Plan Review Details - Permit 08020247
Plan Review Stops For Permit 08020247
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By rmcdouga Date 2008-04-15 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2008-04-15 Time 07:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-22 Cont ID  
Sent By kconrad Date 2008-02-22 Time 15:29 Rev Time 0.00
Received By kconrad Date 2008-02-22 Time 15:29 Sent To I
Notes
2008-02-22 15:30:29PRE-INSPECT APPROVED AS STATED FOR REMAINING
 WORK/VALUATION. VERIFIED BY CJ.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-20 Cont ID  
Sent By rmcdouga Date 2008-02-20 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2008-02-20 Time 16:30 Sent To  
Notes
2008-02-21 06:57:392004 FBC W/2007 REVISIONS
 COMPLETE THE WORK ON A POOL WITH VOIDED PERMIT
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE POOL AND THE STRUCTURES ON THE PROPERTY. FBC
 106.1.1* CITY AMENDMENTS
  
 2) SPECIFY THE SIZE AND TYPE OF POOL DECK. FBC 106.1.1*
 CITY AMENDMENTS
  
 3) A PRE-INSPECTION IS REQUIRED TO DETERMINE THE AMOUNT
 OF WORK THAT HAS BEEN COMPLETED AND THE VALUE FOR THE
 SCOPE OF WORK THAT REMAINS. FBC 108.3* CITY AMENDMENTS
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-02-15 Cont ID  
Sent By btrobaug Date 2008-02-15 Time 15:49 Rev Time 0.00
Received By btrobaug Date 2008-02-15 Time 15:49 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-02-19 Cont ID  
Sent By mperson Date 2008-02-19 Time 13:19 Rev Time 0.00
Received By mperson Date 2008-02-19 Time 13:19 Sent To B
Notes
2008-02-19 13:20:28CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 16:22 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 16:22 Sent To Z
Notes
2008-04-08 16:23:13TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-20 Cont ID  
Sent By rmcdouga Date 2008-02-20 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2008-02-12 Time 08:58 Sent To  
Notes
2008-02-12 08:58:59TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-04-14 Cont ID  
Sent By mperson Date 2008-04-14 Time 15:35 Rev Time 0.00
Received By mperson Date 2008-04-14 Time 15:35 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By mperson Date 2008-02-19 Time 13:14 Rev Time 0.00
Received By mperson Date 2008-02-19 Time 13:14 Sent To G
Notes
2008-02-19 13:19:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT TWO COPIES OF THE
 PROPOSED GAS POOL HEATER CLEARLY INDICATING THE MAKE,
 MODEL NUMBER AND A LISTING FROM A NATIONALLY RECOGNZED
 TESTING LABORATORY)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-09 Cont ID  
Sent By choops Date 2008-04-09 Time 15:25 Rev Time 0.00
Received By choops Date 2008-04-09 Time 15:25 Sent To P
Notes
2008-04-09 15:29:19***APPROVED - RESUB #1***
  
 PROVISO:"CHILD BARRIER" DOES NOT SATISFY THE ZONING
 REQUIREMENT FOR A FENCE ENCLOSURE.POOL AREA MUST BE
 COMPLETELY ENCLOSED BY A SCREEN ENCLOSURE OR PERMANENT
 FENCE THAT MEETS THE REQUIREMENTS PROVIDED BELOW:
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
  
  
  
 SENT TO "P" - MP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-13 Cont ID  
Sent By choops Date 2008-02-13 Time 15:09 Rev Time 0.00
Received By choops Date 2008-02-13 Time 15:09 Sent To E
Notes
2008-02-13 15:11:05***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE SETBACK DIMENSIONS FROM WATER'S EDGE TO ALL
 PROPERTY LINES.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 3)AS THE SITE PLAN DOES NOT SHOW AN EXISTING
 PERMANENT FENCE COMPLETELY SURROUNDING THE POOL, A
 FENCE PERMIT SHALL BE SUBMITTED CONCURRENTLY AND SHALL
 CONFORM TO THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720