Plan Review Details - Permit 08020382
Plan Review Stops For Permit 08020382
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-06-13 Cont ID  
Sent By lursu Date 2008-06-13 Time 15:27 Rev Time 0.00
Received By lursu Date 2008-06-13 Time 15:27 Sent To  
Notes
2008-06-13 15:28:13PERMIT ATTACHED TO CORRECT PCN AND ADDRESS 3309 S
 FLAGLER DR.
  
 LACRAMIOARA URSU, MA ,GISP
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-03-05 Cont ID  
Sent By lursu Date 2008-03-05 Time 10:59 Rev Time 0.00
Received By lursu Date 2008-03-05 Time 10:59 Sent To  
Notes
2008-03-05 11:06:30***FAILED***
  
 THE PERMIT APPLICATION HAS THE ADDRESS OF 3301 S
 FLAGLER DR , PCN = 74434334100130010 AND THE SITE PLANS
 SHOW THE ADDRESS FOR THE NEW HOUSE AT 3309 S FLAGLER DR
 ,
 PCN = 74434334100130041.PLEASE CLARIFY THE JOB LOCATION
 .
  
 QUESTIONS/COMMENTS
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-01-16 Cont ID  
Sent By kconrad Date 2009-01-16 Time 14:35 Rev Time 0.00
Received By kconrad Date 2009-01-16 Time 14:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-13 Cont ID  
Sent By mjacobs Date 2008-06-13 Time 15:58 Rev Time 0.00
Received By mjacobs Date 2008-06-13 Time 14:57 Sent To PC
Notes
2008-06-13 15:21:07BUILDING PROVISO:
 TO BE IN PLACE AT C.O:
  
 PRIVATE
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-26 Cont ID  
Sent By mjacobs Date 2008-04-26 Time 13:48 Rev Time 0.00
Received By mjacobs Date 2008-04-26 Time 12:02 Sent To PC
Notes
2008-04-26 13:48:14BUILDING PLAN REVIEW#2
 PERMIT: 08020382
 ADD:
 CONT: PUGH?S POOLS & SPA INC.
 TEL: (561)772-418-2013
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-26-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 OK
  
 **PLEASE CONTACT LILY AT 822-1239 TO CLARIFY THE
 ADDRESS.**
 2)THE ADDRESS ON THE APPLICATION AND THE PLANS ARE
 INCORRECT. TWO DIFFERENT PROPERTIES ON DIFFERENT LOTS
 CANNOT HAVE THE SAME ADDRESS. IS THE ADDRESS FOR THE
 POOL PROJECT 3301 OR 3309? PLEASE MAKE SURE THE CORRECT
 OWNER AND ADDRESS IS ON THE APPLICATION. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED.
 FBC 106.1.1.
  
 **NO RESPONSE NOT ADDRESSED**
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES THE VALUATION SHALL BE THE
 TOTAL VALUE INCLUDING ELECTRIC, PLUMBING, STRUCTURAL,
 INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT EXCLUDING LAND
 VALUE. OUR VALUATION REFERENCE IS ICC (BVD)
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 **PLEASE CONTACT LILY AT 822-1239 TO CLARIFY THE
 ADDRESS.**
 4)THE PROPERTY APPRAISER WEB-SITE SHOWS THE SAME
 ADDRESS FOR TWO DIFFERENT LOTS WITH DIFFERENT OWNERS.
 THE PLANS CONTAIN THE NAME RATHER HOWEVER, ON THE
 INFORMATION ON PROPERTY APPRAISER FORMS HAVE THE NAME
 HAISFIELD LISA ON ONE SHEET AND THE OTHER HAS RATNER
 DENNIS. WHO OWNS THIS PROPERTY?
  
