Plan Review Stops For Permit 08020160 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2008-02-26 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2008-02-26 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2008-02-26 |
Time |
08:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2009-02-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-02-26 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-02-26 |
Time |
08:36 |
Sent To |
|
|
Notes |
2009-02-26 09:10:48 | AUDIT - REVISED SHEETS A201, A502 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2008-11-18 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-11-18 |
Time |
10:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-11-18 |
Time |
10:43 |
Sent To |
|
|
Notes |
2008-11-18 10:50:44 | AUDIT - REVISED SHEETS A0201, A0501, A0502, A1001 DATED | | 9/30/8 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-10-28 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-10-28 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-10-28 |
Time |
10:36 |
Sent To |
|
|
Notes |
2008-10-28 10:39:34 | ARCHITECT'S 8.5" X 11" SHEET SUBMITTAL DETAILING RATED | | WALL CONSTRUCTION AROUND THE BACK SIEMAN'S CHASE IN | | X-RAY ROOM. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-09-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-09-22 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-09-22 |
Time |
10:56 |
Sent To |
|
|
Notes |
2008-09-22 10:57:24 | PRIVATE PROVIDER AUDIT | | REVISION DATED 7/23 AND 731/8, SHEETS G0001, G0201, | | A0001, A201, A203, A401, A501, A502, A701, A1001, A1002 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-06-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-06-24 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-06-24 |
Time |
11:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-05-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-05-20 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-05-20 |
Time |
16:16 |
Sent To |
|
|
Notes |
2008-05-20 16:35:42 | ****AUDIT**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.PLEASE CORRECT CERTIFICATE OF AUTHORIZATION LICENSE | | NUMBER FOR THE ARCHITECT BUSINESS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-02-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-02-14 |
Time |
14:44 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2008-02-14 |
Time |
14:44 |
Sent To |
|
|
Notes |
2008-02-14 14:45:51 | BUILDING PLAN REVIEW | | PERMIT: 08020160 | | ADD: 525 OKEECHOBEE BLVD | | SUITE 1400 | | CONT: BALFOUR BEATTY | | TEL: (772)215-3063 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 1B) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE2007 SUPPLEMENTS SHEET G0201 NEEDS | | TO UPDATE TO THE 2007 FBC UPDATES( SUBMITTALS) . | | | | 2) URS- THEY ARE MISSING THEIR CERTIFICATE OF | | AUTHORIZATION. 481.219 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING | | THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS | | NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING | | ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE | | OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH | | SHEET. | | THIS MAY BE ADDED BY HAND. | | | | 3) SHEET G0201 INDICATES THE USE OF X-RAY MACHINES. | | PLEASE PROVIDE THE PLANS SUBMITTED TO THE DEPARTMENT OF | | HEALTH FOR REVIEW AND APPROVAL. 435.5.1.3 PRIOR TO | | CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT ARRANGEMENT | | OF ALL NEW INSTALLATIONS, OR MODIFICATIONS OF EXISTING | | INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND | | ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE | | SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND | | APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER | | REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE | | FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR | | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN | | INTO CONSIDERATION. | | 435.5.1.3.1 | | THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING: | | 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S | | RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS; | | GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY | | WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S | | BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. | | 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS | | OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, | | FLOOR AND CEILING OF THE ROOM CONCERNED. 435.5.1.3.1.3 | | THE DIMENSIONS OF THE ROOM CONCERNED. 435.5.1.3.1.4 THE | | TYPE OF OCCUPANCY OF ALL ADJACENT AREAS INCLUSIVE OF | | SPACE ABOVE AND BELOW THE ROOM CONCERNED. IF THERE IS | | AN EXTERIOR WALL, THE DISTANCE TO THE CLOSEST AREA | | WHERE IT IS LIKELY THAT INDIVIDUALS MAY BE PRESENT. | | 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT | | AND THE MAXIMUM TECHNIQUE FACTORS. | | 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS | | WHICH WILL BE PERFORMED WITH THE EQUIPMENT. | | 435.5.1.3.2 | | INFORMATION SHALL BE SUBMITTED ON THE ANTICIPATED | | MAXIMUM WORKLOAD OF THE X-RAY SYSTEM. | | 435.5.1.3.3 | | IF THE SERVICES OF A QUALIFIED PERSON HAVE BEEN | | UTILIZED TO DETERMINE THE SHIELDING REQUIREMENTS, A | | COPY OF THE REPORT, INCLUDING ALL BASIC ASSUMPTIONS | | USED, SHALL BE SUBMITTED WITH THE PLANS. | | | | 4) SHEET G0201- HANDICAPPED RESTROOM, PLANS INDICATE | | THEDOOR SWINGING INTO THE CLEAR FLOOR SPACE REQUIRED | | FOR FIXTURES PLEASE SEE PLAN. 11-4.22.3. | | | | 5)SHEETGO201- MISSING INFORMATION ON THE CHANGING | | ROOMS OR DRESSING ROOMS: 11-4.35 DRESSING AND FITTING | | ROOMS. | | | | 11-4.35.1 GENERAL. | | DRESSING AND FITTING ROOMS REQUIRED TO BE ACCESSIBLE BY | | SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.35 AND | | SHALL BE ON AN ACCESSIBLE ROUTE. | | | | 11-4.35.2 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE ALLOWING A PERSON USING A | | WHEELCHAIR TO MAKE A 180-DEGREE TURN SHALL BE PROVIDED | | IN EVERY ACCESSIBLE DRESSING ROOM ENTERED THROUGH A | | SWINGING OR SLIDING DOOR. NO DOOR SHALL SWING INTO ANY | | PART OF THE TURNING SPACE. TURNING SPACE SHALL NOT BE | | REQUIRED IN A PRIVATE DRESSING ROOM ENTERED THROUGH A | | CURTAINED OPENING AT LEAST 32 INCHES (815 MM) WIDE IF | | CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2 RENDERS | | THE DRESSING ROOM USABLE BY A PERSON USING A | | WHEELCHAIR. | | | | 11-4.35.3 DOORS. | | ALL DOORS TO ACCESSIBLE DRESSING ROOMS SHALL BE IN | | COMPLIANCE WITH SECTION 11-4.13 . | | | | 11-4.35.4 BENCH. | | EVERY ACCESSIBLE DRESSING ROOM SHALL HAVE A 24 INCHES | | BY 48 INCHES (610 MM BY 1219 MM) BENCH FIXED TO THE | | WALL ALONG THE LONGER DIMENSION. THE BENCH SHALL BE | | MOUNTED 17 INCHES TO 19 INCHES (430 MM TO 485 MM) ABOVE | | THE FINISH FLOOR. CLEAR FLOOR SPACE SHALL BE PROVIDED | | ALONGSIDE THE BENCH TO ALLOW A PERSON USING A | | WHEELCHAIR TO MAKE A PARALLEL TRANSFER ONTO THE BENCH. | | THE STRUCTURAL STRENGTH OF THE BENCH AND ATTACHMENTS | | SHALL COMPLY WITH SECTION 11-4.26.3 . WHERE INSTALLED | | IN CONJUNCTION WITH SHOWERS, SWIMMING POOLS, OR OTHER | | WET LOCATIONS, WATER SHALL NOT ACCUMULATE UPON THE | | SURFACE OF THE BENCH AND THE BENCH SHALL HAVE A | | SLIP-RESISTANT SURFACE. | | | | 11-4.35.5 MIRROR. | | WHERE MIRRORS ARE PROVIDED IN DRESSING ROOMS OF THE | | SAME USE, THEN IN AN ACCESSIBLE DRESSING ROOM, A | | FULL-LENGTH MIRROR, MEASURING AT LEAST 18 INCHES WIDE | | BY 54 INCHES HIGH (460 MM BY 1370 MM), SHALL BE MOUNTED | | IN A POSITION AFFORDING A VIEW TO A PERSON ON THE BENCH | | AS WELL AS TO A PERSON IN A STANDING POSITION. | | | | 6)A0703 ADA SINK BASE DOES NOT MEET THE TOE CLEARANCE | | REQUIREMENTS NOR DOES THE REMOVABLE WHEELCHAIR ACCESS | | PANEL FOR KNEE CLEARANCES. 11-4.24.3. | | | | 7) SHEET A0502 DETAIL ?B? INDICATES 2 HANDICAPPED | | RESTROOMS ONE INDICATES THE DOOR SWING INTO THE CLEAR | | FLOOR SPACE FOR ACCESSIBLE FIXTURES SEE 11-422.3. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
9 |
Status |
P |
Date |
2009-03-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-30 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-30 |
Time |
13:43 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
F |
Date |
2009-03-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-03-12 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-03-12 |
Time |
13:32 |
Sent To |
PC |
|
Notes |
2009-03-12 13:33:10 | ** DENIED REVISIONS ** | | | | | | 1) NOTE: PER FS 553.791 ALL REVISIONS TO PRIVATE | | PROVIDER PROJECTS MUST GO BACK TO THE PROVIDER, BE | | REVIEWED, STAMPED AND SUBMIT AFFIDAVITS FOR NEW REVISED | | SHEETS. | | THERE ARE SEVERAL REVISED SHEETS WHICH DO NOT CONTAIN | | THE STAMPED AND NO NEW AFFIDAVITS WERE SUBMITTED. | | PLEASE BE SURE TO CALL IF THERE ARE | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
F |
Date |
2009-02-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-02-23 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-02-23 |
Time |
14:22 |
Sent To |
|
|
Notes |
2009-02-23 14:22:44 | ** DENIED AUDIT ** | | | | | | | | 1) NOTE: THERE IS STILL NO REVISED LIGHTING PERFORMANCE | | CALCULATIONS SUBMITTED. THERE HAS BEEN AN INCREASE IN | | WATTAGE FROM THE ORIGINAL CALCULATIONS. | | SOME FIXTURES HAVE BEEN REVISED TO ACTUALLY DOUBLE THE | | WATTAGE FROM THE ORIGINAL FIXTURE DESIGNS. | | PLEASE SEE 13-415.2.ABC.1.1,.1.2, 13-415.2.B.2. | | PLEASE BE SURE TO ALSO SUBMIT THE LATEST REVISED | | FIXTURE LEGEND. THE PREVIOUS PLANS WHICH CONTAINED THE | | REVISED FIXTURE LEGEND WERE REJECTED ON THE PREVIOUS | | REVIEW DATED 10/31/2008. | | NO REVISED PLANS ADDRESSING THIS ISSUE HAVE BEEN | | SUBMITTED SINCE THAT DATE. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2008-10-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-31 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-31 |
Time |
09:05 |
Sent To |
|
|
Notes |
2008-10-31 09:05:46 | | | ** DENIED REVISION** | | | | 1) NOTE: PLEASE SHOW AND DISPLAY ALL REVISIONS AS NOTED | | ON TITLE BLOCKS. FOR EXAMPLE THE LAST REVISION ON | | RECORD TO DATE FOR SHEET E500 IS REVISION #4, WHEREAS | | THE NEW REVISED SHEET CONTAINS REVISION #6. WHERE IS | | REVISION #5 LOCATED ON PLANS? NO CLOUDS OR TRIANGLES | | ARE SHOWN INDICATING THESE REVISIONS. THERE WAS A | | PREVIOUS REV #5 HOWEVER FOR OTHER SHEETS. | | PLEASE COORDINATE PLANS. | | FBC 106.1.1 | | FBC CHAPTER 13, NEC 220 | | | | 2) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE | | CALCULATIONS. AS THE FIXTURES HAVE BEEN REVISED TO | | INCREASE WATTAGES THE PREVIOUSLY SUBMITTED CALCULATIONS | | NO LONGER COORDINATE. | | PLEASE SEE 13-415.2,13-415.2.ABC.1.1,.1.2. | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2008-09-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-15 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-15 |
Time |
13:36 |
Sent To |
|
|
Notes |
2008-09-15 13:37:38 | REV #5 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2008-07-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-09 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-09 |
Time |
14:06 |
Sent To |
B |
|
Notes |
2008-07-09 14:07:06 | ENGINEER OF RECORD CAME INTO OFFICE AND PERSONALLY | | SIGNED, DATED AND SEALED ALL ELECTRICAL PLANS. | | | | ** PLANS ROUTED TO LUIS MARTINEZ AS FIRE REVIEW STILL | | NEEDS TO STAMP ELECTRICAL, AND FIRE SHEETS. THIS WAS | | STATED IN PREVIOUS REVIEW NOTES.. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-07-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-03 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-03 |
Time |
11:58 |
Sent To |
PC |
|
Notes |
2008-07-03 11:58:44 | | | | | ** DENIED AUDIT** | | | | 1) NOTE: PLEASE SEE THE PLANS SUBMITTED NOW SHOW A | | COMPLETELY DIFFERENT SIGNATURE OF THE DESIGNER OF | | RECORD FOR THE ELECTRICAL SHEETS. | | THE NEW SHEETS CONTAIN A SIGNATURE WHICH IS NOT THE | | SAME AS THE PREVIOUS SHEETS. SHEETS FROM JANUARY PLANS, | | APRIL PLANS AND MAY PLANS CONTAIN DIFFERENT | | SIGNATURES. | | | | NEED SIGNATURE VERIFICATION LETTER FOR LEGAL SIGNATURE | | TO PLACE IN FILE AND ALL SIGNATURES NEED TO | | COORDINATE? | | THE OTHER OPTION IS FOR THE DESIGNER OF RECORD TO COME | | INTO THIS OFFICE TO RE-SIGN, DATE AND SEAL PLANS. | | SPOKE TO ARCHITECT IN CHARGE OF PROJECT FOR URS AND HE | | MENTIONED THEY WOULD HAVE ENGINEER COME INTO OFFICE. A | | TIME WILL BE SET UP FOR MEETING. | | | | ONE SET OF ELECTRICAL SHEETS FROM EACH WILL BE RETAINED | | BY THIS OFFICE. FS 471.025, FAC61G15-23.002 | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-05-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-05-20 |
Time |
12:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-05-20 |
Time |
12:08 |
Sent To |
|
|
Notes |
