Plan Review Details - Permit 08020160
Plan Review Stops For Permit 08020160
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-02-26 Cont ID  
Sent By lursu Date 2008-02-26 Time 08:18 Rev Time 0.00
Received By lursu Date 2008-02-26 Time 08:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-02-26 Cont ID  
Sent By shill Date 2009-02-26 Time 08:36 Rev Time 0.00
Received By shill Date 2009-02-26 Time 08:36 Sent To  
Notes
2009-02-26 09:10:48AUDIT - REVISED SHEETS A201, A502

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-11-18 Cont ID  
Sent By shill Date 2008-11-18 Time 10:49 Rev Time 0.00
Received By shill Date 2008-11-18 Time 10:43 Sent To  
Notes
2008-11-18 10:50:44AUDIT - REVISED SHEETS A0201, A0501, A0502, A1001 DATED
 9/30/8
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-10-28 Cont ID  
Sent By rbrown Date 2008-10-28 Time 10:37 Rev Time 0.00
Received By rbrown Date 2008-10-28 Time 10:36 Sent To  
Notes
2008-10-28 10:39:34ARCHITECT'S 8.5" X 11" SHEET SUBMITTAL DETAILING RATED
 WALL CONSTRUCTION AROUND THE BACK SIEMAN'S CHASE IN
 X-RAY ROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-22 Cont ID  
Sent By shill Date 2008-09-22 Time 10:56 Rev Time 0.00
Received By shill Date 2008-09-22 Time 10:56 Sent To  
Notes
2008-09-22 10:57:24PRIVATE PROVIDER AUDIT
 REVISION DATED 7/23 AND 731/8, SHEETS G0001, G0201,
 A0001, A201, A203, A401, A501, A502, A701, A1001, A1002
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-24 Cont ID  
Sent By shill Date 2008-06-24 Time 13:26 Rev Time 0.00
Received By shill Date 2008-06-24 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By shill Date 2008-05-20 Time 16:44 Rev Time 0.00
Received By shill Date 2008-05-20 Time 16:16 Sent To  
Notes
2008-05-20 16:35:42****AUDIT****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE CORRECT CERTIFICATE OF AUTHORIZATION LICENSE
 NUMBER FOR THE ARCHITECT BUSINESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-14 Cont ID  
Sent By jwitmer Date 2008-02-14 Time 14:44 Rev Time 2.22
Received By jwitmer Date 2008-02-14 Time 14:44 Sent To  
Notes
2008-02-14 14:45:51BUILDING PLAN REVIEW
 PERMIT: 08020160
 ADD: 525 OKEECHOBEE BLVD
 SUITE 1400
 CONT: BALFOUR BEATTY
 TEL: (772)215-3063
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS SHEET G0201 NEEDS
 TO UPDATE TO THE 2007 FBC UPDATES( SUBMITTALS) .
  
 2) URS- THEY ARE MISSING THEIR CERTIFICATE OF
 AUTHORIZATION. 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH
 SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) SHEET G0201 INDICATES THE USE OF X-RAY MACHINES.
 PLEASE PROVIDE THE PLANS SUBMITTED TO THE DEPARTMENT OF
 HEALTH FOR REVIEW AND APPROVAL. 435.5.1.3 PRIOR TO
 CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT ARRANGEMENT
 OF ALL NEW INSTALLATIONS, OR MODIFICATIONS OF EXISTING
 INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND
 ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE
 SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND
 APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER
 REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE
 FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
 435.5.1.3.1
 THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING:
 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S
 RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED. 435.5.1.3.1.3
 THE DIMENSIONS OF THE ROOM CONCERNED. 435.5.1.3.1.4 THE
 TYPE OF OCCUPANCY OF ALL ADJACENT AREAS INCLUSIVE OF
 SPACE ABOVE AND BELOW THE ROOM CONCERNED. IF THERE IS
 AN EXTERIOR WALL, THE DISTANCE TO THE CLOSEST AREA
 WHERE IT IS LIKELY THAT INDIVIDUALS MAY BE PRESENT.
 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT.
 435.5.1.3.2
 INFORMATION SHALL BE SUBMITTED ON THE ANTICIPATED
 MAXIMUM WORKLOAD OF THE X-RAY SYSTEM.
 435.5.1.3.3
 IF THE SERVICES OF A QUALIFIED PERSON HAVE BEEN
 UTILIZED TO DETERMINE THE SHIELDING REQUIREMENTS, A
 COPY OF THE REPORT, INCLUDING ALL BASIC ASSUMPTIONS
 USED, SHALL BE SUBMITTED WITH THE PLANS.
  
 4) SHEET G0201- HANDICAPPED RESTROOM, PLANS INDICATE
 THEDOOR SWINGING INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR FIXTURES PLEASE SEE PLAN. 11-4.22.3.
  
 5)SHEETGO201- MISSING INFORMATION ON THE CHANGING
 ROOMS OR DRESSING ROOMS: 11-4.35 DRESSING AND FITTING
 ROOMS.
  
 11-4.35.1 GENERAL.
 DRESSING AND FITTING ROOMS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.35 AND
 SHALL BE ON AN ACCESSIBLE ROUTE.
  
 11-4.35.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE ALLOWING A PERSON USING A
 WHEELCHAIR TO MAKE A 180-DEGREE TURN SHALL BE PROVIDED
 IN EVERY ACCESSIBLE DRESSING ROOM ENTERED THROUGH A
 SWINGING OR SLIDING DOOR. NO DOOR SHALL SWING INTO ANY
 PART OF THE TURNING SPACE. TURNING SPACE SHALL NOT BE
 REQUIRED IN A PRIVATE DRESSING ROOM ENTERED THROUGH A
 CURTAINED OPENING AT LEAST 32 INCHES (815 MM) WIDE IF
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2 RENDERS
 THE DRESSING ROOM USABLE BY A PERSON USING A
 WHEELCHAIR.
  
 11-4.35.3 DOORS.
 ALL DOORS TO ACCESSIBLE DRESSING ROOMS SHALL BE IN
 COMPLIANCE WITH SECTION 11-4.13 .
  
 11-4.35.4 BENCH.
 EVERY ACCESSIBLE DRESSING ROOM SHALL HAVE A 24 INCHES
 BY 48 INCHES (610 MM BY 1219 MM) BENCH FIXED TO THE
 WALL ALONG THE LONGER DIMENSION. THE BENCH SHALL BE
 MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM) ABOVE
 THE FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE PROVIDED
 ALONGSIDE THE BENCH TO ALLOW A PERSON USING A
 WHEELCHAIR TO MAKE A PARALLEL TRANSFER ONTO THE BENCH.
 THE STRUCTURAL STRENGTH OF THE BENCH AND ATTACHMENTS
 SHALL COMPLY WITH SECTION 11-4.26.3 . WHERE INSTALLED
 IN CONJUNCTION WITH SHOWERS, SWIMMING POOLS, OR OTHER
 WET LOCATIONS, WATER SHALL NOT ACCUMULATE UPON THE
 SURFACE OF THE BENCH AND THE BENCH SHALL HAVE A
 SLIP-RESISTANT SURFACE.
  
 11-4.35.5 MIRROR.
 WHERE MIRRORS ARE PROVIDED IN DRESSING ROOMS OF THE
 SAME USE, THEN IN AN ACCESSIBLE DRESSING ROOM, A
 FULL-LENGTH MIRROR, MEASURING AT LEAST 18 INCHES WIDE
 BY 54 INCHES HIGH (460 MM BY 1370 MM), SHALL BE MOUNTED
 IN A POSITION AFFORDING A VIEW TO A PERSON ON THE BENCH
 AS WELL AS TO A PERSON IN A STANDING POSITION.
  
