Plan Review Details - Permit 08020371
Plan Review Stops For Permit 08020371
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-02 Cont ID  
Sent By rmcdouga Date 2008-10-02 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2008-10-02 Time 16:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-08-27 Cont ID  
Sent By rmcdouga Date 2008-08-27 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2008-08-27 Time 11:50 Sent To  
Notes
2008-08-27 11:44:302004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATION AND ADDITION
 EXPIRED PERMIT 05070071
  
 DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS HAVE INCORRECT INFORMATION
 LISTED FOR THE FASTENING DATA FROM THE NOA. THE NOA
 FASTENER SPACING IS 8" OC IN 4 ROWS, ONE OF WHICH IS
 THE LAP. THE NUMBER OF ROWS IN THE FIELD IS 3, WHICH
 DOES NOT INCLUDE THE LAP. THE ROW SPACING IS 9.34".
 HOWEVER, THE CALCULATED FASTENER SPACINGS ARE
 ACCEPTABLE. PLEASE REVISE THE RAS CALCULATIONS TO
 CONCUR WITH THE NOA. NOTE: THE SYSTEM THAT WAS SELECTED
 REQUIRES SCREWS AND 3" PLATES FOR FASTENERS. FAC RULE
 9B-72
  
 2) THE PRODUCT APPROVAL FOR THE TOWN AND COUNTRY STORM
 PANELS HAS NO REQUIREMENT FOR GLASS SEPARATION PROVIDED
 THE MINIMUM PANEL LENGTHS ARE AS NOTED IN TABLE 2 ON
 SHEET 6. USING DIRECT MOUNT WITH PANELMATE ANCHORS THE
 MINIMUM LENGTH IS 52". THERE ARE 2 OPENINGS WITH SPANS
 OF 46" THAT DO NOT COMPLY. PLEASE CORRECT. SEE TABLE 2
 OF PRODUCT APPROVAL. NOT: THE DRAWINGS THAT WERE
 SUBMITTED WERE PARTIALLY ILLEGIBLE AND HAVE BEEN
 REPLACED WITH NEW PAGES. R301.2.1.2
  
 3) ON THE STORM PANEL SCHEDULE UNDER SHUTTER MOUNT
 CONNECTION SECTION 8 IS SPECIFIED. NUMBER 8 ON SHEET 1
 IS FOR "F" TRACK. PANELMATES ARE USED FOR DIRECT MOUNT.
 PLEASE CLARIFY. ALSO INDICATE CONNECTION TYPE AS C1,
 C2, C3 OR C4, WHICH IS NEEDED TO DETERMINE FASTENER
 SPACING FROM THE TABLES ON SHEETS 5 AND 6 OF THE
 PRODUCT APPROVAL. SEE SHEETS 2 AND 3 OF PRODUCT
 APPROVAL.R301.2.1.2
  
 4) SUBMIT 2 COPIES OF PRODUCT APPROVALS APPROVED BY THE
 DESIGNER OF RECORD FOR WINDOW MULLIONS THAT WILL USED
 ON LIVING ROOM WINDOW. FAC RULE 9B-72 AND FBC 106.3.3*
 CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-24 Cont ID  
Sent By rmcdouga Date 2008-06-24 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2008-06-24 Time 16:25 Sent To  
Notes
2008-06-24 16:25:302004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATION AND ADDITION
 EXPIRED PERMIT 05070071
  
 DENIED BY BUILDING
  
 1) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL
 SIGNATURE OF THE ARCHITECT. COPIED SIGNATURES ARE NOT
 ACCEPTABLE. THE DATE SEAL IS AFFIXED IS ALSO REQUIRED.
 SEE FS 481 AND FAC 61G1-16.003. REPEAT COMMENT.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR GLAZED FRENCH DOORS AS REQUIRED BY FAC RULE
 9B-72. REPEAT COMMENT.
  
