Plan Review Details - Permit 08020439
Plan Review Stops For Permit 08020439
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-04 Cont ID  
Sent By mwennerg Date 2008-04-04 Time 16:04 Rev Time 0.00
Received By mwennerg Date 2008-04-04 Time 16:03 Sent To  
Notes
2008-04-04 16:05:43PLANS APPROVED AND STAMPED REGARDING UL CERTIFICATION
 FOR CENTRAL STATION SERVICE REQUIREMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-04 Cont ID  
Sent By mawillia Date 2008-03-04 Time 15:07 Rev Time 0.00
Received By mawillia Date 2008-03-04 Time 11:16 Sent To  
Notes
2008-03-04 12:25:45*****DENIED******
  
  
 1.ON SHEET 1 OF 1, AMEND FIRE ALARM SEQUENCE OF
 OPERATION TO REFLECT THAT DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 2.ON SHEET 1 OF 1, INCLUDE THE INSTALLATION OF THE
 FIRE ALARM ANNUNCIATOR (FAA) IN THE TOTAL SCOPE OF
 WORK.
  
 3.ON SHEET 1 OF 1, THERE ARE 22 HORN STROBES
 INSTALLED ACCORDING TO THE SCOPE OF WORK AND THE
 LEGEND/EQUIPMENT LIST. IT APPEARS THAT ONLY 21 SUCH
 DEVICES ARE SHOWN ON THE FIRE ALARM LAYOUT (SHEET 1)
 AND THE FIRE ALARM RISER (SHEET 2).
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 11:15 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 11:15 Sent To FIRE
Notes
2008-03-27 11:16:35TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-04 Cont ID  
Sent By mawillia Date 2008-03-04 Time 11:16 Rev Time 0.00
Received By mawillia Date 2008-02-20 Time 11:47 Sent To  
Notes
2008-02-20 11:47:52TO "F" BOX