 6)A0703 ADA SINK BASE DOES NOT MEET THE TOE CLEARANCE
 REQUIREMENTS NOR DOES THE REMOVABLE WHEELCHAIR ACCESS
 PANEL FOR KNEE CLEARANCES. 11-4.24.3.
  
 7) SHEET A0502 DETAIL ?B? INDICATES 2 HANDICAPPED
 RESTROOMS ONE INDICATES THE DOOR SWING INTO THE CLEAR
 FLOOR SPACE FOR ACCESSIBLE FIXTURES SEE 11-422.3.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-03-30 Cont ID  
Sent By dpalmer Date 2009-03-30 Time 13:43 Rev Time 0.00
Received By dpalmer Date 2009-03-30 Time 13:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2009-03-12 Cont ID  
Sent By dpalmer Date 2009-03-12 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2009-03-12 Time 13:32 Sent To PC
Notes
2009-03-12 13:33:10** DENIED REVISIONS **
  
  
 1) NOTE: PER FS 553.791 ALL REVISIONS TO PRIVATE
 PROVIDER PROJECTS MUST GO BACK TO THE PROVIDER, BE
 REVIEWED, STAMPED AND SUBMIT AFFIDAVITS FOR NEW REVISED
 SHEETS.
 THERE ARE SEVERAL REVISED SHEETS WHICH DO NOT CONTAIN
 THE STAMPED AND NO NEW AFFIDAVITS WERE SUBMITTED.
 PLEASE BE SURE TO CALL IF THERE ARE
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2009-02-23 Cont ID  
Sent By dpalmer Date 2009-02-23 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2009-02-23 Time 14:22 Sent To  
Notes
2009-02-23 14:22:44** DENIED AUDIT **
  
  
  
 1) NOTE: THERE IS STILL NO REVISED LIGHTING PERFORMANCE
 CALCULATIONS SUBMITTED. THERE HAS BEEN AN INCREASE IN
 WATTAGE FROM THE ORIGINAL CALCULATIONS.
 SOME FIXTURES HAVE BEEN REVISED TO ACTUALLY DOUBLE THE
 WATTAGE FROM THE ORIGINAL FIXTURE DESIGNS.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2, 13-415.2.B.2.
 PLEASE BE SURE TO ALSO SUBMIT THE LATEST REVISED
 FIXTURE LEGEND. THE PREVIOUS PLANS WHICH CONTAINED THE
 REVISED FIXTURE LEGEND WERE REJECTED ON THE PREVIOUS
 REVIEW DATED 10/31/2008.
 NO REVISED PLANS ADDRESSING THIS ISSUE HAVE BEEN
 SUBMITTED SINCE THAT DATE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-10-31 Cont ID  
Sent By dpalmer Date 2008-10-31 Time 09:05 Rev Time 0.00
Received By dpalmer Date 2008-10-31 Time 09:05 Sent To  
Notes
2008-10-31 09:05:46 
 ** DENIED REVISION**
  
 1) NOTE: PLEASE SHOW AND DISPLAY ALL REVISIONS AS NOTED
 ON TITLE BLOCKS. FOR EXAMPLE THE LAST REVISION ON
 RECORD TO DATE FOR SHEET E500 IS REVISION #4, WHEREAS
 THE NEW REVISED SHEET CONTAINS REVISION #6. WHERE IS
 REVISION #5 LOCATED ON PLANS? NO CLOUDS OR TRIANGLES
 ARE SHOWN INDICATING THESE REVISIONS. THERE WAS A
 PREVIOUS REV #5 HOWEVER FOR OTHER SHEETS.
 PLEASE COORDINATE PLANS.
 FBC 106.1.1
 FBC CHAPTER 13, NEC 220
  
 2) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE
 CALCULATIONS. AS THE FIXTURES HAVE BEEN REVISED TO
 INCREASE WATTAGES THE PREVIOUSLY SUBMITTED CALCULATIONS
 NO LONGER COORDINATE.
 PLEASE SEE 13-415.2,13-415.2.ABC.1.1,.1.2.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-09-15 Cont ID  
Sent By dpalmer Date 2008-09-15 Time 13:37 Rev Time 0.00
Received By dpalmer Date 2008-09-15 Time 13:36 Sent To  
Notes
2008-09-15 13:37:38REV #5

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-07-09 Cont ID  
Sent By dpalmer Date 2008-07-09 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2008-07-09 Time 14:06 Sent To B
Notes
2008-07-09 14:07:06ENGINEER OF RECORD CAME INTO OFFICE AND PERSONALLY
 SIGNED, DATED AND SEALED ALL ELECTRICAL PLANS.
  
 ** PLANS ROUTED TO LUIS MARTINEZ AS FIRE REVIEW STILL
 NEEDS TO STAMP ELECTRICAL, AND FIRE SHEETS. THIS WAS
 STATED IN PREVIOUS REVIEW NOTES..

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-03 Cont ID  
Sent By dpalmer Date 2008-07-03 Time 11:58 Rev Time 0.00
Received By dpalmer Date 2008-07-03 Time 11:58 Sent To PC
Notes
2008-07-03 11:58:44 
  
 ** DENIED AUDIT**
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED NOW SHOW A
 COMPLETELY DIFFERENT SIGNATURE OF THE DESIGNER OF
 RECORD FOR THE ELECTRICAL SHEETS.
 THE NEW SHEETS CONTAIN A SIGNATURE WHICH IS NOT THE
 SAME AS THE PREVIOUS SHEETS. SHEETS FROM JANUARY PLANS,
 APRIL PLANS AND MAY PLANS CONTAIN DIFFERENT
 SIGNATURES.
  
 NEED SIGNATURE VERIFICATION LETTER FOR LEGAL SIGNATURE
 TO PLACE IN FILE AND ALL SIGNATURES NEED TO
 COORDINATE?
 THE OTHER OPTION IS FOR THE DESIGNER OF RECORD TO COME
 INTO THIS OFFICE TO RE-SIGN, DATE AND SEAL PLANS.
 SPOKE TO ARCHITECT IN CHARGE OF PROJECT FOR URS AND HE
 MENTIONED THEY WOULD HAVE ENGINEER COME INTO OFFICE. A
 TIME WILL BE SET UP FOR MEETING.
  
 ONE SET OF ELECTRICAL SHEETS FROM EACH WILL BE RETAINED
 BY THIS OFFICE. FS 471.025, FAC61G15-23.002
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By dpalmer Date 2008-05-20 Time 12:08 Rev Time 0.00
Received By dpalmer Date 2008-05-20 Time 12:08 Sent To  
Notes
2008-05-20 12:08:18** DENIED2ND AUDIT**
  
 ** PLEASE SEE SOME ITEMS STILL REMAIN FROM PREVIOUS
 AUDIT.
  
 1) NOTE: PLEASE SEE AFFIDAVITS ARE NOW ONLY BEING
 SUBMITTED. PLEASE SEE THESE ARE BEING MADE OUT TO
 BALFOUR CONCORD. THE CONTRACTOR ON THIS PROJECT IS
 BALFOUR/BEATTY.
 PLEASE COORDINATE.
 PLEASE ALSO SEE NOTICE TO BUILDING OFFICIAL SUBMITTED
 WHICH IS IN FACT PHOTO-COPIES AND ARE NOT ORIGINAL.
 THESE CONTAIN STAMPS *REVIEWED FOR COMPLIANCE8 FROM THE
 PRIVATE PROVIDER.
 PLEASE ONLY INCLUDE ORIGINAL DOCUMENTS AND PLEASE BE
 SURE TO FILL OUT WITH THE CORRECT CONTRACTOR.
  
