Plan Review Details - Permit 08020236
Plan Review Stops For Permit 08020236
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-03-24 Cont ID  
Sent By shill Date 2009-03-24 Time 17:42 Rev Time 0.00
Received By shill Date 2009-03-24 Time 17:42 Sent To  
Notes
2009-03-24 17:42:26REVISION, SHEET AR102
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-02-27 Cont ID  
Sent By shill Date 2009-02-27 Time 16:23 Rev Time 0.00
Received By shill Date 2009-02-27 Time 16:23 Sent To  
Notes
2009-02-27 16:25:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLANS SUBMITTED ARE FOR PHASE V (SUITE 280). THIS
 PERMIT IS FOR PHASE IV, DR. JONES BUILDOUT. OUR RECORDS
 SHOW SUITE 280 UNDER PERMIT 08080450.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-06 Cont ID  
Sent By shill Date 2008-06-06 Time 10:38 Rev Time 0.00
Received By shill Date 2008-06-06 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-12 Cont ID  
Sent By shill Date 2008-05-12 Time 15:28 Rev Time 0.00
Received By shill Date 2008-05-12 Time 15:28 Sent To  
Notes
2008-05-12 15:29:09****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE SEE PLUMBING COMMENTS AND REVISE DETAILS AS
 NECESSARY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-21 Cont ID  
Sent By shill Date 2008-02-21 Time 15:04 Rev Time 0.00
Received By shill Date 2008-02-21 Time 15:04 Sent To  
Notes
2008-02-21 15:04:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE CLARIFY SCOPE OF WORK.BASED ON THE PLANS,
 IT APPEARS THAT THIS IS A SECOND FLOOR BUILDOUT.
 HOWEVER, GV102, SE CORNER, STATES "BUILDING OUTSIDE
 SCOPE OF WORK PERMITTED UNDER PHASE II AND PHASE III".
 FROM THE LANGUAGE IT APPEARS THAT THIS AREA HIGHLIGHTED
 IS NOT WITHIN THE SCOPE OF THIS WORK, "OUTSIDE SCOPE OF
 WORK", BUT I THINK THAT THE LANGUAGE MEANS EXTERIOR. IS
 THIS CORRECT?THE LABEL "SCOPE OF WORK" APPEARS IN
 TWO PLACES BUT DOESN'T POINT TO ANYTHING.SCOPE OF
 WORK IS CLARIFIED ON OTHER SHEETS BUT PLEASE REVISE
 THIS SHEET FOR CONSISTENCY.
  
 2.ROOM 272 IS REQUIRED TO BE ADAPTABLE
 FBC11-4.1.3(11).PLEASE SHOW THE TURNING RADIUS,
 FBC11-4.22.3, CLEAR FLOOR SPACE REQUIRED FOR FIXTURES,
 FBC11-4.22.3.DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE FOR ANY FIXTURE FBC1104.22.2(1). LAVATORIES
 AND MIRRORS TO COMPLY WITH FBC11-4.19.
  
 3.ROOM 272, PROVIDE A BACKING DETAIL FOR GRAB BARS.
  
 4.THE STAFF TOILET ROOM, ROOM 275, IS TO BE
 ACCESSIBLE FBC11-4.1.3(11).THE LAVATORY AND MIRRORS
 TO COMPLY WITH FBC11-4.19, CLEAR FLOOR SPACE TO BE
 SHOWN ON THE PLAN, TURNING RADIUS FBC11-4.22.3, GRAB
 BARS FBC11-4.26.2.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-24 Cont ID  
Sent By dpalmer Date 2009-03-24 Time 19:31 Rev Time 0.00
Received By dpalmer Date 2009-03-24 Time 19:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-19 Cont ID  
Sent By dpalmer Date 2008-05-19 Time 08:33 Rev Time 0.00
Received By dpalmer Date 2008-05-19 Time 08:33 Sent To  
Notes
2008-05-19 08:37:07REDLINED THE FOLLOWING ITEMS ON PLANS.
  
