2008-02-20 08:41:50 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION 401.1 SCOPE. |
| **NOT ALL CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF |
| PIPE ARE INDICATED. PLEASE REFERENCE THE RED CIRCLED |
| CUT SECTIONS HIGH LIGHTED YELLOW INDICATING THIS. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| **NOT ALL PIPE SIZES OR MATERIALS ARE BEING INDICATED. |
| |
| |
| 3. WHITE OUT ON PLANS IS UNACCEPTABLE PER CITY OF WPB |
| AMENDMENTS TO CHAPTER 1, SECTION 106.1.3 QUALITY OF |
| BUILDING PLANS. |
| |
| 4. AT A MINIMUM TWO SETS OF PLANS ARE REQUIRED AND |
| THEY MUST BE CORRELATED. PER CITY OF WPB AMENDMENTS TO |
| CHAPTER 1, SECTION *106.1 SUBMITTAL DOCUMENTS. |
| NOTE: THE SUBMITTED PLANS ARE NOT CORRELATED, ONE |
| DRAWING IS INDICATING A 1" GAS SUPPLY FROM THE METER |
| AND ANOTHER DRAWING IS INDICATING A 1-1/4" GAS SUPPLY |
| FROM THE METER. PLEASE CORRELATE PLANS AND RESUBMIT. |
| |
| 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| END OF COMMENTS: |
| |