 2) NOTE: PLEASE SUBMIT PLANS IN A NEAT AND ORDERLY
 FASHION WITH STAPLES SECURING ALL SHEETS TOGETHER.
 SEVERAL SHEETS IN THE BACK OF THE SETS WERE NOT SECURED
 TO THE REST OF THE SET. PLEASE ALSO DO NOT ATTACHED ALL
 OTHER DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS.
 PLEASE SUBMIT THESE IN SOME SORT OF BINDER/FOLDER WHICH
 THESE DOCUMENTS MAY BE READILY GONE OVER.
 PLEASE KNOW THESE WERE DETACHED AND PLACED INTO
 SEPARATE CLIPS AT THIS TIME.
 PLEASE ALSO KNOW DUE TO SOME COMMENTS BELOW SOME
 DOCUMENTS MAY ALSO BE RETAINED BY THIS OFFICE.
 FBC 106.1.2, 106.1, 106.1.3, 106.5 FOR ADDITIONAL
 INFORMATION, SUBMITTING OF PLANS, RECORD DOCUMENTS.
  
 3) NOTE: PLEASE SEE THE FLORIDA ENERGY EFFICIENCY CODE
 CALCULATIONS SUBMITTED ARE NOT CODE COMPLIANT.
 PLEASE SEE 13-400.3.A AS THE INCORRECT VERSION WAS
 SUBMITTED. THE VERSION SUBMITTED IS 3.0 WHEN THE CODE
 REQUIRES VERSION 2.5 WHEN USING FLA-COM PROGRAM.
 IN ANY CASE METHOD *A* MAY NOT BE USED AS THIS IS A
 TENANT SPACE BUILD OUT IN A BUILDING AND IS NOT A *
 WHOLE BUILDING*. PLEASE SEE THE DEFINITIONS IN THE FBC
 13-400.0.A. PLEASE PROVIDE INFORMATION AND
 DOCUMENTATION EXPLAINING HOW METHOD *A* SUBMITTED IS
 BEING USED.
  
 4) NOTE: PLEASE SEE THE SUBMITTED CALCULATIONS WERE
 ALSO STAMPED AS BEING CODE COMPLIANT BY THE PRIVATE
 PROVIDER WHEN IN FACT THESE ARE NOT SIGNED, DATED OR
 SEALED BY ANY ENGINEER OF RECORD. PLEASE SEE 13-103.1
 AS THIS SCOPE OF WORK IS REQUIRED TO BE DONE BY A
 LICENSED ENGINEER. PLEASE SEE THE SUBMITTED DOCUMENTS
 WERE SIGNED BY AN INDIVIDUAL WHICH DOES NOT LIST ANY
 LICENSE INFORMATION. IN FACT THE DOCUMENTS SUBMITTED
 CLEARLY SHOW A (PHOTO-COPIED SIGNATURE* FROM A
 *PREPARER* WHICH IS NOT LISTED AS A PE AND NOT AS ONE
 OF THE DESIGNERS OF RECORD. THIS IS THE SAME ON ALL
 THREE SETS SUBMITTED.
 WHEN SIGNING, DATING AND SEALING ANY DOCUMENTS AN
 ENGINEER MUST USE AN ORIGINAL SIGNATURE.
 FS 471.025, FAC 61G15-23.002
  
 5) NOTE: ** PLEASE SEE THE LIGHTING CALCULATIONS ALSOO
 SUBMITTED ARE IN FACT PHOTO-METRIC LEVELS WHICH ARE NOT
 LIGHTING PERFORMANCE CALCULATIONS REQUIRED PER FBC
 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE KNOW THESE
 SHALL NOT BE USED IN LIEU OF REQUIRED CALCULATIONS.
 PLEASE KNOW THESE WERE GONE OVER IN MEETING HELD BEFORE
 RESUBMITTING PLANS HOWEVER THESE ARE STILL BEING
 SUBMITTED.
 ** FOR INFORMATION:
 PLEASE KNOW ANY DOCUMENTS SUBMITTED AND PART OF THE
 DESIGN OF A PROJECT BY THE ENGINEER SHALL BE SIGNED,
 DATED, SEALED CONTAINING TITLE BLOCKS ETC.
  
 6) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS MEETING THE FLORIDA BUILDING CODE
 13-415.2, 13-415.2.ABC.1.1, .1.2.
 THE LIGHTING DENSITIES LISTED ON SHEET E200 ARE NOT
 COMPLETE. PLEASE COMPLETE AS SEE LEVELS IN TABLES IN
 THE FBC. PLEASE BE SURE THE LIGHTING FIXTURE LEGEND
 COORDINATES WITH CALCULATIONS, NUMBERS OF FIXTURES,
 TYPES OF FIXTURES ETC TO COORDINATE CODE COMPLIANCE.
 ** PLEASE KNOW SOME LEVELS SHOWN IN THE SPACE BY SPACE
 EXCEED LEVELS IN 13-415.2.B
  
 7) NOTE: PLEASE SEE MISSING MAXIMUM TIMES ON OVER RIDES
 AND OCCUPANCY SENSOR DEVICES. THE RESPONSE MENTIONS TO
 SEE E-100 AND E200 HOWEVER THE REVISED DEVICES, OVER
 RIDES AND OCCUPANCY SENSOR SWITCHES DO NOT INDICATE ANY
 TIMES.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SOME DEVICES ON PLANS ARE NOT ON SYMBOL
 LEGEND: FOR EXAMPLE PLEASE SEE READING ROOM AND OUTSIDE
 READING ROOM IN HALL AND SOME OTHER LOCATIONS WHICH
 SHOW A S IN A BOX HOWEVER NO OTHER DESIGNATION IS
 SHOWN. THERE IS NO S IN A SQUARE BOX ON SYMBOL LEGEND.
 WHICH DEVICE IS THIS?
 PLEASE COMPLETE.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-10 Cont ID  
Sent By dpalmer Date 2008-02-10 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2008-02-10 Time 10:40 Sent To  
Notes
2008-02-11 10:40:15 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE REQUIRED AFFIDAVIT AS REQUIRED
 PER FS 553.791(4)(C) WAS NOT SUBMITTED.
  
 2) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN THE
 FOLLOWING RELEVANT CODES STATED FOR DESIGN.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** SOME MAY ALREADY BE SHOWN HOWEVER NOT ALL. PLEASE BE
 AWARE OF ANY CODES REQUIRED BY OTHER TRADE REVIEWERS.
 PLEASE ALSO SEE THE CODES ARE NEEDED ON ELECTRICAL AS
 WELL.
 FBC 106.5, 106.1.2, FS 553.73
  
 3) NOTE: PLEASE SEE THAT THE SUITE/UNIT NUMBER IS
 REFLECTED ON TITLE BLOCKS. PLEASE KNOW IF ANY
 PARTICULAR SHEET DOES NOT NEED TO BE REVISED FOR CODE
 COMPLIANCE, THEN THIS MAY BE HAND PRINTED ON SHEETS.
 FBC 106.1.2, 106.5
 FAC 61G1-16.004, FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON
 TITLE BLOCKS FOR URS CORPORATION. PLEASE SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL
 FIRM WHICH IS REQUIRED PER FS 481.219 AND TO BE ON
 PLANS PER FAC 61G1-16.004
 PLEASE ALSO SEE FS 471.023 AND FAC 61G15-23.002 WHICH
 REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER FOR
 ENGINEERING BUSINESS AS WELL.
  