  
 1) THE LIGHTING POWERE DENSITIES PER 13-415.2 ARE
 ATTACHED TO LIGHTING SHEETS.
  
 2) THE DESIGNATION OF THE IT ROOM WAS CHANGED TO A
 COMMUNICATIONS ROOM. NO WIRING METHODS ALLOWED IN NEC
 645 ARE PERMITTED TO BE USED. MUST COMPLY WITH ALL
 WIRING METHODS OF NEC CHAPTERS 1-4.
 WIRING METHODS OF 645 ARE ONLY PERMITTED WHEN A TRUE IT
 ROOM MEETING ALL ITEMS AS LISTED IN 645.2.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICLA PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-15 Cont ID  
Sent By dpalmer Date 2008-02-15 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2008-02-15 Time 15:41 Sent To  
Notes
2008-02-15 15:41:24*** DENIEDREVIEW***
  
  
 1) NOTE: PLEASE CLARIFY THE METHOD *B* CALCULATIONS
 BEING SUBMITTED FOR SPACE WHICH ALREADY HAS ASSUMPTIONS
 ON THE ORIGINAL PHASE PERMIT.
 PLEASE SEE 13-400.3.B, 13-400.2.A. WHICH INDICATES
 SHELL BUILDINGS. PLEASE SEE THIS SPACE DOES NOT MEET
 RENOVATED BUILDING SO PLEASE VERIFY METHOD SUBMITTED.
 THESE WERE SUBMITTED ALONG WITH SPACE BY SPACE
 CALCULATIONS PER 13-415.2
 ** PLEASE SEE THAT IN ANY CASE THERE ARE SPACES NOTED
 ON THE IDR WHICH INDICATES MANUAL ON/OFF CONTROLS WHEN
 THESE ARE ACTUALLY AUTOMATED ON PLANS.
  
 2) NOTE: PLEASE INCLUDE NOTES AND DESIGNS ON PLANS FOR
 517.1, AND 517 PART II.
  
 3) NOTE: PLANS SHOW NEW IT ROOM HOWEVER AT THIS TIME NO
 REVIEW OF ITEMS FOR THIS ROOM FALLING UNDER THE
 DEFINITIONS OF 645.4 CAN BE FOUND. IF THIS IS A TRUE IT
 ROOM PLEASE ADJUST ELECTRICAL, MECHANICAL AND BUILDING
 PLANS ACCORDINGLY.
  
 4) NOTE: PLEASE SEE ANY COMMENTS UNDER OTHER SUBMITTED
 REVISION WHICH MAY AFFECT SPACE.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-03-25 Cont ID  
Sent By mawillia Date 2009-03-25 Time 11:20 Rev Time 0.00
Received By mawillia Date 2009-03-25 Time 11:02 Sent To  
Notes
2009-03-25 11:16:02*****REVISION #2, APPROVED*****
  
  
 REVISED PLAN SHEETS AR-102, EL-102, AND EA-102 WERE
 STAMPED, INITIALEDL, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-05-19 Time 13:40 Rev Time 0.00
Received By mawillia Date 2008-05-19 Time 12:56 Sent To  
Notes
2008-05-19 13:24:23*****APPROVED*****
  
  
 PLAN SHEETS GV-102, AR-102, FD-102, FK-102, EL-102, AND
 EA-102 WERE STAMPED, INITIALEDLED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-05-19 Time 13:10 Rev Time 0.00
Received By mawillia Date 2008-05-19 Time 12:59 Sent To  
Notes
2008-05-19 13:11:07SEE 3RD REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-23 Cont ID  
Sent By mawillia Date 2008-03-22 Time 23:37 Rev Time 0.00
Received By mawillia Date 2008-03-22 Time 22:31 Sent To  
Notes
2008-03-23 00:12:00*****PROVISO*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 BELOW COMMENTS AS WELL AS THE OTHER PLAN REVIEWERS
 COMMENTS HAVE BEEN ADDRESSED
  
  
 1.PLANS SHOW THAT THERE WILL BE AT LEAST ONE MORE
 TENANT ON THE SECOND FLOOR BESIDES DR JONES' BUILDOUT.
 PROVIDE TENANT SPACE NUMBER AS TO BE DISTINGUISHABLE
 FROM OTHER TENANT SPACE(S) ON THE SECOND FLOOR.(THE
 SUITE NUMBER SHALL BE INCLUDED IN THE ADDRESS LISTED IN
 THE TITLE BLOCK OF THE APPROPIATE PLAN SHEETS.)
  