 3) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 CASEMENT WINDOWS IS EXPIRED AND DOES NOT CORRESPOND
 WITH THE NOA NUMBERS LISTED ON THE FLORIDA COVER SHEET.
 SUBMIT THE CORRECT NOA. RULE 9B-72
  
 4) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOFING
 WILL BE USED. SPECIFY THE FASTENING OPTION AND DESIGN
 PRESSURE FOR THE ASSEMBLY. SUBMIT RAS 117 CALCULATIONS
 FOR ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER
 7 OF THE PRODUCT APPROVAL. R905.11.3
  
 5) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED FOR THE
 STORM PANELS IS FROM EASTERN METAL SUPPLIES AND THE
 PRODUCT APPROVALS ARE FROM TOWN AND COUNTRY. THE
 SUBSTRATE IS LISTED AS CONC. BLOCK AND THE PLANS SHOW
 WOOD FRAME AT SOME OF THE OPENINGS. PLEASE CORRECT. FBC
 R 301.2.1.2
  
 6) ON SHEET A-2 GENERAL NOTE SPECIFIES IMPACT RATED PGT
 DOORS. THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE
 FOR IMPACT RATED WINDOWS AND PANEL DOORS. IF WINDOWS
 AND DOORS ARE IMPACT RATED, THEN STORM PANELS ARE NOT
 REQUIRED. PLEASE CLARIFY.
  
 7)THE ENERGY CALCULATIONS THAT WERE SUBMITTED ON FORM
 600A-04R ARE TAKING A CEILING FAN CREDIT. THE ELECTRIC
 PLANS DO NOT SPECIFY A CEILING FAN IN THE LIVING ROOM,
 WHICH IS REQUIRED IF TAKING THE CREDIT. ALSO, SPECIFY
 THE SIZE OF THE FANS ON THE PLANS.SEE FBC
 13-607.1.A.1
  
 8) SUBMIT BUCK DETAILS FOR THE WINDOWS AND DOORS. FBC
 R613.6.1.1 THE DOOR JAMB DETAIL THAT WAS SUBMITTED ON
 THE 8.5" X 11" SHEET, IS NOT SIGNED, SEALED AND DATED
 BY THE DESIGNER OF RECORD, IT DOES NOT HAVE A TITLE
 BLOCK IDENTIFYING THE PROJECT AND IT REFERS TO DETAIL 5
 ON S7 WHICH WAS NOT SUBMITTED AS PART OF THE DOCUMENTS
 FOR THIS PROJECT. SEE FAC 61G1-16.003.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By rmcdouga Date 2008-02-27 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2008-02-27 Time 11:34 Sent To  
Notes
2008-02-27 14:16:122004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATIONS AND ADDITION
 EXPIRED PERMIT 05070071
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT WILL BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE PLANS ARE REQUIRED TO HAVE THE RAISED SEAL AND
 ORIGINAL SIGNATURE OF THE ARCHITECT. COPIED SIGNATURES
 ARE NOT ALLOWED. FS 481
  
 4) THE SITE PLAN INDICATES THAT ONE WALL OF THE
 ADDITION IS 5' FROM THE PROPERTY LINE. SUBMIT A SITE
 PLAN OR SURVEY THAT SHOWS THAT THE DISTANCE TO THE
 STRUCTURES ON THE ADJACENT PROPERTY IS MORE THAN 6 FEET
 OR SHOW COMPLIANCE WITH FBC R302.1 AND R302.2 WHICH
 REQUIRE ONE HOUR FIRE RATED WALLS AND NO OPENINGS IN
 WALLS WITH LESS THAN 6 FEET OF SEPARATION.
  
 5) SUBMIT TWO (2) COPIES OF CURRENT (2004 FBC) PRODUCT
 APPROVALS FOR THE NEW EXTERIOR DOORS, WINDOWS, WINDOW
 MULLIONS, ROOF COVERING, WOOD CONNECTORS AND STORM
 PANELS. FAC RULE 9B-72.
  
 6)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 ANCHOR TYPE AND SPACING, EDGE DISTANCE, ETC. SEE
 ATTACHED SAMPLE OF INSTALLATION SCHEDULE. FBC 106.1.1*
 CITY AMENDMENTS.
  
 8) SPECIFY THE WINDOW TYPES AND SIZES ON THE PLANS. FBC
 106.1.1*CITY AMENDMENTS.
  
 9)SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION AS REQUIRED BY FBC 11-600. NOTE: OWNER/AGENT
 IS REQUIRED TO SIGN THE ENERGY CALC. FORMS.
  