 5)OK
  
 **NEW**
 THE DRAWINGS INDICATE THE POOL FINISH AS TILE. NOTE:
 424.1.2.1
 POOLS SHALL BE CONSTRUCTED OF CONCRETE OR OTHER
 IMPERVIOUS AND STRUCTURALLY RIGID MATERIAL. ALL POOLS
 SHALL BE WATERTIGHT, FREE FROM STRUCTURAL CRACKS AND
 SHALL HAVE A NONTOXIC SMOOTH AND SLIP-RESISTANT FINISH.
 TILE USED IN LESS THAN 5 FEET OF WATER MUST BE SLIP
 RESISTANT EXCEPT FOR BULL-NOSE TILE WHEN UTILIZED AS
 STEP, BENCH OR SWIM-OUT MARKINGS.PROVIDE THE
 MANUFACTURE?S SPECIFICATIONS FOR THE TILE INDICATING
 THAT THEY CAN BE USED IN THIS SITUATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-01 Cont ID  
Sent By mjacobs Date 2008-03-01 Time 10:29 Rev Time 0.00
Received By mjacobs Date 2008-03-01 Time 06:05 Sent To PC
Notes
2008-03-01 10:29:00BUILDING PLAN REVIEW
 PERMIT: 08020382
 ADD:
 CONT: PUGH?S POOLS & SPA INC.
 TEL: (561)772-418-2013
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3-01-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)THE ADDRESS ON THE APPLICATION AND THE PLANS ARE
 INCORRECT. TWO DIFFERENT PROPERTIES ON DIFFERENT LOTS
 CANNOT HAVE THE SAME ADDRESS. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. FBC
 106.1.1.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES THE VALUATION SHALL BE THE
 TOTAL VALUE INCLUDING ELECTRIC, PLUMBING, STRUCTURAL,
 INTERIOR FINISHES, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT EXCLUDING LAND
 VALUE. OUR VALUATION REFERENCE IS ICC (BVD)
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
 4)THE PROPERTY APPRAISER WEB-SITE SHOWS THE SAME
 ADDRESS FOR TWO DIFFERENT LOTS WITH DIFFERENT OWNERS.
 THE PLANS CONTAIN THE NAME RATHER HOWEVER, ON THE
 INFORMATION ON PROPERTY APPRAISER FORMS HAVE THE NAME
 HAISFIELD LISA ON ONE SHEET AND THE OTHER HAS RATNER
 DENNIS. WHO OWNS THIS PROPERTY?PLEASE CONTACT LILLI
 AT 822-1239 FOR CLARIFICATION ON THE ADDRESSING
 PROBLEM.
  
 5)DUE TO THE FACT THE POOL IS LOCATED ON A ROOF DECK;
 SUBMIT THE STRUCTURAL DETAIL CALCULATION FOR THE LOAD
 BEARING OF THE POOL AND ALL OTHER EQUIPMENT ON THE ROOF
 DECK. THE STRUCTURAL ENGINEERED ROOF DETAIL DRAWINGS
 SHALL BE SUBMITTED TO THIS OFFICE, SHOWING THE POOL
 LAYOUT WITH ALL SUPPORTS. THE DRAWINGS SHALL BE
 DESIGNED BY A STRUCTURAL ENGINEER AND SIGN, SEAL AND
 DATED BY THE RESPONSIBLE ENGINEER IN ACCORDANCE WITH
 F.A.C 61G1-16.004.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-12 Cont ID  
Sent By jleahy Date 2009-02-12 Time   Rev Time 0.00
Received By jleahy Date 2009-02-12 Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 07:01 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 06:37 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-02-22 Cont ID  
Sent By btrobaug Date 2008-02-22 Time 07:33 Rev Time 0.00
Received By btrobaug Date 2008-02-22 Time 07:16 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-02-28 Cont ID  
Sent By mperson Date 2008-02-28 Time 08:35 Rev Time 0.00
Received By mperson Date 2008-02-28 Time 08:35 Sent To B
Notes
2008-02-28 08:37:15CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-02 Cont ID  
Sent By rbrown Date 2009-01-02 Time 14:39 Rev Time 0.00
Received By rbrown Date 2009-01-02 Time 14:39 Sent To  
Notes
2009-01-02 14:46:29SUBMITTAL ROUTED TO LARRY WAGNER FOR REVIEW OF PROPOSED
 SKIMMER DETAIL (PLUMBING) AND FURTHER ROUTING TO JAKE
 LEAHY AND KEN CONRAD FOR ELECTRICAL AND BUILDING. RB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 16:49 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 16:49 Sent To Z
Notes
2008-06-03 16:49:43TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 15:44 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 15:44 Sent To Z
Notes
2008-04-21 15:44:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-03-01 Time   Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 12:36 Sent To  
Notes
2008-02-19 12:36:16TO "Z" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-01-06 Cont ID  
Sent By lwagner Date 2009-01-06 Time 14:49 Rev Time 0.00
Received By lwagner Date 2009-01-05 Time 13:27 Sent To B
Notes
2009-01-05 13:41:05REVISION OK - LEW

