Plan Review Details - Permit 08020280
Plan Review Stops For Permit 08020280
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-11-17 Cont ID  
Sent By lmartine Date 2008-11-17 Time 14:51 Rev Time 0.00
Received By lmartine Date 2008-11-17 Time 14:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-27 Cont ID  
Sent By lmartine Date 2008-10-27 Time 09:18 Rev Time 0.00
Received By lmartine Date 2008-10-27 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-01 Cont ID  
Sent By kconrad Date 2008-04-01 Time 15:24 Rev Time 0.00
Received By kconrad Date 2008-04-01 Time 15:24 Sent To  
Notes
2008-04-01 15:26:07A PRE-INSPECT WAS PERFORMED BY CJ AND WAS APPROVED. NO
 ADDITIONAL DETAILS REQUIRED AT THIS TIME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-25 Cont ID  
Sent By kconrad Date 2008-03-25 Time 16:45 Rev Time 0.00
Received By kconrad Date 2008-03-25 Time 16:00 Sent To  
Notes
2008-03-25 16:56:35PROJECT: 1921 SOUTH DIXIE HIGHWAY/ ELECTRICAL&
 SUSPENDED CEILING REPAIR
  
 CODE REVIEW:
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH AMENDMENTS 2004 EDITION
  
 STATUS:
  
 COMMENTS:
  
 1) PLEASE PROVIDE DETAILS FOR THE ATTACHMENT OF THE
 REPAIRED CEILING GRID SYSTEM.
  
 2) A PRELIMINARY INSPECTION WILL BE PERFORMED SINCE A
 HOLD WAS PLACED ON THIS PARCEL NUMBER DUE TO EXPIRED
 PERMITS AND INCOMPLETED INSPECTIONS.
  
 3) THE BUILDING PLAN REVIEW REMAINS INCOMPLETE AT THIS
 TIME UNTIL A PRELIMINARY INSPECTION IS COMPLETED AS PER
 THE FBC, SECTION 109.2:
  
 109.2 PRELIMINARY INSPECTION.
  
 BEFORE ISSUING A PERMIT, THE BUILDING OFFICIAL IS
 AUTHORIZED TO EXAMINE OR CAUSE TO BE EXAMINED
 BUILDINGS, STRUCTURES AND SITES FOR WHICH AN
 APPLICATION HAS BEEN FILED.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-08 Cont ID  
Sent By dpalmer Date 2008-10-08 Time 12:22 Rev Time 0.00
Received By dpalmer Date 2008-10-08 Time 12:22 Sent To  
Notes
2008-10-08 12:22:51** DENIED **
  
  
 ** PLANS NOW SUBMITTED HAVE BEEN REVISED. PLEASE SEE
 THE FOLLOWING COMMENTS
  
 1) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM IS
 NOT COMPLETE. PLEASE SEE 250.50,250.56 ETC. NO GROUND
 RODS OR OTHER SYSTEM SHOWN. ONLY NOTED FOR CWP.
  
 2) NOTE: PLEASE INDICATE THE CONDUCTORS FROM NEW GUTTER
 TO MAINS.
 310.16, 240.4.
  
 3) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW
 MAINS/SERVICE EQUIPMENT. 110.03
 FBC 106.1.1
  
 4) NOTE: PLEASE CLARIFY THE LIGHTING CONTROLS AS NOTED
 AND SHOWN ON PLANS. SOME PARTS OF THE PLANS INDICATE
 OCCUPANCY DEVICES HOWEVER NOT IN ALL LOCATIONS.
 PLEASE SEE FBC 13-415.1.ABC.1.2 FOR CONTROLS IN
 SEPARATE SPACES.
  
 5) NOTE: PLEASE SEE FBC 108.3, AS SCOPE OF WORK HAS
 INCREASED PLEASE REVISED VALUE ON PERMIT APPLICATION.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-15 Cont ID  
Sent By dpalmer Date 2008-02-15 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2008-02-15 Time 17:42 Sent To  
Notes
2008-02-15 17:42:28*** DENIEDREVIEW***
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES SHALL
 BE STATED ON PLANS RELEVANT FOR SCOPE OF WORK.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE PLANS NEED TO SHOW HOW AND
 WHERE INTERIOR LIGHTING IS BEING FED, CONTROLLED ETC.
 PLEASE SEE NOTES FROM FIRE MARSHAL ALSO AS MINIMUM
 LIGHTING FOR EMERGENCY ILLUMINATION OF SOME SORT WILL
 BE REQUIRED PER LS 7.8 AND 7.9.
 PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING.
 PLEASE VERIFY AND STATE ON PLANS IF THERE ARE ANY OTHER
 EXISTING LIGHTING FIXTURES WHICH MAY BE ENERGIZED OR
 LOCATED AT PROPERTY.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE FOR
 EXTERIOR PER 13-415.2, 13-415.2.ABC.1.3.
 PLEASE BE SURE TO INCLUDE FIXTURE SCHEDULE FOR NEW
 FIXTURES.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF
 EXTERIOR LIGHTING.
  