 10) PROVIDE BUCK DETAILS FOR THE WINDOWS AND DOORS. SEE
 FBC 1714.5.4.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-11-23 Cont ID  
Sent By btrobaug Date 2009-11-23 Time 12:04 Rev Time 0.00
Received By btrobaug Date 2009-11-23 Time 11:39 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-09-29 Cont ID  
Sent By btrobaug Date 2008-09-29 Time 12:25 Rev Time 0.00
Received By btrobaug Date 2008-09-29 Time 12:01 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-08-25 Cont ID  
Sent By btrobaug Date 2008-08-25 Time 15:43 Rev Time 0.00
Received By btrobaug Date 2008-08-25 Time 09:40 Sent To B
Notes
2008-08-25 14:42:32 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E1, UNLESS OTHERWISE
 NOTED.
  
 DUE TO THE REVISED PLAN THE FOLLOWING COMMENTS ARE
 REQUIRED FOR CODE COMPLIANCE.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1). THE ONE ON THE PLAN IS INSIDE, THE
 PURPOSE OF THIS ARTICLE IS TO DISCONNECT THE SERVICE
 CONDUCTORS OUTSIDE TJHE BUILDING.
 .
 2} CRCUIT # 13, SMALL APPLIANCE IS NOW IN THE FOYER AS
 WELL AS THE KITCHEN STILL IN VIOLATION OF
 210.52(B)(2).
  
 3} CLARIFY THE CLOUD WITH 54" MARKED AT ALL CEILING
 FANS. SEE 110.3(B) INSTALLATION AND USE LISTED OR
 LABELED EQUIPMENT SHALL BE INSTALLED AND USED IN
 ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE
 LISTING OR LABELING.
  
 4} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.THE REAR RECEPTALE IS MISSING ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-16 Cont ID  
Sent By btrobaug Date 2008-06-16 Time 13:21 Rev Time 0.00
Received By btrobaug Date 2008-06-16 Time 12:41 Sent To B
Notes
2008-06-16 13:21:08 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ELECTRIC METER LOCATIONS ON SHEET A-1AND E-1 ARE
 DIFFERENT. CORRELATE SAME.A-1 INDICATES A NEW SERVICE
 AND E-1 INDICATES EXISTING SERVICE.
  
 2} THE RISER DIAGRAM ON SHEET E-1 RATES THE PANEL AND
 DISCONNECT AT 150 AMPS. THE PANEL SCHEDULE INDICATES
 200 AMP MAIN BREAKER, CORRELATE SAME TO SHOW ACTUAL
 INTENTION.
  
 3} THE RISER DIAGRAM SHOWS A 150 AMP DISCONNECT, NONE
 IS LOCATED ON THE PLAN.
  
 4} ALL DEVICES ARE LABLED WITH CIRCUIT NUMBERS EXCEPT
 THE DINING ROOM. SEE 210.52(B)(1) FOR SMALL APPLIANCE
 REQUIREMENTS.
  
 5} CIRCUIT #13, SMALL APPLIANCE, IN THE HALLWAY IS IN
 VIOLATION OF 210.52(B)(1).
  
 6} SEE 210.52(E) FOR RECEPTACLE REQUIREMENTS OUTDOORS,
 THERE IS NONE IN THE FRONT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-21 Cont ID  
Sent By btrobaug Date 2008-02-21 Time 10:02 Rev Time 0.00
Received By btrobaug Date 2008-02-21 Time 07:09 Sent To M
Notes
2008-02-21 09:40:27 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, EXISTING BUILDING
 CODE 2004,2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ARCHITECT'S SIGNATURE AND SEAL IS A PHOTOCOPY.
 WHEN SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE
 WET AND THE SEAL MUST MAKE AN IMPRESSION PER
 481.221(1)(A) FLORIDA STATUTES.2}
  
 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 3.} SUBMIT A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULESPER 106.3.5.4 FBC. PER 215.5 NEC.
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. SEE ARTICLE FOR
 EXCEPTIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-11-19 Cont ID  
Sent By kstevens Date 2009-11-19 Time 09:13 Rev Time 0.00
Received By kstevens Date 2009-11-19 Time 09:13 Sent To  
Notes
2009-11-19 09:13:28SENT TO BTROBAUGH.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-05 Cont ID  
Sent By adarroug Date 2009-01-05 Time 09:09 Rev Time 0.00
Received By adarroug Date 2009-01-05 Time 09:09 Sent To P
Notes
2009-01-05 09:09:20TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 16:59 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 16:58 Sent To P
Notes
2008-12-10 16:59:20TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-19 Cont ID  
Sent By adarroug Date 2008-09-19 Time 11:31 Rev Time 0.00
Received By adarroug Date 2008-09-19 Time 11:31 Sent To E
Notes
2008-09-19 11:31:21TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 11:07 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 11:07 Sent To E
Notes
2008-08-18 11:08:05TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 09:18 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 09:18 Sent To Z
Notes
2008-06-16 09:19:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-27 Cont ID  
Sent By rmcdouga Date 2008-02-27 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2008-02-19 Time 11:04 Sent To  
Notes
2008-02-19 11:04:28TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-02-22 Cont ID  
Sent By tgordon Date 2008-02-22 Time 12:06 Rev Time 0.25
Received By tgordon Date 2008-02-22 Time 12:06 Sent To P
Notes
2008-02-22 12:07:23NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-01-12 Cont ID  
Sent By lwagner Date 2009-01-12 Time 12:50 Rev Time 0.00
Received By lwagner Date 2009-01-12 Time 12:32 Sent To  
Notes
2009-01-12 12:49:50REVISION OK SHEET P1