 5) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED
 GROUNDING AND INSTALLATION OF SYSTEMS PER NEC 517.
 PLEASE SEE 517.1 COMMENTARIES WHICH ARE QUOTED BELOW:
  
 *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY
 TO ALL TYPES OF HEALTH CARE FACILITIES. THE
 REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE
 NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC
 MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES
 WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE
 WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE
 REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER
 PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS
 ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE
 REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45
 IN ARTICLE 517.*
 PLEASE ALSO BE AWARE ANY UNDER GROUND SLAB AREAS TO
 EQUIPMENT SHALL BE RMC, IMC OR OTHER APPROVED CONDUIT
 SYSTEM. 517.13, 250, AND SEE USES PERMITTED IN CHAPTER
 13 FOR CONDUITS.
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND NOTES
 ON PLANS ACCORDINGLY.
  
 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 A LIGHTING CONTROL SYSTEM IS BEING NOTED HOWEVER OVER
 RIDES AND LOCATIONS ARE IN NEED OF MEETING THE ABOVE
 SECTIONS. MANY OF THESE ARE SHOWN AS STANDARD SWITCHES.
 SOME AREAS ARE EXEMPT PER EXCEPTIONS LISTED IN
 13-415.1.ABC.1.1
 PLEASE LIST SCHEDULING.
 PLEASE LIST MAXIMUM TIMES ON OVER RIDES.
 PLEASE SUBMIT DETAIL FOR ANY LIGHTING WHICH IS BEING
 OVER RIDDEN FROM A LOCATION IN WHICH THE LIGHTING BEING
 CONTROLLED CAN NOT BEE SEEN.
 PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS WHICH
 CAN NOT BE REVIEWED AND MAY HAVE NEW COMMENTS WHICH CAN
 NOT BE MADE AT THIS TIME.
  
 8) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2.
  
 9) NOTE: PLEASE SEE ROOM 14-312 WHICH INDICATES *FAN
 ROOM* PLEASE INDICATE AS DEDICATED ELECTRICAL
 /MECHANICAL SPACE.
 110.26
  
 10) NOTE: PLEASE CLARIFY THE ITD ROOM # 14-121 ON
 PLANS. ARCHITECTURAL SHEETS INDICATE 1HR FIRE RATING
 AND THIS ROOM CONTAINS SEPARATE A/C SYSTEM HOWEVER
 COULD NOT LOCATE THE REQUIRED DISCONNECTING MEANS PER
 645.10 FOR ALL. PLANS CONTAIN NOTE FOR MOST RECEPTACLES
 HOWEVER SOME ARE FED FROM A SEPARATE PANEL ALL
 TOGETHER. PLEASE CLARIFY USE OF THESE.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW PROPOSED IT EQUIPMENT.
 110.3, 90.7. PLEASE BE SURE SPECS/CUT SHEETS INDICATE A
 LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING
 LABORATORY).
  
 11) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF TRANSFORMER T112.5 ARE REQUIRED TO BE
 RATED FOR THE OVER CURRENT PROTECTION IN WHICH ARE
 BEING TERMINATED. PLEASE SEE 240.21, 310.16, 240.4 AND
 110.14.
 PLEASE KNOW IT IS ACCEPTABLE TO MOVE TO THE NEXT SIZE
 BREAKER (DEVICES 800AMPS AND LOWER) ON TYPICAL FEEDERS
 ETC HOWEVER NOT ON THE SECONDARY SIDE OF THE
 TRANSFORMER.
 THIS WAS INFORMATION GIVEN AND CONFIRMED BY THE CODE
 PANELIST AND NFPA.
 PLEASE ADJUST THESE TAPPED CONDUCTORS.
  
 12) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE ATTACHMENT
 POINT FOR THE TRANSFORMER GROUNDING PER 250.30, 250.50,
 AND 250.66.
  
 13) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON EXISTING
 EL41A FOR NEW LOAD BEING ADDED TO EXISTING SYSTEM
 SERVICE EQUIPMENT.
 220.87.
  
 14) NOTE: PLEASE KNOW THE NEW ELECTRIC WATER HEATER IS
 REQUIRED TO BE FIGURED INTO ENERGY CONSUMPTION. PLEASE
 SEE 13-412.1.ABC.3.4
  
 15) NOTE: PLEASE INDICATE ALL MINIMUM LEVELS FOR
 SOUNDING DEVICES PER FBC 11-4.28.1, .2. PLEASE SEE
 VISUAL DEVICES APPEAR TO BE OK ATTHIS TIME FOR ADA
 COMPLIANCE.
 PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM FIRE
 MARSHAL WHICH MAY AFFECT THE ELECTRICAL AND/OR F
 SHEETS.
  
 16) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS PER
 13-413.1.ABC.1.1. PLEASE SEE MORE SPECIFICALLY THE
 FEEDERS FROM 4TH FLOOR TO ECB.
  
 17) NOTE: PLEASE PROVIDE MORE INFORMATION PER
 517.71-517.78.
 SOME ITEMS ARE SHOWN HOWEVER NOT ALL.
  
 18) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCED FOR
 LOW VOLTAGE SCOPE OF WORK HOWEVER THE LV WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT. THIS IS NOTED FOR
 INFORMATION ONLY AT THIS TIME.
  
 ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED
 THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE ARE ANY
 QUESTIONS PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-02-24 Cont ID  
Sent By mwennerg Date 2009-02-24 Time 13:25 Rev Time 0.00
Received By mwennerg Date 2009-02-24 Time 13:25 Sent To  
Notes
2009-02-24 13:26:15REVISION #4 AND #7.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2008-11-10 Cont ID  
Sent By mwennerg Date 2008-11-10 Time 11:00 Rev Time 0.00
Received By mwennerg Date 2008-11-10 Time 11:00 Sent To  
Notes
2008-11-10 11:01:24NO LIFE SAFETY OR FIRE PROTECTION SYSTEMS CHANGE NOTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-09-23 Cont ID  
Sent By mwennerg Date 2008-09-23 Time 14:33 Rev Time 0.00
Received By mwennerg Date 2008-09-23 Time 14:33 Sent To  
Notes
2008-09-23 14:34:18STAMPED REVISED SHEETS FP001, FP101, FP201 AND FA200.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-11 Cont ID  
Sent By mwennerg Date 2008-07-11 Time 11:19 Rev Time 0.00
Received By mwennerg Date 2008-07-11 Time 11:19 Sent To  
Notes
2008-07-11 11:20:11PLANS APPROVED BY M.A. WILLIAMS AND STAMPED ON THIS
 DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By mawillia Date 2008-05-20 Time 15:54 Rev Time 0.00
Received By mawillia Date 2008-05-20 Time 14:32 Sent To  
Notes
2008-05-20 14:57:56*****PROVISO*****
  
 07.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.IT IS UNDERSTOOD
 THAT CLEVELAND CLINIC WILL BE THE ONLY TENANT ON THE
 FLOOR, HOWEVER THE SUITE NUMBER SHALL BE DISPLAYED
  
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 ABOVE COMMENT AND THE OTHERS PLAN REVIEWERS COMMENTS
 HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-14 Cont ID  
Sent By mawillia Date 2008-02-14 Time 16:40 Rev Time 0.00
Received By mawillia Date 2008-02-14 Time 14:50 Sent To  
Notes
2008-02-14 15:57:29*****DENIED*****
  
  
 01.THE ASSIGNED SUITE NUMBER SHALL BE INCLUDED IN THE
 ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION
 CODE AS LISTED IN THE CODE NOTES ON SHEET G0201, NFPA
 101- LIFE SAFETY CODE - 2003 EDITION SHALL BE
 REFERENCED.
  
 04.NO EXIT LIGHTS/DOORS SHOWN ON LIFE SAFETY PLAN
 (SHEET A0001) TO DETERMINE IF THE PATH OF TRAVEL IS TO
 THE EXIT(S).
  
