Plan Review Details - Permit 08020225
Plan Review Stops For Permit 08020225
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-04-11 Cont ID  
Sent By mperson Date 2008-04-11 Time 13:15 Rev Time 0.00
Received By mperson Date 2008-04-11 Time 13:15 Sent To PC
Notes
2008-04-11 13:18:21REVISION: "OK" CHANGE STATUS OF GENERATOR FROM "FUTERE"
 TO "NEW". GENERATOR IS APPROVED ON GEN/RES PERMIT
 #08030277.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-03-03 Cont ID  
Sent By mperson Date 2008-03-03 Time 08:03 Rev Time 0.00
Received By mperson Date 2008-03-03 Time 08:03 Sent To PC
Notes
2008-03-03 08:12:59 
 ****************PROVISO****************
 FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-02-29 Cont ID  
Sent By mperson Date 2008-02-29 Time 09:06 Rev Time 0.00
Received By mperson Date 2008-02-29 Time 08:19 Sent To PC
Notes
2008-02-29 09:18:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NOTE: THERE WERE NO COMMENT RESPONSES TO THE GAS PLAN
 REVIEW FROM THE DESIGNER.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. AT A MINIMUM GAS PLANS SHALL REFLECT THE PERMIT
 APPLICATION. THE PERMIT APPLICATION HAS DELETED THE
 GENERATOR. PLEASE CORRELATE THE PLANS WITH THE PERMIT
 APPLICATION AND DELETE THE PIPING AND FITTINGS TO THE
 GENERATOR. PER FBC-2004 FUEL GAS, SECTION *401.1
 SCOPE.
  
 **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED ON
 RESUBMIITED PLANS. NOTE: A SEPERATE RESIDENTIAL
 GENERATOR PERMIT IS REQUIRED FOR THE GENERATOR. PERMIT
 INFORMATION FOR SAID ADDRESS 6202 WASHINGTON RD.
 INDICATES THAT THERE HAS NOT BEEN A GEN/RES PERMIT
 APPLIED FOR. REFERENCE THE PERMIT INFORMATION ATTACHED
 TO THESE GAS COMMENTS INDICATING THIS.
  
 3. **OK** COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By mperson Date 2008-02-11 Time 15:22 Rev Time 0.00
Received By mperson Date 2008-02-11 Time 15:22 Sent To PC
Notes
2008-02-11 15:32:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 **THE SUBMITTED ISOMETRIC IS NOT INDICATING THE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE ON
 THE PROPOSED POOL HEATER. REFERENCE THE RED CIRCLED
 AREAS HIGH LIGHTED YELLOW INDICATING THIS.
  
 2. AT A MINIMUM GAS PLANS SHALL REFLECT THE PERMIT
 APPLICATION. THE PERMIT APPLICATION HAS DELETED THE
 GENERATOR. PLEASE CORRELATE THE PLANS WITH THE PERMIT
 APPLICATION AND DELETE THE PIPING AND FITTINGS TO THE
 GENERATOR. PER FBC-2004 FUEL GAS, SECTION *401.1
 SCOPE.
  
 3. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-09 Cont ID  
Sent By adarroug Date 2008-04-09 Time 14:21 Rev Time 0.00
Received By adarroug Date 2008-04-09 Time 14:21 Sent To G
Notes
2008-04-09 14:24:17TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-29 Cont ID  
Sent By mperson Date 2008-02-11 Time 08:17 Rev Time 0.00
Received By mperson Date 2008-02-11 Time 08:16 Sent To  
Notes
***NONE***