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-02 Cont ID  
Sent By lwagner Date 2009-01-02 Time   Rev Time 0.00
Received By lwagner Date 2008-12-31 Time 09:14 Sent To  
Notes
2008-12-31 09:19:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 NOTE: PLEASE HAVE LICENSED PLUMBING CONTRACTOR APPLY
 FOR PERMIT. PLEASE NOTE THAT THE VALUATION OF THIS
 PROJECT WILL BE INCREASED DUE TO THE NEW PLUMBING.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED TO MEET CODE
 COMPLIANCE.
  
 1. SHEET P-1 SANITARY RISER DIAGRAM: THE KITCHEN SINK
 SHALL DRAIN DOWNSTREAM OF THE WET VENTED BATHROOMS. PER
 909.1 WET VENT PERMITTED.
  
 2. SHEET P-1 SANITARY RISER DIAGRAM. THE WASHER IS
 SIZED WRONG, PLEASE CORRECT THE FOLLOWING.
 (A) 406.3 WASTE CONNECTION. THE AUTOMATIC CLOTHES
 WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN OR
 DRAINAGE STACK OF 3 INCHES IN DIAMETER.
  
 (B) 708.3.4 BASE OF STACK. A CLEANOUT SHALL BE PROVIDED
 AT THE BASES OF EACH WASTE OR SOIL STACK.
  
 (C) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS (CLEANOUT FOR WASHING MACHINE SHALL BE
 LOCATED AT 4' A.F.F.)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 LARRY WAGNER
 BUILDING PLANS EXAMINER / PLUMBING
 OFFICE: (561) 805-6692
 FAX: (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-02-25 Cont ID  
Sent By jleech Date 2008-02-25 Time 07:57 Rev Time 0.00
Received By jleech Date 2008-02-25 Time 07:57 Sent To B
Notes
2008-02-25 07:58:39NO PLUMBING WORK SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By choops Date 2008-06-16 Time 11:16 Rev Time 0.00
Received By choops Date 2008-06-16 Time 11:16 Sent To E
Notes
2008-06-16 11:17:16***APPROVED - RESUB #1***
  
 PROVISOS:
 1)A/C EQUIPMENT SHALL NOT PROJECT MORE THAN 4' INTO A
 REQUIRED SETBACK.
  
 2)REPAIR OF EXISTING DRIVEWAY/WALKWAY ONLY.
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By choops Date 2008-02-19 Time 11:49 Rev Time 0.00
Received By choops Date 2008-02-19 Time 11:49 Sent To E
Notes
2008-02-19 11:57:01***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)INDICATE SETBACK DIMENSIONS FROM STRUCTURAL POSTS
 OF PATIO AND PORCH TO THE PROPERTY LINES.NOTE: MUST
 MEET MINIMUM SETBACK REQUIREMENTS FOUND IN SECTION
 94-74 OF THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS).
  
 3)INDICATE SEPARATION DISTANCE FROM PROPOSED WORK TO
 THE EXISTING ACCESSORY STRUCTURE.NOTE:MUST BE A
 MINIMUM OF 6 FEET.
  
  
 NOTE:OVERHANGS SHALL NOT PROJECT MORE THAN 3' INTO A
 REQUIRED SETBACK, PURSUANT TO SECTION 94-305 OF THE
 ZLDRS.
  
 NOTE:PERMIT APPLICATION DENOTES REPLACEMENT OF
 EXISTING DRIVEWAY, ANY CHANGE TO EXISTING WILL REQUIRE
 THE PLANS TO REFLECT SUCH.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - SF RACK