2008-05-20 12:08:18 | ** DENIED2ND AUDIT** | | | | ** PLEASE SEE SOME ITEMS STILL REMAIN FROM PREVIOUS | | AUDIT. | | | | 1) NOTE: PLEASE SEE AFFIDAVITS ARE NOW ONLY BEING | | SUBMITTED. PLEASE SEE THESE ARE BEING MADE OUT TO | | BALFOUR CONCORD. THE CONTRACTOR ON THIS PROJECT IS | | BALFOUR/BEATTY. | | PLEASE COORDINATE. | | PLEASE ALSO SEE NOTICE TO BUILDING OFFICIAL SUBMITTED | | WHICH IS IN FACT PHOTO-COPIES AND ARE NOT ORIGINAL. | | THESE CONTAIN STAMPS *REVIEWED FOR COMPLIANCE8 FROM THE | | PRIVATE PROVIDER. | | PLEASE ONLY INCLUDE ORIGINAL DOCUMENTS AND PLEASE BE | | SURE TO FILL OUT WITH THE CORRECT CONTRACTOR. | | | | 2) NOTE: PLEASE SUBMIT PLANS IN A NEAT AND ORDERLY | | FASHION WITH STAPLES SECURING ALL SHEETS TOGETHER. | | SEVERAL SHEETS IN THE BACK OF THE SETS WERE NOT SECURED | | TO THE REST OF THE SET. PLEASE ALSO DO NOT ATTACHED ALL | | OTHER DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS. | | PLEASE SUBMIT THESE IN SOME SORT OF BINDER/FOLDER WHICH | | THESE DOCUMENTS MAY BE READILY GONE OVER. | | PLEASE KNOW THESE WERE DETACHED AND PLACED INTO | | SEPARATE CLIPS AT THIS TIME. | | PLEASE ALSO KNOW DUE TO SOME COMMENTS BELOW SOME | | DOCUMENTS MAY ALSO BE RETAINED BY THIS OFFICE. | | FBC 106.1.2, 106.1, 106.1.3, 106.5 FOR ADDITIONAL | | INFORMATION, SUBMITTING OF PLANS, RECORD DOCUMENTS. | | | | 3) NOTE: PLEASE SEE THE FLORIDA ENERGY EFFICIENCY CODE | | CALCULATIONS SUBMITTED ARE NOT CODE COMPLIANT. | | PLEASE SEE 13-400.3.A AS THE INCORRECT VERSION WAS | | SUBMITTED. THE VERSION SUBMITTED IS 3.0 WHEN THE CODE | | REQUIRES VERSION 2.5 WHEN USING FLA-COM PROGRAM. | | IN ANY CASE METHOD *A* MAY NOT BE USED AS THIS IS A | | TENANT SPACE BUILD OUT IN A BUILDING AND IS NOT A * | | WHOLE BUILDING*. PLEASE SEE THE DEFINITIONS IN THE FBC | | 13-400.0.A. PLEASE PROVIDE INFORMATION AND | | DOCUMENTATION EXPLAINING HOW METHOD *A* SUBMITTED IS | | BEING USED. | | | | 4) NOTE: PLEASE SEE THE SUBMITTED CALCULATIONS WERE | | ALSO STAMPED AS BEING CODE COMPLIANT BY THE PRIVATE | | PROVIDER WHEN IN FACT THESE ARE NOT SIGNED, DATED OR | | SEALED BY ANY ENGINEER OF RECORD. PLEASE SEE 13-103.1 | | AS THIS SCOPE OF WORK IS REQUIRED TO BE DONE BY A | | LICENSED ENGINEER. PLEASE SEE THE SUBMITTED DOCUMENTS | | WERE SIGNED BY AN INDIVIDUAL WHICH DOES NOT LIST ANY | | LICENSE INFORMATION. IN FACT THE DOCUMENTS SUBMITTED | | CLEARLY SHOW A (PHOTO-COPIED SIGNATURE* FROM A | | *PREPARER* WHICH IS NOT LISTED AS A PE AND NOT AS ONE | | OF THE DESIGNERS OF RECORD. THIS IS THE SAME ON ALL | | THREE SETS SUBMITTED. | | WHEN SIGNING, DATING AND SEALING ANY DOCUMENTS AN | | ENGINEER MUST USE AN ORIGINAL SIGNATURE. | | FS 471.025, FAC 61G15-23.002 | | | | 5) NOTE: ** PLEASE SEE THE LIGHTING CALCULATIONS ALSOO | | SUBMITTED ARE IN FACT PHOTO-METRIC LEVELS WHICH ARE NOT | | LIGHTING PERFORMANCE CALCULATIONS REQUIRED PER FBC | | 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE KNOW THESE | | SHALL NOT BE USED IN LIEU OF REQUIRED CALCULATIONS. | | PLEASE KNOW THESE WERE GONE OVER IN MEETING HELD BEFORE | | RESUBMITTING PLANS HOWEVER THESE ARE STILL BEING | | SUBMITTED. | | ** FOR INFORMATION: | | PLEASE KNOW ANY DOCUMENTS SUBMITTED AND PART OF THE | | DESIGN OF A PROJECT BY THE ENGINEER SHALL BE SIGNED, | | DATED, SEALED CONTAINING TITLE BLOCKS ETC. | | | | 6) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE | | CALCULATIONS MEETING THE FLORIDA BUILDING CODE | | 13-415.2, 13-415.2.ABC.1.1, .1.2. | | THE LIGHTING DENSITIES LISTED ON SHEET E200 ARE NOT | | COMPLETE. PLEASE COMPLETE AS SEE LEVELS IN TABLES IN | | THE FBC. PLEASE BE SURE THE LIGHTING FIXTURE LEGEND | | COORDINATES WITH CALCULATIONS, NUMBERS OF FIXTURES, | | TYPES OF FIXTURES ETC TO COORDINATE CODE COMPLIANCE. | | ** PLEASE KNOW SOME LEVELS SHOWN IN THE SPACE BY SPACE | | EXCEED LEVELS IN 13-415.2.B | | | | 7) NOTE: PLEASE SEE MISSING MAXIMUM TIMES ON OVER RIDES | | AND OCCUPANCY SENSOR DEVICES. THE RESPONSE MENTIONS TO | | SEE E-100 AND E200 HOWEVER THE REVISED DEVICES, OVER | | RIDES AND OCCUPANCY SENSOR SWITCHES DO NOT INDICATE ANY | | TIMES. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE SEE SOME DEVICES ON PLANS ARE NOT ON SYMBOL | | LEGEND: FOR EXAMPLE PLEASE SEE READING ROOM AND OUTSIDE | | READING ROOM IN HALL AND SOME OTHER LOCATIONS WHICH | | SHOW A S IN A BOX HOWEVER NO OTHER DESIGNATION IS | | SHOWN. THERE IS NO S IN A SQUARE BOX ON SYMBOL LEGEND. | | WHICH DEVICE IS THIS? | | PLEASE COMPLETE. | | | | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A | | NOTICE GIVEN AT THIS TIME. | | | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-02-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-10 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-10 |
Time |
10:40 |
Sent To |
|
|
Notes |
2008-02-11 10:40:15 | | | ** DENIED REVIEW ** | | | | 1) NOTE: PLEASE SEE THE REQUIRED AFFIDAVIT AS REQUIRED | | PER FS 553.791(4)(C) WAS NOT SUBMITTED. | | | | 2) NOTE: PLEASE SEE THE PLANS NEED TO CONTAIN THE | | FOLLOWING RELEVANT CODES STATED FOR DESIGN. | | 2004 FBC W/2007 REVISIONS. | | 2005 NFPA-70 | | 2003 NFPA-101 | | 2002 NFPA-72 | | | | ** SOME MAY ALREADY BE SHOWN HOWEVER NOT ALL. PLEASE BE | | AWARE OF ANY CODES REQUIRED BY OTHER TRADE REVIEWERS. | | PLEASE ALSO SEE THE CODES ARE NEEDED ON ELECTRICAL AS | | WELL. | | FBC 106.5, 106.1.2, FS 553.73 | | | | 3) NOTE: PLEASE SEE THAT THE SUITE/UNIT NUMBER IS | | REFLECTED ON TITLE BLOCKS. PLEASE KNOW IF ANY | | PARTICULAR SHEET DOES NOT NEED TO BE REVISED FOR CODE | | COMPLIANCE, THEN THIS MAY BE HAND PRINTED ON SHEETS. | | FBC 106.1.2, 106.5 | | FAC 61G1-16.004, FAC 61G15-23.002 | | | | 4) NOTE: PLEASE SEE MISSING LICENSE INFORMATION ON | | TITLE BLOCKS FOR URS CORPORATION. PLEASE SEE MISSING | | CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL | | FIRM WHICH IS REQUIRED PER FS 481.219 AND TO BE ON | | PLANS PER FAC 61G1-16.004 | | PLEASE ALSO SEE FS 471.023 AND FAC 61G15-23.002 WHICH | | REQUIRES CERTIFICATE OF AUTHORIZATION NUMBER FOR | | ENGINEERING BUSINESS AS WELL. | | | | 5) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED | | GROUNDING AND INSTALLATION OF SYSTEMS PER NEC 517. | | PLEASE SEE 517.1 COMMENTARIES WHICH ARE QUOTED BELOW: | | | | *THE REQUIREMENTS OF ARTICLE 517 ARE INTENDED TO APPLY | | TO ALL TYPES OF HEALTH CARE FACILITIES. THE | | REQUIREMENTS FOR EACH TYPE OF HEALTH CARE FACILITY ARE | | NEVERTHELESS INTENDED TO BE APPLIED IN A VERY SPECIFIC | | MANNER. FOR EXAMPLE, IN A SUITE OF DOCTORS' OFFICES | | WITHIN AN OFFICE BUILDING, A DOCTOR'S BUSINESS OFFICE | | WOULD BE TREATED AS AN ORDINARY OCCUPANCY AND WOULD BE | | REQUIRED TO MEET ONLY THE APPLICABLE PORTIONS OF OTHER | | PARTS OF THIS CODE. HOWEVER, THE EXAMINING ROOMS | | ATTACHED TO THE DOCTOR'S BUSINESS OFFICE WOULD BE | | REQUIRED TO MEET THE PROVISIONS OF PART II AND 517.45 | | IN ARTICLE 517.* | | PLEASE ALSO BE AWARE ANY UNDER GROUND SLAB AREAS TO | | EQUIPMENT SHALL BE RMC, IMC OR OTHER APPROVED CONDUIT | | SYSTEM. 