 2.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 16:49 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 16:49 Sent To  
Notes
2009-01-30 16:50:11TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 09:08 Sent To  
Notes
2008-05-30 09:18:23TO "COMM" BD#51/PLANS ON RACK, 3 ROLLS AND 2 BOOKS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 16:33 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 16:33 Sent To  
Notes
2008-05-01 16:34:06TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-22 Time 11:01 Rev Time 0.00
Received By adarroug Date 2008-02-11 Time 11:34 Sent To  
Notes
2008-02-11 11:38:50TO "COMM" BD#39

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-03-24 Cont ID  
Sent By rregueir Date 2009-03-24 Time 19:53 Rev Time 0.00
Received By rregueir Date 2009-03-24 Time 19:53 Sent To  
Notes
2009-03-24 19:53:23REVISED MH-102 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-02 Cont ID  
Sent By tgordon Date 2008-05-02 Time 09:06 Rev Time 1.00
Received By tgordon Date 2008-05-02 Time 09:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-02-29 Cont ID  
Sent By tgordon Date 2008-02-29 Time 11:42 Rev Time 1.00
Received By tgordon Date 2008-02-29 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-06 Cont ID  
Sent By jleech Date 2008-06-06 Time 08:03 Rev Time 0.00
Received By jleech Date 2008-06-06 Time 08:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-06 Cont ID  
Sent By jleech Date 2008-05-06 Time 08:59 Rev Time 0.00
Received By jleech Date 2008-05-06 Time 07:58 Sent To  
Notes
2008-05-06 09:09:38DENIED;
 1.(ROOM 272) PAGE AF-102 SHOWS WIDTH OF ROOM AS 6'-1"S.
 DETAIL 3, SAME PAGE 4'-11 1/2" TO CENTER OF LAVATORY
 FLOOR PLAN SHOWS 5'. PAGE AF-406 DETAIL 7 SHOWS WIDTH
 OF ROOM IS 5'-3"S. PLEASE SHOW ALL, DETAIL AND FLOOR
 PLAN THE SAME.
 2. FLOOR PLAN NOT UP DATED ON PAGES 1N-102, AND
 1N-202.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-19 Cont ID  
Sent By jleech Date 2008-03-19 Time 08:28 Rev Time 0.00
Received By jleech Date 2008-03-19 Time 08:26 Sent To  
Notes
2008-03-19 08:47:26DENIED;
 1. ROOM 272 PRIVATE BATHROOM IS REQUIRED TO BE
 ADAPTABLE PER FBC BUILDING CHAPTER 11 SECTION
 11-4.1.3(11). SHOW DETAIL WITH WIDTH AND LENGTH
 MEASUREMENTS. W/C TO BE 18" OFF WALL AND SHOW TURNING
 RADIUS.
 2. STAFF BATHROOM # 275 NOT TO ACCESSIBILITY CODE
 SECTION 11-4.1.2.
 (A) DOOR SWINGS INTO THE CLEAR FLOOR SPACE OF
 THE LAVATORY. SECTION 11-4.22.2(1).
 (B) TURNING RADIUS IN BATHROOM REQUIRED, SEE
 SECTION 11-4.22.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2008-02-19 Cont ID  
Sent By lfranco Date 2008-02-19 Time 17:09 Rev Time 0.00
Received By lfranco Date 2008-02-19 Time 17:09 Sent To  
Notes
***NONE***