 05.ON SHEET A0401,EXIT LIGHTS DIRECT PERSON(S) TO
 THE CORRIDORS.WHERE DO PERSON(S) GO ONCE THEY'RE IN
 THE CORRIDOR?CORRELATE THIS SHEET WITH G0201, E200
  
 06.GENERAL SHEET NOTE # 5 INCOMPLETE AS SHOWN ON
 SHEETS A0501 AND A0502.
  
 07.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 08.DOOR(S) LEADING DIRECTLY TO THE CORRIDOR SHALL BE
 AN APPROVED, LISTED, AND LABELED FIRE DOOR & ASSEMBLY
 IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80.
  
 09.SPECIFY THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 10.PLEASE CLARIFY OR CORRELATE THE NUMBER OF CORRIDOR
 EMERGENCY LIGHTING FIXTURES.ON SHEET E200 AND SHEET
 E201 THER ARE15 DEVICES SHOWN, BUT 30 DEVICES ARE
 LISTED IN THE DESIGN CRITERIA LUMINAIRES USED
 INFORMATION DATA ON SHEET E201.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 11:05 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 11:05 Sent To E
Notes
2009-03-27 11:05:54TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-03-06 Cont ID  
Sent By adarroug Date 2009-03-06 Time 09:45 Rev Time 0.00
Received By adarroug Date 2009-03-06 Time 09:45 Sent To E
Notes
2009-03-06 09:46:48TO "DPALMER" DESK/1 REV AND 1 SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-10-24 Cont ID  
Sent By adarroug Date 2008-10-24 Time 14:14 Rev Time 0.00
Received By adarroug Date 2008-10-24 Time 14:14 Sent To P
Notes
2008-10-24 14:15:15TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-10-10 Cont ID  
Sent By adarroug Date 2008-10-10 Time 16:27 Rev Time 0.00
Received By adarroug Date 2008-10-10 Time 16:27 Sent To  
Notes
2008-10-10 16:30:39TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-10 Cont ID  
Sent By adarroug Date 2008-10-10 Time 16:26 Rev Time 0.00
Received By adarroug Date 2008-10-10 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 15:41 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 15:41 Sent To  
Notes
2008-09-03 15:49:40TO "COMM" BD#35--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 11:20 Sent To  
Notes
2008-07-01 09:43:37TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 16:56 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 16:56 Sent To  
Notes
2008-05-12 16:57:21TO "COMM" BD#34/PLANS ON RACK/2 ROLLS**PRIVATE
 PROVIDER**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-10 Cont ID  
Sent By lmartine Date 2008-02-15 Time 10:31 Rev Time 0.00
Received By lmartine Date 2008-02-08 Time 09:25 Sent To  
Notes
2008-02-08 09:25:22TO "COMM" BD#18--PRIVATE PROVIDER--

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-09-16 Cont ID  
Sent By rregueir Date 2008-09-16 Time 12:31 Rev Time 0.00
Received By rregueir Date 2008-09-16 Time 12:30 Sent To  
Notes
2008-09-16 12:31:01PAGE M200 REV 5

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-19 Cont ID  
Sent By rregueir Date 2008-05-19 Time 11:30 Rev Time 0.00
Received By rregueir Date 2008-05-19 Time 11:28 Sent To E
Notes
2008-05-19 11:30:10SMOKE CONTROL ANALYSIS AND ORIGINAL NOTICE TO BUILDING
 OFFICIAL SUBMITTED PRIOR TO REVIEW BY OTHER TRADES.
 THIS REVIEW IS NOW IN PASS STATUS FOR 1ST RESUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-14 Cont ID  
Sent By rregueir Date 2008-05-14 Time 17:01 Rev Time 0.00
Received By rregueir Date 2008-05-14 Time 15:48 Sent To  
Notes
2008-05-14 17:01:02AUDIT #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 5: OK
  
 6. THE SMOKE CONTROL SYSTEM FOR THIS BUILDING HAS BEEN
 TESTED, COMMISSIONED AND IS COMPLETE. A NEW RATIONAL
 ANALYSIS SUPPORTING THE DESIGN OF THE PROPOSED
 MODIFICATIONS WITHIN THIS TENANT SPACE AND A SEQUENCE
 OF OPERATIONS SHALL BE SUBMITTED PRIOR TO PERMIT
 ISSUANCE.
  
 NOTE: ONCE CONSTRUCTION IS COMPLETE AND PRIOR TO A
 CERTIFICATE OF OCCUPANCY FOR THIS SPACE, THE BUILDING
 SMOKE CONTROL SYSTEM SHALL BE RE-TESTED AND
 RE-COMMISSIONED. THE EXTENT OF THE TESTING NECESSARY TO
 DEMONSTRATE THE FUNCTIONALITY OF NEW AND EXISTING
 PORTIONS OF THE SYSTEM MUST BE COORDINATED WITH THE
 CHIEF MECHANICAL INSPECTOR, FIRE MARSHAL AND
 COMMISSIONING AGENT. ANALYSIS AND TESTING SHALL BE DONE
 IN ACCORDANCE WITH FBCB SECTION 909.
  
 7 THROUGH 11: OK
  
 12. THE NOTICE TO BUILDING OFFICIAL AFFIDAVIT WHICH WAS
 PROVIDED IS A PHOTOCOPY. PLEASE PROVIDE ORIGINAL
 DOCUMENTATION WITH ORIGINAL SIGNATURES AND NOTARY
 STAMP.
  
 NEW: A PLAN REVIEW AFFIDAVIT FROM CAPRI ENGINEERING WAS
 NOT PROVIDED FOR THE FOLLOWING MECHANICAL PAGES WITH
 THIS SUBMITTAL: M300, M600, M700, M701, M702 SIGNED
 3/11/08.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-15 Cont ID  
Sent By rregueir Date 2008-02-15 Time 11:22 Rev Time 0.00
Received By rregueir Date 2008-02-14 Time 13:41 Sent To  
Notes
2008-02-15 11:22:31REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M200: THERE ARE SEVERAL LOCATIONS THROUGHOUT THIS
 FLOOR PLAN WHERE DUCTS ARE SHOWN PENETRATING FIRE
 RESISTANCE RATED WALL ASSEMBLIES WITHOUT ANY OPENING
 PROTECTIVE. EXAMPLE: FAN ROOM 14-312 IS FULLY ENCLOSED
 IN TYPE 2A WALLS, WHICH CARRY A 1-HOUR RATING AS SHOWN
 ON PG A1002. THERE ARE AT LEAST TWO DUCTS EXITING THIS
 ROOM WITHOUT FIRE DAMPERS AT THE WALL PENETRATIONS.
 THERE ARE MULTIPLE OTHER INSTANCES. PLEASE COORDINATE
 FLOOR PLANS FOR ARCHITECTURAL AND MECHANICAL, SHOWING
 OPENING PROTECTIVES WHERE REQUIRED IN ACCORDANCE WITH
 FBC, M 607.5.
  
 2. M200: CONVERSELY, THERE IS A FIRE DAMPER SHOWN IN A
 24X10 DUCT PENETRATING A TYPE 6 WALL (NON RATED
 ACCORDING TO PG A1002) NEAR COLUMN LINE F. A FIRE
 DAMPER IS SHOWN AT THIS LOCATION. FIRE DAMPERS ARE TO
 BE INSTALLED IN ACCORDANCE WITH THEIR LISTING PER FBC,
 M 607.2. THE SPECIFIC BRAND OF FIRE DAMPER IS NOT KNOWN
 AT THIS TIME BUT THE LISTING LIKELY REQUIRES THAT IT BE
 INSTALLED IN A RATED ASSEMBLY. AGAIN, PLEASE COORDINATE
 MECHANICAL AND ARCHITECTURAL FLOOR PLANS ACCORDINGLY.
  