517.13, 250, AND SEE USES PERMITTED IN CHAPTER | | 13 FOR CONDUITS. | | | | 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND NOTES | | ON PLANS ACCORDINGLY. | | | | 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | A LIGHTING CONTROL SYSTEM IS BEING NOTED HOWEVER OVER | | RIDES AND LOCATIONS ARE IN NEED OF MEETING THE ABOVE | | SECTIONS. MANY OF THESE ARE SHOWN AS STANDARD SWITCHES. | | SOME AREAS ARE EXEMPT PER EXCEPTIONS LISTED IN | | 13-415.1.ABC.1.1 | | PLEASE LIST SCHEDULING. | | PLEASE LIST MAXIMUM TIMES ON OVER RIDES. | | PLEASE SUBMIT DETAIL FOR ANY LIGHTING WHICH IS BEING | | OVER RIDDEN FROM A LOCATION IN WHICH THE LIGHTING BEING | | CONTROLLED CAN NOT BEE SEEN. | | PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS WHICH | | CAN NOT BE REVIEWED AND MAY HAVE NEW COMMENTS WHICH CAN | | NOT BE MADE AT THIS TIME. | | | | 8) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE | | CALCULATIONS PER 13-415.2. | | | | 9) NOTE: PLEASE SEE ROOM 14-312 WHICH INDICATES *FAN | | ROOM* PLEASE INDICATE AS DEDICATED ELECTRICAL | | /MECHANICAL SPACE. | | 110.26 | | | | 10) NOTE: PLEASE CLARIFY THE ITD ROOM # 14-121 ON | | PLANS. ARCHITECTURAL SHEETS INDICATE 1HR FIRE RATING | | AND THIS ROOM CONTAINS SEPARATE A/C SYSTEM HOWEVER | | COULD NOT LOCATE THE REQUIRED DISCONNECTING MEANS PER | | 645.10 FOR ALL. PLANS CONTAIN NOTE FOR MOST RECEPTACLES | | HOWEVER SOME ARE FED FROM A SEPARATE PANEL ALL | | TOGETHER. PLEASE CLARIFY USE OF THESE. | | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE | | NEW PROPOSED IT EQUIPMENT. | | 110.3, 90.7. PLEASE BE SURE SPECS/CUT SHEETS INDICATE A | | LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING | | LABORATORY). | | | | 11) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE | | SECONDARY SIDE OF TRANSFORMER T112.5 ARE REQUIRED TO BE | | RATED FOR THE OVER CURRENT PROTECTION IN WHICH ARE | | BEING TERMINATED. PLEASE SEE 240.21, 310.16, 240.4 AND | | 110.14. | | PLEASE KNOW IT IS ACCEPTABLE TO MOVE TO THE NEXT SIZE | | BREAKER (DEVICES 800AMPS AND LOWER) ON TYPICAL FEEDERS | | ETC HOWEVER NOT ON THE SECONDARY SIDE OF THE | | TRANSFORMER. | | THIS WAS INFORMATION GIVEN AND CONFIRMED BY THE CODE | | PANELIST AND NFPA. | | PLEASE ADJUST THESE TAPPED CONDUCTORS. | | | | 12) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE ATTACHMENT | | POINT FOR THE TRANSFORMER GROUNDING PER 250.30, 250.50, | | AND 250.66. | | | | 13) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON EXISTING | | EL41A FOR NEW LOAD BEING ADDED TO EXISTING SYSTEM | | SERVICE EQUIPMENT. | | 220.87. | | | | 14) NOTE: PLEASE KNOW THE NEW ELECTRIC WATER HEATER IS | | REQUIRED TO BE FIGURED INTO ENERGY CONSUMPTION. PLEASE | | SEE 13-412.1.ABC.3.4 | | | | 15) NOTE: PLEASE INDICATE ALL MINIMUM LEVELS FOR | | SOUNDING DEVICES PER FBC 11-4.28.1, .2. PLEASE SEE | | VISUAL DEVICES APPEAR TO BE OK ATTHIS TIME FOR ADA | | COMPLIANCE. | | PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM FIRE | | MARSHAL WHICH MAY AFFECT THE ELECTRICAL AND/OR F | | SHEETS. | | | | 16) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS PER | | 13-413.1.ABC.1.1. PLEASE SEE MORE SPECIFICALLY THE | | FEEDERS FROM 4TH FLOOR TO ECB. | | | | 17) NOTE: PLEASE PROVIDE MORE INFORMATION PER | | 517.71-517.78. | | SOME ITEMS ARE SHOWN HOWEVER NOT ALL. | | | | 18) NOTE: PLEASE KNOW THESE PLANS MAY BE REFERENCED FOR | | LOW VOLTAGE SCOPE OF WORK HOWEVER THE LV WILL BE | | REQUIRED TO BE UNDER SEPARATE PERMIT. THIS IS NOTED FOR | | INFORMATION ONLY AT THIS TIME. | | | | ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED | | THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS | | TIME. | | | | PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE ARE ANY | | QUESTIONS PLEASE DO NOT HESITATE IN CONTACTING THIS | | OFFICE/REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2009-02-24 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2009-02-24 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2009-02-24 |
Time |
13:25 |
Sent To |
|
|
Notes |
2009-02-24 13:26:15 | REVISION #4 AND #7. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
N |
Date |
2008-11-10 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-11-10 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-11-10 |
Time |
11:00 |
Sent To |
|
|
Notes |
2008-11-10 11:01:24 | NO LIFE SAFETY OR FIRE PROTECTION SYSTEMS CHANGE NOTED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-09-23 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-09-23 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-09-23 |
Time |
14:33 |
Sent To |
|
|
Notes |
2008-09-23 14:34:18 | STAMPED REVISED SHEETS FP001, FP101, FP201 AND FA200. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-07-11 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-07-11 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-07-11 |
Time |
11:19 |
Sent To |
|
|
Notes |
2008-07-11 11:20:11 | PLANS APPROVED BY M.A. WILLIAMS AND STAMPED ON THIS | | DATE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2008-05-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-05-20 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-05-20 |
Time |
14:32 |
Sent To |
|
|
Notes |
2008-05-20 14:57:56 | *****PROVISO***** | | | | 07.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO | | THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON | | THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | SHALL BE NO LESS THAN 3" IN HEIGHT.IT IS UNDERSTOOD | | THAT CLEVELAND CLINIC WILL BE THE ONLY TENANT ON THE | | FLOOR, HOWEVER THE SUITE NUMBER SHALL BE DISPLAYED | | | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE | | ABOVE COMMENT AND THE OTHERS PLAN REVIEWERS COMMENTS | | HAVE BEEN ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | | | | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-02-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-02-14 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-02-14 |
Time |
14:50 |
Sent To |
|
|
Notes |