 5) NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) FOR NEW
 LIGHTING BEING SHOWN ON PLANS. PLEASE COMPLETE THE
 CIRCUITS ON PLANS. BRANCH CIRCUIT(S), SIZE OF OVER
 CURRENT PROTECTION, CONDUCTOR SIZES ETC.
 240.4, 310.16, 408.4 ETC
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE LOCATION OF THE SERVICE IS IN
 QUESTION AS THE SERVICE DROP APPEARS TO NOT MEET 230
 PART I OR PART II. THERE IS NOT ENOUGH INFORMATION.
 PLEASE SEE RISER WHICH ONLY SHOWS A BOX WHICH STATES
 400A SINGLE PHASE. WHAT IS THIS? THIS CAN BE ASSUMED
 THIS IS A METER HOWEVER PLANS NEED TO BE SPECIFIC FOR
 ALL ELECTRICAL EQUIPMENT.
  
 7) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AND
 FEEDERS ARE NOT RATED FOR THE 150AMP MAINS OR PANELS
 PER 310.16.
 ** THIS IS NOT A RESIDENCE AND 310.15B6 MAY NOT BE
 USED.
 240.4, 310.16.
  
 8) NOTE: PLEASE SEE 250.6 AND 250.24 AS *EQUIPMENT
 GROUNDING CONDUCTORS* ARE NOT PERMITTED AHEAD OF THE
 FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY
 DESIGN PROFESSIONAL. PLEASE SEE FBC 105.3.1.2, FS
 481.229, 471.003, 489.
  
 10) NOTE: PLEASE SEE PANEL *A* MAY NOT BE LOCATED IN
 CLOSET AS SHOWN.
 PLEASE SEE110.26, 240.24, 408.17
  
 11) NOTE: PLEASE SUBMIT THE AIC RATINGS PER 110.9.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE MISSING COLD WATER PIPE REQUIRED
 TO BE PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 13) NOTE: PLEASE CLARIFY THE CONDUITS SHOWN ON RISER.
 WHAT IS CMT OR EMC?
 110.3, NEC 300, 320-388
  
 14) NOTE: PLEASE PROVIDE INFORMATION ON PLANS IF THIS
 IS A SHELL BUILDING AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2, 110
  
 15) NOTE: PLEASE KNOW THERE IS CURRENTLY A HOLD IN
 SYSTEM FOR EXPIRED PERMITS AT THIS LOCATION PER THE
 CHIEF BUILDING INSPECTOR.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-11-14 Cont ID  
Sent By mwennerg Date 2008-11-14 Time 13:48 Rev Time 0.00
Received By mwennerg Date 2008-11-14 Time 13:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By mwennerg Date 2008-10-21 Time 11:34 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 11:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-13 Cont ID  
Sent By mwennerg Date 2008-03-13 Time 16:11 Rev Time 0.00
Received By mwennerg Date 2008-03-13 Time 16:11 Sent To  
Notes
2008-03-13 16:15:10***DENIED***
  
 1) PLEASE NOTE MORE DETAILS ARE REQUIRED.
  
 2) PLEASE ILLUSTRATE THE LOCATION OF REQUIRED
 ILLUMINATED EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-30 Cont ID  
Sent By adarroug Date 2008-10-30 Time 14:22 Rev Time 0.00
Received By adarroug Date 2008-10-30 Time 14:22 Sent To  
Notes
2008-10-30 14:22:19TO "COMM" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 10:52 Sent To  
Notes
2008-09-29 10:52:41TO "COMM" BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-27 Cont ID  
Sent By lmartine Date 2008-03-25 Time 09:02 Rev Time 0.00
Received By lmartine Date 2008-02-12 Time 15:57 Sent To  
Notes
2008-02-12 16:02:44TO "COMM" BD#47

Review Stop Z ZONING
Rev No 1 Status N Date 2008-02-19 Cont ID  
Sent By choops Date 2008-02-19 Time 10:04 Rev Time 0.00
Received By choops Date 2008-02-19 Time 10:04 Sent To  
Notes
2008-02-19 10:05:04*ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY AND
 THE VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved