Plan Review Stops For Permit 08020236 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2009-03-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-03-24 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-03-24 |
Time |
17:42 |
Sent To |
|
|
Notes |
2009-03-24 17:42:26 | REVISION, SHEET AR102 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2009-02-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-02-27 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-02-27 |
Time |
16:23 |
Sent To |
|
|
Notes |
2009-02-27 16:25:09 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PLANS SUBMITTED ARE FOR PHASE V (SUITE 280). THIS | | PERMIT IS FOR PHASE IV, DR. JONES BUILDOUT. OUR RECORDS | | SHOW SUITE 280 UNDER PERMIT 08080450. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-06-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-06-06 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-06-06 |
Time |
10:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-05-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-05-12 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-05-12 |
Time |
15:28 |
Sent To |
|
|
Notes |
2008-05-12 15:29:09 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.PLEASE SEE PLUMBING COMMENTS AND REVISE DETAILS AS | | NECESSARY. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-02-21 |
Time |
15:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-02-21 |
Time |
15:04 |
Sent To |
|
|
Notes |
2008-02-21 15:04:39 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.PLEASE CLARIFY SCOPE OF WORK.BASED ON THE PLANS, | | IT APPEARS THAT THIS IS A SECOND FLOOR BUILDOUT. | | HOWEVER, GV102, SE CORNER, STATES "BUILDING OUTSIDE | | SCOPE OF WORK PERMITTED UNDER PHASE II AND PHASE III". | | FROM THE LANGUAGE IT APPEARS THAT THIS AREA HIGHLIGHTED | | IS NOT WITHIN THE SCOPE OF THIS WORK, "OUTSIDE SCOPE OF | | WORK", BUT I THINK THAT THE LANGUAGE MEANS EXTERIOR. IS | | THIS CORRECT?THE LABEL "SCOPE OF WORK" APPEARS IN | | TWO PLACES BUT DOESN'T POINT TO ANYTHING.SCOPE OF | | WORK IS CLARIFIED ON OTHER SHEETS BUT PLEASE REVISE | | THIS SHEET FOR CONSISTENCY. | | | | 2.ROOM 272 IS REQUIRED TO BE ADAPTABLE | | FBC11-4.1.3(11).PLEASE SHOW THE TURNING RADIUS, | | FBC11-4.22.3, CLEAR FLOOR SPACE REQUIRED FOR FIXTURES, | | FBC11-4.22.3.DOORS SHALL NOT SWING INTO THE CLEAR | | FLOOR SPACE FOR ANY FIXTURE FBC1104.22.2(1). LAVATORIES | | AND MIRRORS TO COMPLY WITH FBC11-4.19. | | | | 3.ROOM 272, PROVIDE A BACKING DETAIL FOR GRAB BARS. | | | | 4.THE STAFF TOILET ROOM, ROOM 275, IS TO BE | | ACCESSIBLE FBC11-4.1.3(11).THE LAVATORY AND MIRRORS | | TO COMPLY WITH FBC11-4.19, CLEAR FLOOR SPACE TO BE | | SHOWN ON THE PLAN, TURNING RADIUS FBC11-4.22.3, GRAB | | BARS FBC11-4.26.2. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2009-03-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-24 |
Time |
19:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-24 |
Time |
19:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-05-19 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-19 |
Time |
08:33 |
Sent To |
|
|
Notes |
2008-05-19 08:37:07 | REDLINED THE FOLLOWING ITEMS ON PLANS. | | | | | | 1) THE LIGHTING POWERE DENSITIES PER 13-415.2 ARE | | ATTACHED TO LIGHTING SHEETS. | | | | 2) THE DESIGNATION OF THE IT ROOM WAS CHANGED TO A | | COMMUNICATIONS ROOM. NO WIRING METHODS ALLOWED IN NEC | | 645 ARE PERMITTED TO BE USED. MUST COMPLY WITH ALL | | WIRING METHODS OF NEC CHAPTERS 1-4. | | WIRING METHODS OF 645 ARE ONLY PERMITTED WHEN A TRUE IT | | ROOM MEETING ALL ITEMS AS LISTED IN 645.2. | | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | OFFICE. | | | | DEWEY PALMER | | ELECTRICLA PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-15 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-15 |
Time |
15:41 |
Sent To |
|
|
Notes |
2008-02-15 15:41:24 | *** DENIEDREVIEW*** | | | | | | 1) NOTE: PLEASE CLARIFY THE METHOD *B* CALCULATIONS | | BEING SUBMITTED FOR SPACE WHICH ALREADY HAS ASSUMPTIONS | | ON THE ORIGINAL PHASE PERMIT. | | PLEASE SEE 13-400.3.B, 13-400.2.A. WHICH INDICATES | | SHELL BUILDINGS. PLEASE SEE THIS SPACE DOES NOT MEET | | RENOVATED BUILDING SO PLEASE VERIFY METHOD SUBMITTED. | | THESE WERE SUBMITTED ALONG WITH SPACE BY SPACE | | CALCULATIONS PER 13-415.2 | | ** PLEASE SEE THAT IN ANY CASE THERE ARE SPACES NOTED | | ON THE IDR WHICH INDICATES MANUAL ON/OFF CONTROLS WHEN | | THESE ARE ACTUALLY AUTOMATED ON PLANS. | | | | 2) NOTE: PLEASE INCLUDE NOTES AND DESIGNS ON PLANS FOR | | 517.1, AND 517 PART II. | | | | 3) NOTE: PLANS SHOW NEW IT ROOM HOWEVER AT THIS TIME NO | | REVIEW OF ITEMS FOR THIS ROOM FALLING UNDER THE | | DEFINITIONS OF 645.4 CAN BE FOUND. IF THIS IS A TRUE IT | | ROOM PLEASE ADJUST ELECTRICAL, MECHANICAL AND BUILDING | | PLANS ACCORDINGLY. | | | | 4) NOTE: PLEASE SEE ANY COMMENTS UNDER OTHER SUBMITTED | | REVISION WHICH MAY AFFECT SPACE. | | | | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY | | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR | | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN | | CONTACTING THIS REVIEWER. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2009-03-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-03-25 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-03-25 |
Time |
11:02 |
Sent To |
|
|
Notes |
2009-03-25 11:16:02 | *****REVISION #2, APPROVED***** | | | | | | REVISED PLAN SHEETS AR-102, EL-102, AND EA-102 WERE | | STAMPED, INITIALEDL, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-05-19 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-05-19 |
Time |
12:56 |
Sent To |
|
|
Notes |
2008-05-19 13:24:23 | *****APPROVED***** | | | | | | PLAN SHEETS GV-102, AR-102, FD-102, FK-102, EL-102, AND | | EA-102 WERE STAMPED, INITIALEDLED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
N |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-05-19 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-05-19 |
Time |
12:59 |
Sent To |
|
|
Notes |
2008-05-19 13:11:07 | SEE 3RD REVIEW |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-03-23 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-03-22 |
Time |
23:37 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-03-22 |
Time |
22:31 |
Sent To |
|
|
Notes |
2008-03-23 00:12:00 | *****PROVISO***** | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE | | BELOW COMMENTS AS WELL AS THE OTHER PLAN REVIEWERS | | COMMENTS HAVE BEEN ADDRESSED | | | | | | 1.PLANS SHOW THAT THERE WILL BE AT LEAST ONE MORE | | TENANT ON THE SECOND FLOOR BESIDES DR JONES' BUILDOUT. | | PROVIDE TENANT SPACE NUMBER AS TO BE DISTINGUISHABLE | | FROM OTHER TENANT SPACE(S) ON THE SECOND FLOOR.(THE | | SUITE NUMBER SHALL BE INCLUDED IN THE ADDRESS LISTED IN | | THE TITLE BLOCK OF THE APPROPIATE PLAN SHEETS.) | | | | 2.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2009-01-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-01-30 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-01-30 |
Time |
16:49 |
Sent To |
|
|
Notes |
2009-01-30 16:50:11 | TO "COMM" BD#16 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-05-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-30 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-30 |
Time |
09:08 |
Sent To |
|
|
Notes |
2008-05-30 09:18:23 | TO "COMM" BD#51/PLANS ON RACK, 3 ROLLS AND 2 BOOKS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-01 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-01 |
Time |
16:33 |
Sent To |
|
|
Notes |
2008-05-01 16:34:06 | TO "COMM" BD#60 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-03-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-22 |
Time |
11:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-11 |
Time |
11:34 |
Sent To |
|
|
Notes |
2008-02-11 11:38:50 | TO "COMM" BD#39 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2009-03-24 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-03-24 |
Time |
19:53 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-03-24 |
Time |
19:53 |
Sent To |
|
|
Notes |
2009-03-24 19:53:23 | REVISED MH-102 DELTA 2 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2008-05-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-02 |
Time |
09:06 |
Rev Time |
1.00 |
Received By |
tgordon |
Date |
2008-05-02 |
Time |
09:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2008-02-29 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-02-29 |
Time |
11:42 |
Rev Time |
1.00 |
Received By |
tgordon |
Date |
2008-02-29 |
Time |
11:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2008-06-06 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-06-06 |
Time |
08:03 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-06-06 |
Time |
08:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-05-06 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-05-06 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-05-06 |
Time |
07:58 |
Sent To |
|
|
Notes |
2008-05-06 09:09:38 | DENIED; | | 1.(ROOM 272) PAGE AF-102 SHOWS WIDTH OF ROOM AS 6'-1"S. | | DETAIL 3, SAME PAGE 4'-11 1/2" TO CENTER OF LAVATORY | | FLOOR PLAN SHOWS 5'. PAGE AF-406 DETAIL 7 SHOWS WIDTH | | OF ROOM IS 5'-3"S. PLEASE SHOW ALL, DETAIL AND FLOOR | | PLAN THE SAME. | | 2. FLOOR PLAN NOT UP DATED ON PAGES 1N-102, AND | | 1N-202. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-03-19 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2008-03-19 |
Time |
08:28 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2008-03-19 |
Time |
08:26 |
Sent To |
|
|
Notes |
2008-03-19 08:47:26 | DENIED; | | 1. ROOM 272 PRIVATE BATHROOM IS REQUIRED TO BE | | ADAPTABLE PER FBC BUILDING CHAPTER 11 SECTION | | 11-4.1.3(11). SHOW DETAIL WITH WIDTH AND LENGTH | | MEASUREMENTS. W/C TO BE 18" OFF WALL AND SHOW TURNING | | RADIUS. | | 2. STAFF BATHROOM # 275 NOT TO ACCESSIBILITY CODE | | SECTION 11-4.1.2. | | (A) DOOR SWINGS INTO THE CLEAR FLOOR SPACE OF | | THE LAVATORY. SECTION 11-4.22.2(1). | | (B) TURNING RADIUS IN BATHROOM REQUIRED, SEE | | SECTION 11-4.22.3. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2008-02-19 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2008-02-19 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2008-02-19 |
Time |
17:09 |
Sent To |
|
|
Notes |
|
|