2008-02-14 15:57:29 | *****DENIED***** | | | | | | 01.THE ASSIGNED SUITE NUMBER SHALL BE INCLUDED IN THE | | ADDRESS LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET. | | | | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 03.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION | | CODE AS LISTED IN THE CODE NOTES ON SHEET G0201, NFPA | | 101- LIFE SAFETY CODE - 2003 EDITION SHALL BE | | REFERENCED. | | | | 04.NO EXIT LIGHTS/DOORS SHOWN ON LIFE SAFETY PLAN | | (SHEET A0001) TO DETERMINE IF THE PATH OF TRAVEL IS TO | | THE EXIT(S). | | | | 05.ON SHEET A0401,EXIT LIGHTS DIRECT PERSON(S) TO | | THE CORRIDORS.WHERE DO PERSON(S) GO ONCE THEY'RE IN | | THE CORRIDOR?CORRELATE THIS SHEET WITH G0201, E200 | | | | 06.GENERAL SHEET NOTE # 5 INCOMPLETE AS SHOWN ON | | SHEETS A0501 AND A0502. | | | | 07.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO | | THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON | | THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | SHALL BE NO LESS THAN 3" IN HEIGHT. | | | | 08.DOOR(S) LEADING DIRECTLY TO THE CORRIDOR SHALL BE | | AN APPROVED, LISTED, AND LABELED FIRE DOOR & ASSEMBLY | | IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 80. | | | | 09.SPECIFY THE INTERIOR FINISH CLASSIFICATION FOR THE | | WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR | | CLASS C. | | | | 10.PLEASE CLARIFY OR CORRELATE THE NUMBER OF CORRIDOR | | EMERGENCY LIGHTING FIXTURES.ON SHEET E200 AND SHEET | | E201 THER ARE15 DEVICES SHOWN, BUT 30 DEVICES ARE | | LISTED IN THE DESIGN CRITERIA LUMINAIRES USED | | INFORMATION DATA ON SHEET E201. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2009-03-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-03-27 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-03-27 |
Time |
11:05 |
Sent To |
E |
|
Notes |
2009-03-27 11:05:54 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2009-03-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-03-06 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-03-06 |
Time |
09:45 |
Sent To |
E |
|
Notes |
2009-03-06 09:46:48 | TO "DPALMER" DESK/1 REV AND 1 SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-10-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-24 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-24 |
Time |
14:14 |
Sent To |
P |
|
Notes |
2008-10-24 14:15:15 | TO "P" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-10-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-10 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-10 |
Time |
16:27 |
Sent To |
|
|
Notes |
2008-10-10 16:30:39 | TO "COMM" BD#50 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-10-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-10 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-10 |
Time |
16:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-09-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-03 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-03 |
Time |
15:41 |
Sent To |
|
|
Notes |
2008-09-03 15:49:40 | TO "COMM" BD#35--EXPEDITED-- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-06-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-17 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-17 |
Time |
11:20 |
Sent To |
|
|
Notes |
2008-07-01 09:43:37 | TO "COMM" BD#24 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-05-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-12 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-12 |
Time |
16:56 |
Sent To |
|
|
Notes |
2008-05-12 16:57:21 | TO "COMM" BD#34/PLANS ON RACK/2 ROLLS**PRIVATE | | PROVIDER** |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-07-10 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2008-02-15 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2008-02-08 |
Time |
09:25 |
Sent To |
|
|
Notes |
2008-02-08 09:25:22 | TO "COMM" BD#18--PRIVATE PROVIDER-- |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2008-09-16 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-09-16 |
Time |
12:31 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-09-16 |
Time |
12:30 |
Sent To |
|
|
Notes |
2008-09-16 12:31:01 | PAGE M200 REV 5 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-05-19 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-05-19 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-05-19 |
Time |
11:28 |
Sent To |
E |
|
Notes |
2008-05-19 11:30:10 | SMOKE CONTROL ANALYSIS AND ORIGINAL NOTICE TO BUILDING | | OFFICIAL SUBMITTED PRIOR TO REVIEW BY OTHER TRADES. | | THIS REVIEW IS NOW IN PASS STATUS FOR 1ST RESUBMITTAL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2008-05-14 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-05-14 |
Time |
17:01 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-05-14 |
Time |
15:48 |
Sent To |
|
|
Notes |
2008-05-14 17:01:02 | AUDIT #: 2ND | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | 1 THROUGH 5: OK | | | | 6. THE SMOKE CONTROL SYSTEM FOR THIS BUILDING HAS BEEN | | TESTED, COMMISSIONED AND IS COMPLETE. A NEW RATIONAL | | ANALYSIS SUPPORTING THE DESIGN OF THE PROPOSED | | MODIFICATIONS WITHIN THIS TENANT SPACE AND A SEQUENCE | | OF OPERATIONS SHALL BE SUBMITTED PRIOR TO PERMIT | | ISSUANCE. | | | | NOTE: ONCE CONSTRUCTION IS COMPLETE AND PRIOR TO A | | CERTIFICATE OF OCCUPANCY FOR THIS SPACE, THE BUILDING | | SMOKE CONTROL SYSTEM SHALL BE RE-TESTED AND | | RE-COMMISSIONED. THE EXTENT OF THE TESTING NECESSARY TO | | DEMONSTRATE THE FUNCTIONALITY OF NEW AND EXISTING | | PORTIONS OF THE SYSTEM MUST BE COORDINATED WITH THE | | CHIEF MECHANICAL INSPECTOR, FIRE MARSHAL AND | | COMMISSIONING AGENT. ANALYSIS AND TESTING SHALL BE DONE | | IN ACCORDANCE WITH FBCB SECTION 909. | | | | 7 THROUGH 11: OK | | | | 12. THE NOTICE TO BUILDING OFFICIAL AFFIDAVIT WHICH WAS | | PROVIDED IS A PHOTOCOPY. PLEASE PROVIDE ORIGINAL | | DOCUMENTATION WITH ORIGINAL SIGNATURES AND NOTARY | | STAMP. | | | | NEW: A PLAN REVIEW AFFIDAVIT FROM CAPRI ENGINEERING WAS | | NOT PROVIDED FOR THE FOLLOWING MECHANICAL PAGES WITH | | THIS SUBMITTAL: M300, M600, M700, M701, M702 SIGNED | | 3/11/08. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-02-15 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-02-14 |
Time |
13:41 |
Sent To |
|
|
Notes |
2008-02-15 11:22:31 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. M200: THERE ARE SEVERAL LOCATIONS THROUGHOUT THIS | | FLOOR PLAN WHERE DUCTS ARE SHOWN PENETRATING FIRE | | RESISTANCE RATED WALL ASSEMBLIES WITHOUT ANY OPENING | | PROTECTIVE. EXAMPLE: FAN ROOM 14-312 IS FULLY ENCLOSED | | IN TYPE 2A WALLS, WHICH CARRY A 1-HOUR RATING AS SHOWN | | ON PG A1002. THERE ARE AT LEAST TWO DUCTS EXITING THIS | | ROOM WITHOUT FIRE DAMPERS AT THE WALL PENETRATIONS. | | THERE ARE MULTIPLE OTHER INSTANCES. PLEASE COORDINATE | | FLOOR PLANS FOR ARCHITECTURAL AND MECHANICAL, SHOWING | | OPENING PROTECTIVES WHERE REQUIRED IN ACCORDANCE WITH | | FBC, M 607.5. | | | | 2. M200: CONVERSELY, THERE IS A FIRE DAMPER SHOWN IN A | | 24X10 DUCT PENETRATING A TYPE 6 WALL (NON RATED | | ACCORDING TO PG A1002) NEAR COLUMN LINE F. A FIRE | | DAMPER IS SHOWN AT THIS LOCATION. FIRE DAMPERS ARE TO | | BE INSTALLED IN ACCORDANCE WITH THEIR LISTING PER FBC, | | M 607.2. THE SPECIFIC BRAND OF FIRE DAMPER IS NOT KNOWN | | AT THIS TIME BUT THE LISTING LIKELY REQUIRES THAT IT BE | | INSTALLED