Plan Review Details - Permit 08020195
Plan Review Stops For Permit 08020195
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-04-09 Cont ID  
Sent By mperson Date 2008-04-09 Time 11:23 Rev Time 0.00
Received By mperson Date 2008-04-09 Time 11:22 Sent To PC
Notes
2008-04-09 11:25:03REVISION: CSST PIPING SIZED TO GASTITE TABLE 7-1.
  
 ****************PROVISO****************
 A} PER FBC MECHANICAL, SECTION *303.4 PROTECTION FROM
 DAMAGE. APPLIANCES (WATER HEATER IN GARAGE) SHALL NOT
 BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS.
  
 B} PER FBC FUEL GAS, SECTION *409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-02-11 Cont ID  
Sent By mperson Date 2008-02-11 Time 10:19 Rev Time 0.00
Received By mperson Date 2008-02-11 Time 10:19 Sent To PC
Notes
2008-02-11 10:27:19****************PROVISO****************
 A} PER FBC MECHANICAL, SECTION *303.4 PROTECTION FROM
 DAMAGE. APPLIANCES (WATER HEATER IN GARAGE) SHALL NOT
 BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS.
  
 B} PER FBC FUEL GAS, SECTION *409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 14:54 Sent To G
Notes
2008-04-08 14:54:42TO "G" BOX/REV