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-09 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 07:02 Rev Time 0.00
Received By mperson Date 2008-06-09 Time 09:18 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-24 Cont ID  
Sent By mperson Date 2008-04-24 Time 13:54 Rev Time 0.00
Received By mperson Date 2008-04-24 Time 13:54 Sent To B
Notes
2008-04-24 14:07:19PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS FOR THE PURPOSE
 OF CONTINUITY.
  
 1) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (TWO COPIES OF MANUFACTURE
 SHEETS REQUIRED INDICATING THE MAKE, MODEL NUMBER, AND
 A LISTING FROM A NATIONALLY RECOGNIZED TESTING AGENCY,
 PLEASE SUBMIT)
 **THE RESUBMITTAL DID NOT HAVE 2 COPIES OF THE POOL
 HEATER MANUFACTURER'S SHEETS INDICATING THE MAKE, MODEL
 NUMBER AND A LISTING FROM A NATIONALLY RECGNIZED
 TESTING LABORATORY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE: (561) 805-6730
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-28 Cont ID  
Sent By mperson Date 2008-02-28 Time 08:30 Rev Time 0.00
Received By mperson Date 2008-02-28 Time 08:30 Sent To G
Notes
2008-02-28 08:35:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (TWO COPIES OF MANUFACTURE
 SHEETS REQUIRED INDICATING THE MAKE, MODEL NUMBER, AND
 A LISTING FROM A NATIONALLY RECOGNIZED TESTING AGENCY,
 PLEASE SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-06 Cont ID  
Sent By choops Date 2008-06-06 Time 11:50 Rev Time 0.00
Received By choops Date 2008-06-06 Time 11:50 Sent To P
Notes
2008-06-06 11:51:23***APPROVED - RESUB #2***
  
  
  
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 2 Status F Date 2008-04-23 Cont ID  
Sent By choops Date 2008-04-23 Time 14:09 Rev Time 0.00
Received By choops Date 2008-04-23 Time 14:09 Sent To P
Notes
2008-04-23 14:27:00***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 2)PROVIDE AN ELEVATION DRAWING SHOWING THE HEIGHT
 DIMENSIONS FROM GRADE TO THE UPPERMOST POINT OF PARAPET
 WALL AND/OR ANY ACCESSORIES.NOTE:MAXIMUM HEIGHT
 ALLOWABLE = 33 FEET (30 FEET, PLUS AN ADDITIONAL 10%
 FOR ACCESSORIES).
  
 NEW COMMENTS:
  
 1)THE SUBMITTED DOCUMENTS STILL HAVE INCORRECT
 ADDRESS OF 3301, AND HAVE BEEN CHANGED WITH A PEN.
 PLEASE ENSURE ALL DOCUMENTS CONTAIN THE CORRECT ADDRESS
 OF THE SUBJECT PROPERTY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-20 Cont ID  
Sent By choops Date 2008-02-20 Time 12:05 Rev Time 0.00
Received By choops Date 2008-02-20 Time 12:05 Sent To E
Notes
2008-02-20 12:11:52***FAILED***
  
  
 1)PROPERTY CONTROL NUMBER/ADDRESS PROVIDED ON PERMIT
 APPLICATION DO NOT MATCH THE LOT SHOWN WITH THE
 PROPOSED POOL.PLEASE CLARIFY AND AMEND THE
 APPLICATION TO REFLECT THE ACCURATE INFORMATION.
  
 2)PROVIDE AN ELEVATION SHOWING THE HEIGHT DIMENSIONS
 FROM GRADE TO THE UPPERMOST POINT OF PARAPET WALL
 AND/OR ANY ACCESSORIES.NOTE:MAXIMUM HEIGHT
 ALLOWABLE = 33 FEET (30 FEET, PLUS AN ADDITIONAL 10%
 FOR ACCESSORIES).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720