IN A RATED ASSEMBLY. AGAIN, PLEASE COORDINATE | | MECHANICAL AND ARCHITECTURAL FLOOR PLANS ACCORDINGLY. | | | | 3. M200: EF-1 AND SF-1 SHOW NEW LOUVERS TO BE INSTALLED | | IN EXTERIOR WALLS. LOUVERS ARE CLASSIFIED AS PANEL | | WALLS PER FAC RULE 9B-72 AND AS SUCH, PRODUCT APPROVAL | | IS REQUIRED. PROVIDE PRODUCT APPROVAL FOR BUILDING PLAN | | REVIEW. PRODUCT APPROVALS SHALL BE APPROVED IN WRITING | | BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THIS | | OFFICE FOR REVIEW IN ACCORDANCE WITH FBC 106.3.3. | | | | 4. M200: THE LOUVER OPENING FOR EF-1 MAY BE IN A 2-HOUR | | RATED EXTERIOR WALL IN ACCORDANCE WITH FBC TABLE 602. | | BASED ON THE DOCUMENTATION PROVIDED, IT IS UNCLEAR AS | | TO THE ALLOWABLE PERCENTAGE OF UNPROTECTED OPENINGS IN | | THIS WALL. OUTDOOR AIR EXHAUST AND INTAKE OPENINGS | | LOCATED IN EXTERIOR WALLS SHALL MEET THE PROVISIONS FOR | | EXTERIOR WALL OPENING PROTECTIVES IN ACCORDANCE WITH | | THE FLORIDA BUILDING CODE, BUILDING PER FBC, M 401.6. | | IF A CLAIM FOR ALLOWED UNPROTECTED OPENINGS IS MADE, | | PLEASE PROVIDE ALL NECESSARY INFORMATION AND | | CALCULATIONS FOR BUILDING PLAN REVIEW. | | | | 5. M200: A 44X12 ?SMOKE CONTROL TRANSFER OPENING IN | | WALL W/ SMOKE DAMPER? IS SHOWN IN WALL ON NORTH SIDE OF | | SPACE. THERE IS NOT INDICATION THAT THIS IS ALSO A FIRE | | DAMPER. A FIRE DAMPER IS REQUIRED AT THIS LOCATION AS | | IT IS LOCATED IN A 1-HOUR RATED WALL AS INDICATED ON | | ARCHITECTURAL FLOOR PLAN. ALSO, BY WHAT MEANS WILL THIS | | SMOKE DAMPER BE CONTROLLED? SMOKE DAMPERS SHALL BE | | ACTUATED BY ONE OF THE METHODS LISTED IN FBC, M | | 607.3.2.1. THIS DAMPER IS NOT PART OF THE BASE BUILDING | | SMOKE CONTROL SYSTEM. WILL THE BASE BUILDING DESIGN BE | | REVISED TO INCORPORATE THIS NEW SMOKE DAMPER? | | | | 6. M200: RELATED TO COMMENT #5 ABOVE, SPECIFIC NOTE #6 | | ON PLAN CALLS FOR SMOKE DAMPERS TO BE INSTALLED IN | | DUCTS IN VARIOUS LOCATIONS THROUGHOUT THE FLOOR PLAN, | | INCLUDING SUPPLY AND RETURN DUCTS WHICH ARE PART OF A | | ?SMOKE REMOVAL SYSTEM IN DUCT.? | | A) EXISTING PAC-1 SUPPLY AND RETURN DUCT IS BEING SHOWN | | AS PART OF A SMOKE REMOVAL SYSTEM. PAC-1 HAS NO ROLE IN | | THIS BUILDING?S SMOKE CONTROL SYSTEM OTHER THAN IT WILL | | BE SHUT DOWN DURING SMOKE CONTROL MODE. | | B) A RATIONAL ANALYSIS OF THIS BUILDING?S SMOKE CONTROL | | SYSTEM HAS BEEN PERFORMED AND SUBMITTED AS PART OF THE | | BASE BUILDING?S PERMIT RECORD. ANY MODIFICATIONS TO THE | | SMOKE CONTROL SYSTEM (AS PROPOSED BY THIS TENANT) MUST | | BE INCORPORATED INTO THE RATIONAL ANALYSIS, INCLUDING | | ANY ADDITIONAL DAMPERS WHICH NEED TO BE CONTROLLED BY | | THE SYSTEM IN ACCORDANCE WITH FBC, M 513.4. | | C) ITD ROOM 14-121 IS SHOWN ON FLOOR PLAN TO 1-HOUR | | RATED WITH TYPE 2A WALLS EXTENDING TO THE UNDERSIDE OF | | THE DECK ABOVE ON THREE SIDES. ONE OF THESE WALLS IS | | SHOWN ON FLOOR PLAN BISECTING THE 60X20 OUTLET OF THE | | SUPPLY DUCT FOR THE BUILDING SMOKE CONTROL SYSTEM. THIS | | WOULD BE AN IMPEDIMENT TO MOST OF THE AIR, TRAPPING IT | | IN THE ITD ROOM AND PREVENTING THE AIR FROM | | PRESSURIZING THE ENTIRE FLOOR, WHICH IS ITS PURPOSE. | | PLEASE SHOW HOW THE RATING OF THIS ROOM IS TO BE | | ACHIEVED WITHOUT DEFEATING THE BUILDING SMOKE CONTROL | | SYSTEM. ADDITIONALLY, THE REQUIRED RATING OF THE TYPE | | 2A WALL CAN NOT BE MAINTAINED AS IT CROSSES THE OPEN | | END OF THE 60X20 DUCT. | | D) WEST OF THE SERVICE ELEVATOR THERE IS AN | | UNIDENTIFIED ENCLOSED AREA SURROUNDED BY TEMPORARY | | CORRIDOR 14-036. THIS AREA ENCLOSES THE EXHAUST INLET | | FOR THE BUILDING SMOKE CONTROL SYSTEM. THIS ENCLOSURE | | CREATES A PLENUM SPACE TO BE USED BY THE EXHAUST | | PORTION OF THE BUILDING SMOKE CONTROL SYSTEM. THIS | | SPACE IS NOT PART OF THE BASE BUILDING DESIGN AS IT IS | | NOT SHOWN ON THE BASE BUILDING PLANS. THE WALL TYPES | | AND FINISHES ARE NOT KNOWN AS THEY ARE NOT IDENTIFIED | | ON THE ARCHITECTURAL FLOOR PLAN FOR THE TENANT SPACE. | | THERE ARE TRANSFER DUCTS AND SMOKE DAMPERS SHOWN | | FEEDING THIS PLENUM SPACE WHICH ARE ALSO NOT PART OF | | THE CURRENT SMOKE CONTROL SYSTEM DESIGN. PLEASE CLARIFY | | THE INTENT, IDENTIFY IF THESE WALLS CARRY ANY SORT OF | | RATING AND DETERMINE IF THIS DESIGN WILL BE | | INCORPORATED INTO THE BASE BUILDING DESIGN. FBC, M | | 513.2 AND 513.4 | | | | 7. M200: SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL | | FOR PROPOSED NEW AC-1 IN ITD ROOM IN COMPLIANCE WITH | | FBC, M 307.2.2. | | | | 8. PROVIDE DETAIL FOR A LISTED THROUGH-PENETRATION | | FIRESTOP SYSTEM TO BE USED WHERE CONDENSER AND/OR | | CONDENSATE PIPING IS TO PENETRATE FIRE RESISTANCE RATED | | WALL ASSEMBLIES IN ACCORDANCE WITH FBC 712.3. | | | | 9. M500: FIRE DAMPER DETAILS, THESE DETAILS ARE LIKELY | | TO BE IN CONFLICT WITH FIRE DAMPER MANUFACTURER?S | | INSTALLATION INSTRUCTIONS. FIRE DAMPERS, SMOKE DAMPERS | | AND COMBINATION FIRE/SMOKE DAMPERS LOCATED WITHIN AIR | | DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE | | INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS | | SECTION, AND THE MANUFACTURER?S INSTALLATION | | INSTRUCTIONS AND LISTING PER FBC, M 607.2. COORDINATE | | DETAIL ON PLANS WITH MANUFACTURER?S INSTALLATION | | INSTRUCTIONS OR PROVIDE A NOTE ON PLANS INDICATING THAT | | IN THE EVENT OF A CONFLICT THE MANUFACTURER?S | | INSTRUCTIONS SHALL PREVAIL. | | | | 10. M200 AND M701: SF2 SHALL BE PROVIDED WITH A DUCT | | SMOKE DETECTOR. SMOKE DETECTORS SHALL BE INSTALLED IN | | SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAN | | 2,000 CFM IN THE SUPPLY AIR DUCT IN ACCORDANCE WITH | | FBC, M 606.2.1. | | | | 11. M701: SEQUENCE OF OPERATION DOES NOT HAVE ANY | | INDICATION THAT SMOKE DETECTORS IN THE SUPPLY DUCT HAVE | | BEEN TAKEN INTO ACCOUNT AS ONLY THE RETURN SMOKE | | DETECTORS ARE SHOWN IN THE SEQUENCE AND DIAGRAMS. NOTE: | | FBC, M 606.2.1 REQUIRES DETECTORS AT A MINIMUM IN THE | | SUPPLY DUCT AND 606.2.2 REQUIRES THEM ADDITIONALLY IN | | THE RETURN DUCT. THE SUPPLY DETECTORS SHALL ALSO | | INITIATE A FAN SHUT-DOWN AND INITIATE AN ALARM SIGNAL | | IN ACCORDANCE WITH THIS SECTION. | | | | 12. THESE PLANS HAVE BEEN REVIEWED AND SUBMITTED UNDER | | THE PRIVATE PROVIDER SYSTEM AS ESTABLISHED UNDER FS | | 553.791. THIS STATUTE REQUIRES AN AFFIDAVIT FROM THE | | FEE OWNER ACKNOWLEDGING THE DECISION TO USE PRIVATE | | PROVIDERS UNDER FS 533.791(4)(C). NO SUCH INFORMATION | | COULD BE FOUND IN THE PACKAGE SUBMITTED FOR PERMIT. | | PROVIDE ALL REQUIRED DOCUMENTATION PURSUANT TO THIS | | STATUTE. | | | | NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH A | | DESCRIPTION OF HOW THE COMMENT HAS BEEN ADDRESSED (OR | | WHY IT HAS NOT) AS WELL AS WHERE THE RELEVANT | | INFORMATION CAN BE FOUND. ALSO, PLEASE RETURN ONE SET | | OF OLD/VOIDED PLANS FOR REFERENCE. THESE STEPS WILL | | HELP TO ENSURE A TIMELY REVIEW UPON RESUBMISSION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-11-06 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-11-06 |
