR THESE FORCES TO THE FOUNDATION. FBC 1609.1.3
  
 4)INDICATE THE HEIGHT OF THE 16 X 16 COLUMN DETAIL #6
 ON SHEET C-501 AND STATE IF THE MASONRY COLUMN WILL BE
 POURED SOLID WITH CONCRETE. WHAT IS THE DIMENSIONS OF
 THE FRAMED POST AND THE DEPTH AND WIDTH OF THE
 FOUNDATIONS FOR THE POSTS?CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION
 NATURE AND EXTENT OF THE WORK PROPOSED. FBC 106.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-03-03 Cont ID  
Sent By btrobaug Date 2008-03-03 Time 07:41 Rev Time 0.00
Received By btrobaug Date 2008-03-03 Time 07:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-05-01 Cont ID  
Sent By rchokshi Date 2008-05-01 Time 13:35 Rev Time 0.00
Received By rchokshi Date 2008-05-01 Time 13:35 Sent To FIRE
Notes
2008-05-01 13:40:10PERMIT # 08040422 & THIS PERMIT # 08020448APPY TO THE
 SAME PROJECT BEING TWO DIFFERENT PID #S
  
 RASIK CHOKSHI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By rchokshi Date 2008-03-10 Time 15:44 Rev Time 0.00
Received By rchokshi Date 2008-03-10 Time 15:36 Sent To  
Notes
2008-03-10 15:43:40FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE IF ANY, YOU CAN GET A C D
 FOR ALL CITY STANDARDS NOTES FROM 1000, 45 STREET,
 ENGINEERING SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION.
  
 6. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS TO US & 1000 45TH
 STREET ENGINEERING FOR THEIR REVIEW.
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-05-27 Cont ID  
Sent By mwennerg Date 2008-05-27 Time 09:52 Rev Time 0.00
Received By mwennerg Date 2008-05-27 Time 09:52 Sent To  
Notes
2008-05-27 09:52:24COMMENTS HAVE BEEN ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By mwennerg Date 2008-03-04 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2008-03-04 Time 14:06 Sent To  
Notes
2008-03-04 14:13:02***DENIED***
  
 1) PLEASE NOTE THAT A PRELIMINARY FIRE REVIEW WAS
 CONDUCTED WITH SOME COMMENTS ATTACHED THAT HAVE NOT
 BEEN ADDRESSED. THE ACCESS ROAD MAY OR MAY NOT BE
 CONSIDERED A CONVENIENCE WAY OF TRAVEL THAT MAY OR MAY
 NOT NOT BE SUBJECT TO THE REQUIREMENTS OF AN ACCESS
 ROAD PER NFPA 1, 2003 EDITION. THAT INFORMATION SHALL
 BE DETERMINED PRIOR TO ANY FURTHER REVIEW. PLEASE
 ADVISE IF ANY PREVIOUS DISCUSSIONS HAVE BEEN HELD WITH
 THIS OFFICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 10:41 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 10:41 Sent To  
Notes
2008-05-16 11:42:235/16/08--FIRE IS THE LAST REVIEW...PLANS TAKEN OFF THE
 BOARD AND ROUTED TO MIKE WENNERGREN'S DESK.
 ADARROUGH
2008-04-17 10:45:28TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-19 Cont ID  
Sent By rchokshi Date 2008-03-19 Time 08:45 Rev Time 0.00
Received By rchokshi Date 2008-02-20 Time 15:58 Sent To  
Notes
2008-02-20 16:03:43TO "COMM" BD#16--EXPEDITED--

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-21 Cont ID  
Sent By kstevens Date 2008-04-21 Time 15:46 Rev Time 0.00
Received By kstevens Date 2008-04-21 Time 15:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-21 Cont ID  
Sent By kstevens Date 2008-02-21 Time 15:41 Rev Time 0.00
Received By kstevens Date 2008-02-21 Time 15:41 Sent To  
Notes
2008-02-21 15:46:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS L1 & I1. THE SEAL BY THE LANDSCAPE ARCHITECT IS
 REQUIRED TO BE APPROXIMATELY 2", NOT 1-1/2". PLEASE
 RESEAL, SIGN & DATE THE PLANS. FAC 61G1-16.002(1) & FS
 481.306.
  
 2. SHT L1 & I1 THE BUSINESS LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS
 481.306.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By eschneid Date 2008-05-27 Time 15:14 Rev Time 0.00
Received By eschneid Date 2008-05-27 Time 15:14 Sent To  
Notes
2008-05-27 15:14:31PASSED
  
 FENCES, GATES AND COLUMNS REQUIRE A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-04-23 Cont ID  
Sent By eschneid Date 2008-04-23 Time 18:41 Rev Time 0.00
Received By eschneid Date 2008-04-23 Time 18:41 Sent To  
Notes
2008-04-23 18:48:36FAILED
  
 1) REPEAT COMMENT -PROVIDE VERIFICATION THAT THE
 COMMENTS FROM THE SURVEY AND FIRE DEPARTMENTS THAT ARE
 PART OF THE MINOR AMENDMENTS HAVE BEEN ADDRESSED.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE FENCES AND
 GATES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-26 Cont ID  
Sent By eschneid Date 2008-02-26 Time 16:39 Rev Time 0.00
Received By eschneid Date 2008-02-26 Time 16:39 Sent To  
Notes
2008-02-26 16:52:26FAILED
  
 1) THIS PERMIT CROSSES 2 DISTINCT PROPERITES.THE
 CITY'S FIRE STATION PARCEL (8007 OKEECHOBEE) AND A
 PARCEL OWNED BY THE RIVERWALK HOA.A PERMIT IS
 REQUIRED FOR EACH PROPERTY FOR THE WORK ON THE SPECIFIC
 PROPERTY.
  
 2) THE COMMENTS FROM THE SURVEY AND FIRE DEPARTMENTS
 THAT ARE PART OF THE MINOR AMENDMENTS HAVE NOT BEEN
 ADDRESSED.
  
 3) A SEPARATE PERMIT IS REQUIRED FOR THE FENCES AND
 GATES.
  
 4) FENCES MAY ONLY BE 6 FEET TALL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  