 3. M200: EF-1 AND SF-1 SHOW NEW LOUVERS TO BE INSTALLED
 IN EXTERIOR WALLS. LOUVERS ARE CLASSIFIED AS PANEL
 WALLS PER FAC RULE 9B-72 AND AS SUCH, PRODUCT APPROVAL
 IS REQUIRED. PROVIDE PRODUCT APPROVAL FOR BUILDING PLAN
 REVIEW. PRODUCT APPROVALS SHALL BE APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE FOR REVIEW IN ACCORDANCE WITH FBC 106.3.3.
  
 4. M200: THE LOUVER OPENING FOR EF-1 MAY BE IN A 2-HOUR
 RATED EXTERIOR WALL IN ACCORDANCE WITH FBC TABLE 602.
 BASED ON THE DOCUMENTATION PROVIDED, IT IS UNCLEAR AS
 TO THE ALLOWABLE PERCENTAGE OF UNPROTECTED OPENINGS IN
 THIS WALL. OUTDOOR AIR EXHAUST AND INTAKE OPENINGS
 LOCATED IN EXTERIOR WALLS SHALL MEET THE PROVISIONS FOR
 EXTERIOR WALL OPENING PROTECTIVES IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING PER FBC, M 401.6.
 IF A CLAIM FOR ALLOWED UNPROTECTED OPENINGS IS MADE,
 PLEASE PROVIDE ALL NECESSARY INFORMATION AND
 CALCULATIONS FOR BUILDING PLAN REVIEW.
  
 5. M200: A 44X12 ?SMOKE CONTROL TRANSFER OPENING IN
 WALL W/ SMOKE DAMPER? IS SHOWN IN WALL ON NORTH SIDE OF
 SPACE. THERE IS NOT INDICATION THAT THIS IS ALSO A FIRE
 DAMPER. A FIRE DAMPER IS REQUIRED AT THIS LOCATION AS
 IT IS LOCATED IN A 1-HOUR RATED WALL AS INDICATED ON
 ARCHITECTURAL FLOOR PLAN. ALSO, BY WHAT MEANS WILL THIS
 SMOKE DAMPER BE CONTROLLED? SMOKE DAMPERS SHALL BE
 ACTUATED BY ONE OF THE METHODS LISTED IN FBC, M
 607.3.2.1. THIS DAMPER IS NOT PART OF THE BASE BUILDING
 SMOKE CONTROL SYSTEM. WILL THE BASE BUILDING DESIGN BE
 REVISED TO INCORPORATE THIS NEW SMOKE DAMPER?
  
 6. M200: RELATED TO COMMENT #5 ABOVE, SPECIFIC NOTE #6
 ON PLAN CALLS FOR SMOKE DAMPERS TO BE INSTALLED IN
 DUCTS IN VARIOUS LOCATIONS THROUGHOUT THE FLOOR PLAN,
 INCLUDING SUPPLY AND RETURN DUCTS WHICH ARE PART OF A
 ?SMOKE REMOVAL SYSTEM IN DUCT.?
 A) EXISTING PAC-1 SUPPLY AND RETURN DUCT IS BEING SHOWN
 AS PART OF A SMOKE REMOVAL SYSTEM. PAC-1 HAS NO ROLE IN
 THIS BUILDING?S SMOKE CONTROL SYSTEM OTHER THAN IT WILL
 BE SHUT DOWN DURING SMOKE CONTROL MODE.
 B) A RATIONAL ANALYSIS OF THIS BUILDING?S SMOKE CONTROL
 SYSTEM HAS BEEN PERFORMED AND SUBMITTED AS PART OF THE
 BASE BUILDING?S PERMIT RECORD. ANY MODIFICATIONS TO THE
 SMOKE CONTROL SYSTEM (AS PROPOSED BY THIS TENANT) MUST
 BE INCORPORATED INTO THE RATIONAL ANALYSIS, INCLUDING
 ANY ADDITIONAL DAMPERS WHICH NEED TO BE CONTROLLED BY
 THE SYSTEM IN ACCORDANCE WITH FBC, M 513.4.
 C) ITD ROOM 14-121 IS SHOWN ON FLOOR PLAN TO 1-HOUR
 RATED WITH TYPE 2A WALLS EXTENDING TO THE UNDERSIDE OF
 THE DECK ABOVE ON THREE SIDES. ONE OF THESE WALLS IS
 SHOWN ON FLOOR PLAN BISECTING THE 60X20 OUTLET OF THE
 SUPPLY DUCT FOR THE BUILDING SMOKE CONTROL SYSTEM. THIS
 WOULD BE AN IMPEDIMENT TO MOST OF THE AIR, TRAPPING IT
 IN THE ITD ROOM AND PREVENTING THE AIR FROM
 PRESSURIZING THE ENTIRE FLOOR, WHICH IS ITS PURPOSE.
 PLEASE SHOW HOW THE RATING OF THIS ROOM IS TO BE
 ACHIEVED WITHOUT DEFEATING THE BUILDING SMOKE CONTROL
 SYSTEM. ADDITIONALLY, THE REQUIRED RATING OF THE TYPE
 2A WALL CAN NOT BE MAINTAINED AS IT CROSSES THE OPEN
 END OF THE 60X20 DUCT.
 D) WEST OF THE SERVICE ELEVATOR THERE IS AN
 UNIDENTIFIED ENCLOSED AREA SURROUNDED BY TEMPORARY
 CORRIDOR 14-036. THIS AREA ENCLOSES THE EXHAUST INLET
 FOR THE BUILDING SMOKE CONTROL SYSTEM. THIS ENCLOSURE
 CREATES A PLENUM SPACE TO BE USED BY THE EXHAUST
 PORTION OF THE BUILDING SMOKE CONTROL SYSTEM. THIS
 SPACE IS NOT PART OF THE BASE BUILDING DESIGN AS IT IS
 NOT SHOWN ON THE BASE BUILDING PLANS. THE WALL TYPES
 AND FINISHES ARE NOT KNOWN AS THEY ARE NOT IDENTIFIED
 ON THE ARCHITECTURAL FLOOR PLAN FOR THE TENANT SPACE.
 THERE ARE TRANSFER DUCTS AND SMOKE DAMPERS SHOWN
 FEEDING THIS PLENUM SPACE WHICH ARE ALSO NOT PART OF
 THE CURRENT SMOKE CONTROL SYSTEM DESIGN. PLEASE CLARIFY
 THE INTENT, IDENTIFY IF THESE WALLS CARRY ANY SORT OF
 RATING AND DETERMINE IF THIS DESIGN WILL BE
 INCORPORATED INTO THE BASE BUILDING DESIGN. FBC, M
 513.2 AND 513.4
  
 7. M200: SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL
 FOR PROPOSED NEW AC-1 IN ITD ROOM IN COMPLIANCE WITH
 FBC, M 307.2.2.
  
 8. PROVIDE DETAIL FOR A LISTED THROUGH-PENETRATION
 FIRESTOP SYSTEM TO BE USED WHERE CONDENSER AND/OR
 CONDENSATE PIPING IS TO PENETRATE FIRE RESISTANCE RATED
 WALL ASSEMBLIES IN ACCORDANCE WITH FBC 712.3.
  
 9. M500: FIRE DAMPER DETAILS, THESE DETAILS ARE LIKELY
 TO BE IN CONFLICT WITH FIRE DAMPER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. FIRE DAMPERS, SMOKE DAMPERS
 AND COMBINATION FIRE/SMOKE DAMPERS LOCATED WITHIN AIR
 DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS
 SECTION, AND THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC, M 607.2. COORDINATE
 DETAIL ON PLANS WITH MANUFACTURER?S INSTALLATION
 INSTRUCTIONS OR PROVIDE A NOTE ON PLANS INDICATING THAT
 IN THE EVENT OF A CONFLICT THE MANUFACTURER?S
 INSTRUCTIONS SHALL PREVAIL.
  