Time |
08:17 |
Sent To |
|
|
Notes |
2008-11-06 08:17:42 | SUBMITTAL FOR WATER SAMPLE RESULTS NOT REQUIRED |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2008-10-27 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-10-27 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-10-27 |
Time |
15:30 |
Sent To |
|
|
Notes |
2008-10-27 15:34:50 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P202 REVISION 4 NOT APPROVED. VENT FROM FD-2 IS | | SHOWN CONNECTING TO THE COLD WATER LINE. SECTION 608.1. | | | | 2. SHT P300 VENT FROM FD-2 DOES NOT REFLECT THE FLOOR | | PLAN AS SHOWN ON SHT P202. THE FUTURE VENT SHOWN ON THE | | FLOOR PLAN IS NOT SHOWN ON THE SANITARY RISER DIAGRAM. | | (SEE SPECIFIC NOTE #1 SHT P202). | | | | 3. A REVISION FOR SHT P201 IS REQUIRED TO REFLECT THE | | CHANGE SHOWN ON THE SANITARY RISER AT COL. L-7, 12TH | | FLOOR. SECTION 106.1.3. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2008-09-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-09-04 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-09-03 |
Time |
17:09 |
Sent To |
|
|
Notes |
2008-09-04 08:23:40 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P202 REVISIONS 3 & 4 WERE NOT FOUND. PLEASE | | CLOUD ALL REVISIONS AND INDICATE REVISIONS WITH THE | | REVISION NUMBER. SECTION 106.1.3. | | | | 2. SHT P202 DRINKING FOUNTAINS WERE DELETED. PER TABLE | | 403.1 MINIMUM 2 DRINKING FOUNTAINS ARE REQUIRED. PLEASE | | INDICATE WHERE THE REQUIRED DRINKING FOUNTAINS ARE | | LOCATED. | | | | 3. SHT P300 WATER ISOMETRIC RISER DIAGRAM DOES NOT | | REFLECT THE CHANGE IN THE FLOOR PLAN INDICATED ON SHT | | P202 AT S1 SINK IN X-RAY ROOM 14307. PLEASE CORRELATE. | | SECTIONS 106.1.1 & 604. | | | | 4. SHT P300 ALL CHANGES/REVISIONS TO THE FLOOR PLAN | | SHALL BE SHOWN ON THE SANITARY RISER DIAGRAM. S-1 SINK | | DOES NOT SHOW CHANGE AS WELL AS THE DELETED DRINKING | | FOUNTAINS. PLEASE CORRELATE. SECTION 106.1.1 & TABLE | | 710.1(2). | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2008-06-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-06-17 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-06-17 |
Time |
16:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-05-21 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-05-21 |
Time |
18:26 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-05-21 |
Time |
18:26 |
Sent To |
|
|
Notes |
2008-05-21 18:51:07 | AUDIT DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | CITY MUNICIPAL CODE | | | | ****FROM PREVIOUS AUDIT: | | | | 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE | | NUMBER, (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN | | THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS | | 481.219, 481.2055. | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | 2. OK | | | | 3. SUBMIT DETAILS FOR THE ACCESSIBLE TOILET ROOMS | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & | | 11-4.22 WITH ALL SUBSECTIONS. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED | | COMPLETLY. SHOW COMPLIANCE WITH: | | ___FOR LAVS: | | A. 11-4.19.4 EXPOSED PIPES & SURFACES | | B. 11-4.19.5 FAUCETS | | C. 11-4.19.6 MIRRORS (SHOWS 46") | | | | 4. SHT A0201 TOILET ROOMS 14-310 & 14-105 THE DOOR | | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR | | ANY FIXTURE. SECTION 11-4.22.3. | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | 5. OK | | 6. OK | | | | 7. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING | | COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED | | COMPLETLY. SHOW COMPLIANCE WITH SECTION 11-4.24.5 CLEAR | | FLOOR SPACE. (FORWARD APPROACH REQUIRED). | | | | 8. OK | | | | 9. SHT P001 WATER HEATER WH-1 PIPING DETAIL. THE VACUUM | | RELIEF VALVE IS SHOWN IN THE HOT WATER LINE. THE VALVE | | SHALL BE INSTALLED IN THE COLD WATER LINE PER SECTION | | 504.2.--FLOOR DRAINS ARE NOT AN APPROVED INDIRECT | | WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED. | | SECTIONS 802.3 & 802.3.2. (MAKE CHANGES TO PIPING & | | RISER DIAGRAMS).--SUBMIT CALCULATIONS FOR THE SIZE | | OF THE EXPANSION TANK, OR PROVIDE MANUF. TABLES | | INDICATING THE MODEL NUMBER AND MAXIMUM GALLONS FOR | | MODEL NUMBER FOR THE EXPANSION TANK TO VERIFY CORRECT | | SIZE. SECTION 607.3.2. | | ****RESPONSE NOTED, BUT THE EXPANSION TANK CALCULATIONS | | WERE NOT FOUND. | | | | 10. OK | | 11. OK | | 12. OK | | 13. OK | | 14. OK | | 15. OK | | 16. OK | | | | 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING ALL | | PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS ETC. | | SECTIONS 106.3.5.1.3 & 604. | | ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN, NOR DOES IS MEET CODE | | REQUIREMENS. THE HOT SUPPLY MAIN CONNECTS INTO THE COLD | | BRANCH LINE TO THE SINKS IN ROOMS 144, 146, 147, 148, | | 149 & 160. SECTION 604.2. --THE HOT SUPPLY TO THE | | SINK IN THE ROOM NEAR THE READING ROOM DOES NOT REFLECT | | THE FLOOR PLAN. SECTIONS 106.1.1 & 601.1.--THE | | PIPING TO THE SINKS FOR ROOMS 112/115 & ROOM 141 DO NOT | | REFLECT THE FLOOR PLAN. SECTIONS 106.1.1 & 601.1.-- | | THE WATER SUPPLIES ARE CROSSED INDICATING THE HOT ON | | THE RIGHT AND THE COLD ON THE LEFT SIDE OF THE SINKS IN | | ROOMS 110, 111, 112, 115, 116, 117, 132, 133, 140 & | | 142. SECTION 607.4.--THE WATER HAMMER ARRESTORS | | SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE | | RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201 | | | | 18. OK | | | | 19. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION | | TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE | | MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN | | OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE, | | SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY | | WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT | | THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT, | | INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF | | FLORIDA STATUTE. | | ****RESPONSE NOTED, BUT SEE COMMENTS NUMBER ONE AND TWO | | OF THE ELECTRICAL REVIEW AND COMMENT NUMBER TWELVE OF | | THE MECHANICAL REVIEW. PLEASE SHOW COMPLIANCE WITH | | THESE REQUIREMENTS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-02-11 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-02-11 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-02-11 |
Time |
12:03 |
Sent To |
|
|
Notes |
2008-02-11 12:43:18 | AUDIT DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | CITY MUNICIPAL CODE | | | | 1. ALL ARCHITECTURAL SHEETS. THE BUSINESS LICENSE | | NUMBER, (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN | | THE TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS | | 481.219, 481.2055. | | | | 2. PER TABLE 403.1 2 DRINKING FOUNTAINS ARE REQUIRED. | | PLEASE INDICATE THE LOCATION OF EACH REQUIRED DRINKING | | FOUNTAIN. SECTION 106.1.1. | | | | 3. SUBMIT DETAILS FOR THE ACCESSIBLE TOILET ROOMS | | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & | | 11-4.22 WITH ALL SUBSECTIONS. | | | | 4. SHT A0201 TOILET ROOMS 14-310 & 14-105 THE DOOR | | SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR | | ANY FIXTURE. SECTION 11-4.22.3. | | | | 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING | | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS | | WELL AS 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE | | DIFFICULTY BENDING OR STOOPING. | | | | 6. SHT A1002 TOILET ROOMS 14-104, 14-105 & 14-310 STATE | | "CT-2 AT WET WALL, PT ALL OTHER WALLS". PER SECTION | | 1210.2 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND | | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT | | SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE | | FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE | | MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS | | NOT ADVERSELY AFFECTED BY MOISTURE. | | PAINTED SURFACES DOES NOT MEET THE REQUIREMENT FOR A | | "HARD SURFACE". | | | | 7. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING | | COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. | | | | 8. SHT P001 INDICATE THE LISTING NUMBER FOR THE FLOOR | | AND WALL PENETRATIONS. SECTION 712.3.1.2. THROUGH | | PENETRATIONS SHALL BE PROTECTED BY AN APPROVED | | PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN | | ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM | | POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA) | | OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN | | THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL | | PENETRATED.--ALSO THE FLOOR SLEEVE DETAIL INDICATES | | THAT THE SLEEVE SHALL BE 1" ABOVE THE FLOOR. WITH THE | | RISER CLAMP SITTING ON THE SLEEVE, PLEASE SUBMIT A | | DETAIL SHOWING HOW THE SLEEVE IS ATTACHED TO THE FLOOR | | AND INDICATE THE MATERIAL AND GUAGE FOR THE SLEEVE. | | SECTION 308.9. | | | | 9. SHT P001 WATER HEATER WH-1 PIPING DETAIL. THE VACUUM | | RELIEF VALVE IS SHOWN IN THE HOT WATER LINE. THE VALVE | | SHALL BE INSTALLED IN THE COLD WATER LINE PER SECTION | | 504.2.--FLOOR DRAINS ARE NOT AN APPROVED INDIRECT | | WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED. | | SECTIONS 802.3 & 802.3.2. (MAKE CHANGES TO PIPING & | | RISER DIAGRAMS).--SUBMIT CALCULATIONS FOR THE SIZE | | OF THE EXPANSION TANK, OR PROVIDE MANUF. TABLES | | INDICATING THE MODEL NUMBER AND MAXIMUM GALLONS FOR | | MODEL NUMBER FOR THE EXPANSION TANK TO VERIFY CORRECT | | SIZE. SECTION 607.3.2. | | | | 10. SHT P202 CONDENSATE SHALL NOT DRAIN TO THE SANITARY | | SYSTEM. MUNICIPAL CODE ARTICLE III SECTION | | 90-125(B)(5). CONDENSATE SHALL CONNECT TO THE | | CONDENSATE RISERS AND DRAIN SEPARATELY. | | | | 11. SHT P202 SPECIFIC NOTES #3 IS NOT FOUND ON THE | | FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1. | | | | 12. SHT P202 SHOWS 2 COLD WATER SUPPLIES TO THE SINK IN | | ROOM 14-130. HOT WATER IS REQUIRED PER SECTION 607.1. | | | | 13. SHT P202 WATER & VENT DROPS TO SINKS IN ROOMS | | 14-010, 14-100 & 14-106 AS WELL AS THE WATER & VENT | | DROPS BETWEEN THE TOILET ROOMS ARE SHOWN DROPING DOWN | | OUT OF THE WALL. PLEASE CLARIFY. | | | | 14. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN F-7 | | DOES NOT REFLECT THE FLOOR PLAN. THE EXTENTION OF THE | | FUTURE SANT IS NOT SHOWN ON THE FLOOR PLAN, THE FLOOR | | PLAN SHOWS OFFSETS IN THE 4" BRANCH LINE TO THE TOILET | | ROOM AND THE 1-1/2" LINE TO THE S-1 SINK. OFFSETS ARE | | NOT SHOWN ON THE RISER DIAGRAM. THE LINE TO THE S-1 | | SINK IS INDICATED AS 1-1/2" ON THE FLOOR PLAN, BUT 2" | | ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION | | 106.1.1. | | | | 15. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-7 | | DOES NOT REFLECT THE FLOOR PLAN, NOR DOES IS MEET CODE. | | THE HUB DRAIN FOR THE A/C CONDENSATE IS NOT APPROVED | | PER MUNICIPAL CODE ARTICLE III SECTION 90-125(B)(5). | | PLEASE DELETE. | | | | 16. SHT P300 THE SANITARY RISER DIAGRAM AT COLUMN L-5 | | DOES NOT REFLECT THE FLOOR PLAN. THE S-1 SINK AT THE | | SOUTH SIDE OF COLUMN SHOWS INDIVICUAL VENTS ON THE | | FLOOR PLAN, BUT SINGLE VENT ON THE RISER DIAGRAM.-- | | FLOOR PLAN SHOWS THE SANT. FOR THE SINK RUNNING SOUTH | | OF THE 3" STACK, BUT THE RISER DIAGRAM SHOWS THE PIPING | | RUNNING EAST THEN SOUTH.--THE 1ST RISER ON THE | | BRANCH LINE TO THE WEST, (FOR ROOMS 14-140 & 14-142), | | RISER IS SHOWN CONNECTING TO THE MAIN LINE RUNNING | | NORTH & SOUTH ON THE FLOOR PLAN, BUT ON THE WEST BRANCH | | LINE ON THE RISER DIAGRAM. OTHER RISERS ON THE WEST | | BRANCH LINE DO NOT REFLECT THE FLOOR PLAN.--THE 3" | | LINE CAPPED FOR THE FUTURE SHOWN ON THE FLOOR PLAN IS | | NOT SHOWN ON THE RISER DIAGRAM.--VENTING DOES NOT | | REFLECT THE FLOOR PLAN FOR THE FUTURE VENT AND THE SINK | | IN ROOM 14-161.--THE BRANCH LINES AT THE UPSTREAM | | END OF THE RISER DIAGRAM SHOW 4 RISERS TO THE WEST AND | | 1 RISER ON THE EAST BRANCH ON THE FLOOR PLAN, BUT SHOW | | 2 RISERS ON EACH BRANCH ON THE RISER DIAGRAM. PLEASE | | CORRELATE AND SUBMIT THE RISER DIAGRAMS THAT REFLECT | | THE FLOOR PLAN. SECTIONS 106.1.1 & TABLE 710.1(2). | | | | 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM SHOWING ALL | | PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS ETC. | | SECTIONS 106.3.5.1.3 & 604. | | | | 18. SUBMIT AN ISOMETRICCONDENSATE RISER DIAGRAM | | SHOWING ALL PIPE SIZES TRAPS, VENTS, POINT OF | | CONNECTION TO THE CONDENSATE RISER ETC. SECTION | | 106.3.5.1.3. | | | | 19. PRIVATE PROVIDER AFFIDAVIT PROJECTS-IN ADDITION | | TO THE SIGNED AFFIDAVIT FROM THE PRIVATE PROVIDER, WE | | MUST ALSO CHECK TO SEE THAT THE OWNER HAS SIGNED AN | | OWNER ACKNOWLEDGEMENT LETTER PER FLORIDA STATUTE, | | SECTION 553.791(4)(C).THE LETTER IS THE MEANS BY | | WHICH THE OWNER ACKNOWLEDGES THAT THEY ARE AWARE THAT | | THEIR PROJECT IS BEING REVIEWED (AND IF RELEVANT, | | INSPECTED) UNDER THE PRIVATE PROVIDER PROVISIONS OF | | FLORIDA STATUTE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | |
|
|