Plan Review Stops For Permit 08020194 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2008-02-11 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-02-11 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-02-11 |
Time |
08:25 |
Sent To |
PC |
|
Notes |
2008-02-11 08:27:39 | ****************PROVISO**************** | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | INGS REQUIRED PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. | | MINIMUM 2,500 CUBIC FEET REQUIRED. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] | | | | ****************PROVISO**************** | | PER FBC MECHANICAL SECTION 303.4 PROTECTION FROM | | DAMAGE. APPLIANCES (WATER HEATER IN GARAGE) SHALL NOT | | BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL | | DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
|