 10. M200 AND M701: SF2 SHALL BE PROVIDED WITH A DUCT
 SMOKE DETECTOR. SMOKE DETECTORS SHALL BE INSTALLED IN
 SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAN
 2,000 CFM IN THE SUPPLY AIR DUCT IN ACCORDANCE WITH
 FBC, M 606.2.1.
  
 11. M701: SEQUENCE OF OPERATION DOES NOT HAVE ANY
 INDICATION THAT SMOKE DETECTORS IN THE SUPPLY DUCT HAVE
 BEEN TAKEN INTO ACCOUNT AS ONLY THE RETURN SMOKE
 DETECTORS ARE SHOWN IN THE SEQUENCE AND DIAGRAMS. NOTE:
 FBC, M 606.2.1 REQUIRES DETECTORS AT A MINIMUM IN THE
 SUPPLY DUCT AND 606.2.2 REQUIRES THEM ADDITIONALLY IN
 THE RETURN DUCT. THE SUPPLY DETECTORS SHALL ALSO
 INITIATE A FAN SHUT-DOWN AND INITIATE AN ALARM SIGNAL
 IN ACCORDANCE WITH THIS SECTION.
  
 12. THESE PLANS HAVE BEEN REVIEWED AND SUBMITTED UNDER
 THE PRIVATE PROVIDER SYSTEM AS ESTABLISHED UNDER FS
 553.791. THIS STATUTE REQUIRES AN AFFIDAVIT FROM THE
 FEE OWNER ACKNOWLEDGING THE DECISION TO USE PRIVATE
 PROVIDERS UNDER FS 533.791(4)(C). NO SUCH INFORMATION
 COULD BE FOUND IN THE PACKAGE SUBMITTED FOR PERMIT.
 PROVIDE ALL REQUIRED DOCUMENTATION PURSUANT TO THIS
 STATUTE.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH A
 DESCRIPTION OF HOW THE COMMENT HAS BEEN ADDRESSED (OR
 WHY IT HAS NOT) AS WELL AS WHERE THE RELEVANT
 INFORMATION CAN BE FOUND. ALSO, PLEASE RETURN ONE SET
 OF OLD/VOIDED PLANS FOR REFERENCE. THESE STEPS WILL
 HELP TO ENSURE A TIMELY REVIEW UPON RESUBMISSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 6 Status N Date 2008-11-06 Cont ID  
Sent By kstevens Date 2008-11-06 Time 08:17 Rev Time 0.00
Received By kstevens Date 2008-11-06 Time 08:17 Sent To  
Notes
2008-11-06 08:17:42SUBMITTAL FOR WATER SAMPLE RESULTS NOT REQUIRED

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-10-27 Cont ID  
Sent By kstevens Date 2008-10-27 Time 15:30 Rev Time 0.00
Received By kstevens Date 2008-10-27 Time 15:30 Sent To  
Notes
2008-10-27 15:34:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P202 REVISION 4 NOT APPROVED. VENT FROM FD-2 IS
 SHOWN CONNECTING TO THE COLD WATER LINE. SECTION 608.1.
  
 2. SHT P300 VENT FROM FD-2 DOES NOT REFLECT THE FLOOR
 PLAN AS SHOWN ON SHT P202. THE FUTURE VENT SHOWN ON THE
 FLOOR PLAN IS NOT SHOWN ON THE SANITARY RISER DIAGRAM.
 (SEE SPECIFIC NOTE #1 SHT P202).
  
 3. A REVISION FOR SHT P201 IS REQUIRED TO REFLECT THE
 CHANGE SHOWN ON THE SANITARY RISER AT COL. L-7, 12TH
 FLOOR. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-09-04 Cont ID  
Sent By kstevens Date 2008-09-04 Time 08:15 Rev Time 0.00
Received By kstevens Date 2008-09-03 Time 17:09 Sent To  
Notes
2008-09-04 08:23:40REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P202 REVISIONS 3 & 4 WERE NOT FOUND. PLEASE
 CLOUD ALL REVISIONS AND INDICATE REVISIONS WITH THE
 REVISION NUMBER. SECTION 106.1.3.
  
 2. SHT P202 DRINKING FOUNTAINS WERE DELETED. PER TABLE
 403.1 MINIMUM 2 DRINKING FOUNTAINS ARE REQUIRED. PLEASE
 INDICATE WHERE THE REQUIRED DRINKING FOUNTAINS ARE
 LOCATED.
  
 3. SHT P300 WATER ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE CHANGE IN THE FLOOR PLAN INDICATED ON SHT
 P202 AT S1 SINK IN X-RAY ROOM 14307. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 604.
  
 4. SHT P300 ALL CHANGES/REVISIONS TO THE FLOOR PLAN
 SHALL BE SHOWN ON THE SANITARY RISER DIAGRAM. S-1 SINK
 DOES NOT SHOW CHANGE AS WELL AS THE DELETED DRINKING
 FOUNTAINS. PLEASE CORRELATE. SECTION 106.1.1 & TABLE
 710.1(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-17 Cont ID  
Sent By kstevens Date 2008-06-17 Time 16:32 Rev Time 0.00
Received By kstevens Date 2008-06-17 Time 16:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-21 Cont ID  
Sent By kstevens Date 2008-05-21 Time 18:26 Rev Time 0.00
Received By kstevens Date 2008-05-21 Time 18:26 Sent To  
Notes
2008-05-21 18:51:07AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY MUNICIPAL CODE
  
 ****FROM PREVIOUS AUDIT:
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE
 NUMBER, (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN
 THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 2. OK
  
 3. SUBMIT DETAILS FOR THE ACCESSIBLE TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED
 COMPLETLY. SHOW COMPLIANCE WITH:
 ___FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
 C. 11-4.19.6 MIRRORS (SHOWS 46")
  
 4. SHT A0201 TOILET ROOMS 14-310 & 14-105 THE DOOR
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. SECTION 11-4.22.3.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 5. OK
 6. OK
  
 7. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED
 COMPLETLY. SHOW COMPLIANCE WITH SECTION 11-4.24.5 CLEAR
 FLOOR SPACE. (FORWARD APPROACH REQUIRED).
  
 8. OK
  
 9. SHT P001 WATER HEATER WH-1 PIPING DETAIL. THE VACUUM
 RELIEF VALVE IS SHOWN IN THE HOT WATER LINE. THE VALVE
 SHALL BE INSTALLED IN THE COLD WATER LINE PER SECTION
 504.2.--FLOOR DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED.
 SECTIONS 802.3 & 802.3.2. (MAKE CHANGES TO PIPING &
 RISER DIAGRAMS).--SUBMIT CALCULATIONS FOR THE SIZE
 OF THE EXPANSION TANK, OR PROVIDE MANUF. TABLES
 INDICATING THE MODEL NUMBER AND MAXIMUM GALLONS FOR
 MODEL NUMBER FOR THE EXPANSION TANK TO VERIFY CORRECT
 SIZE. SECTION 607.3.2.
 ****RESPONSE NOTED, BUT THE EXPANSION TANK CALCULATIONS
 WERE NOT FOUND.
  
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS ETC.
 SECTIONS 106.3.5.1.3 & 604.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IS MEET CODE
 REQUIREMENS. THE HOT SUPPLY MAIN CONNECTS INTO THE COLD
 BRANCH LINE TO THE SINKS IN ROOMS 144, 146, 147, 148,
 149 & 160. SECTION 604.2. --THE HOT SUPPLY TO THE
 SINK IN THE ROOM NEAR THE READING ROOM DOES NOT REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1 & 601.1.--THE
 PIPING TO THE SINKS FOR ROOMS 112/115 & ROOM 141 DO NOT
 REFLECT THE FLOOR PLAN. SECTIONS 106.1.1 & 601.1.--
 THE WATER SUPPLIES ARE CROSSED INDICATING THE HOT ON
 THE RIGHT AND THE COLD ON THE LEFT SIDE OF THE SINKS IN
 ROOMS 110, 111, 112, 115, 116, 117, 132, 133, 140 &
 142. SECTION 607.4.--THE WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201
  
 18. OK
  
 19. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION
 TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE
 MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN
 OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE,
 SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY
 WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT
 THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT,
 INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF
 FLORIDA STATUTE.
 ****RESPONSE NOTED, BUT SEE COMMENTS NUMBER ONE AND TWO
 OF THE ELECTRICAL REVIEW AND COMMENT NUMBER TWELVE OF
 THE MECHANICAL REVIEW. PLEASE SHOW COMPLIANCE WITH
 THESE REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By kstevens Date 2008-02-11 Time 12:03 Rev Time 0.00
Received By kstevens Date 2008-02-11 Time 12:03 Sent To  
Notes
2008-02-11 12:43:18AUDIT DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE
 NUMBER, (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN
 THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
  
 2. PER TABLE 403.1 2 DRINKING FOUNTAINS ARE REQUIRED.
 PLEASE INDICATE THE LOCATION OF EACH REQUIRED DRINKING
 FOUNTAIN. SECTION 106.1.1.
  
 3. SUBMIT DETAILS FOR THE ACCESSIBLE TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 &
 11-4.22 WITH ALL SUBSECTIONS.
  
 4. SHT A0201 TOILET ROOMS 14-310 & 14-105 THE DOOR
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. SECTION 11-4.22.3.
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 6. SHT A1002 TOILET ROOMS 14-104, 14-105 & 14-310 STATE
 "CT-2 AT WET WALL, PT ALL OTHER WALLS". PER SECTION
 1210.2 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
 PAINTED SURFACES DOES NOT MEET THE REQUIREMENT FOR A
 "HARD SURFACE".
  
 7. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 8. SHT P001 INDICATE THE LISTING NUMBER FOR THE FLOOR
 AND WALL PENETRATIONS. SECTION 712.3.1.2. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.--ALSO THE FLOOR SLEEVE DETAIL INDICATES
 THAT THE SLEEVE SHALL BE 1" ABOVE THE FLOOR. WITH THE
 RISER CLAMP SITTING ON THE SLEEVE, PLEASE SUBMIT A
 DETAIL SHOWING HOW THE SLEEVE IS ATTACHED TO THE FLOOR
 AND INDICATE THE MATERIAL AND GUAGE FOR THE SLEEVE.
 SECTION 308.9.
  
 9. SHT P001 WATER HEATER WH-1 PIPING DETAIL. THE VACUUM
 RELIEF VALVE IS SHOWN IN THE HOT WATER LINE. THE VALVE
 SHALL BE INSTALLED IN THE COLD WATER LINE PER SECTION
 504.2.--FLOOR DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED.
 SECTIONS 802.3 & 802.3.2. (MAKE CHANGES TO PIPING &
 RISER DIAGRAMS).--SUBMIT CALCULATIONS FOR THE SIZE
 OF THE EXPANSION TANK, OR PROVIDE MANUF. TABLES
 INDICATING THE MODEL NUMBER AND MAXIMUM GALLONS FOR
 MODEL NUMBER FOR THE EXPANSION TANK TO VERIFY CORRECT
 SIZE. SECTION 607.3.2.
  
 10. SHT P202 CONDENSATE SHALL NOT DRAIN TO THE SANITARY
 SYSTEM. MUNICIPAL CODE ARTICLE III SECTION
 90-125(B)(5). CONDENSATE SHALL CONNECT TO THE
 CONDENSATE RISERS AND DRAIN SEPARATELY.
  
 11. SHT P202 SPECIFIC NOTES #3 IS NOT FOUND ON THE
 FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 12. SHT P202 SHOWS 2 COLD WATER SUPPLIES TO THE SINK IN
 ROOM 14-130. HOT WATER IS REQUIRED PER SECTION 607.1.
  
 13. SHT P202 WATER & VENT DROPS TO SINKS IN ROOMS
 14-010, 14-100 & 14-106 AS WELL AS THE WATER & VENT
 DROPS BETWEEN THE TOILET ROOMS ARE SHOWN DROPING DOWN
 OUT OF THE WALL. PLEASE CLARIFY.
  
 14. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN F-7
 DOES NOT REFLECT THE FLOOR PLAN. THE EXTENTION OF THE
 FUTURE SANT IS NOT SHOWN ON THE FLOOR PLAN, THE FLOOR
 PLAN SHOWS OFFSETS IN THE 4" BRANCH LINE TO THE TOILET
 ROOM AND THE 1-1/2" LINE TO THE S-1 SINK. OFFSETS ARE
 NOT SHOWN ON THE RISER DIAGRAM. THE LINE TO THE S-1
 SINK IS INDICATED AS 1-1/2" ON THE FLOOR PLAN, BUT 2"
 ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1.
  
 15. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-7
 DOES NOT REFLECT THE FLOOR PLAN, NOR DOES IS MEET CODE.
 THE HUB DRAIN FOR THE A/C CONDENSATE IS NOT APPROVED
 PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B)(5).
 PLEASE DELETE.
  
 16. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-5
 DOES NOT REFLECT THE FLOOR PLAN. THE S-1 SINK AT THE
 SOUTH SIDE OF COLUMN SHOWS INDIVICUAL VENTS ON THE
 FLOOR PLAN, BUT SINGLE VENT ON THE RISER DIAGRAM.--
 FLOOR PLAN SHOWS THE SANT. FOR THE SINK RUNNING SOUTH
 OF THE 3" STACK, BUT THE RISER DIAGRAM SHOWS THE PIPING
 RUNNING EAST THEN SOUTH.--THE 1ST RISER ON THE
 BRANCH LINE TO THE WEST, (FOR ROOMS 14-140 & 14-142),
 RISER IS SHOWN CONNECTING TO THE MAIN LINE RUNNING
 NORTH & SOUTH ON THE FLOOR PLAN, BUT ON THE WEST BRANCH
 LINE ON THE RISER DIAGRAM. OTHER RISERS ON THE WEST
 BRANCH LINE DO NOT REFLECT THE FLOOR PLAN.--THE 3"
 LINE CAPPED FOR THE FUTURE SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM.--VENTING DOES NOT
 REFLECT THE FLOOR PLAN FOR THE FUTURE VENT AND THE SINK
 IN ROOM 14-161.--THE BRANCH LINES AT THE UPSTREAM
 END OF THE RISER DIAGRAM SHOW 4 RISERS TO THE WEST AND
 1 RISER ON THE EAST BRANCH ON THE FLOOR PLAN, BUT SHOW
 2 RISERS ON EACH BRANCH ON THE RISER DIAGRAM. PLEASE
 CORRELATE AND SUBMIT THE RISER DIAGRAMS THAT REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1 & TABLE 710.1(2).
  
 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS ETC.
 SECTIONS 106.3.5.1.3 & 604.
  
 18. SUBMIT AN ISOMETRICCONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZES TRAPS, VENTS, POINT OF
 CONNECTION TO THE CONDENSATE RISER ETC. SECTION
 106.3.5.1.3.
  
 19. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION
 TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE
 MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN
 OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE,
 SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY
 WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT
 THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT,
 INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF
 FLORIDA STATUTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved