Plan Review Details - Permit 08020067
Plan Review Stops For Permit 08020067
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2010-02-04 Cont ID  
Sent By rmcdouga Date 2010-02-04 Time 13:44 Rev Time 0.00
Received By rmcdouga Date 2010-02-04 Time 13:44 Sent To  
Notes
2010-02-04 13:47:40CONTRACTOR SUBMITED CORRECTED CHANGE OF DESIGNER OF
 RECORD LETTER FROM THE ARCHITECT WITH SIGNED RECEIPT
 MAIL SLIP. PLANS WITH NEW TITLE BLOCK WERE STAMPED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2010-01-20 Cont ID  
Sent By rmcdouga Date 2010-01-20 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2010-01-20 Time 11:17 Sent To  
Notes
2010-01-20 12:00:152004 FBC W/2007 REVISIONS
 APPLICATION FOR SUCCESSOR ARCHITECT
  
 DENIED BY BUILDING
  
 1) TWO SETS OF PLANS, WHICH ARE COPIES OF THE APPROVED
 PLANS WITH THE TITLE BLOCKS CHANGED TO A DIFFERENT
 DESIGNER OF RECORD (ARCHITECT) WERE SUBMITTED. THE
 INTENT OF THE NEW ARCHITECT IS TO ADOPT THE WORK OF THE
 ORIGNIAL DESIGNER OF RECORD AS ALLOWED BY FAC
 61G1-18.002. THE SIGNED AND SEALED LETTER FROM THE
 SUCCESSOR ARCHITECT STATES THAT A NOTIFICATION LETTER
 WAS SENT TO THE GARRISON DESIGN GROUP. THE DESIGNER OF
 RECORD IS THE ENGINEER THAT SIGNED AND SEALED THE
 ORIGINAL PLANS, LUIS A. LOPEZ, PE # 59805. IN
 ACCORDANCE WITH FAC 61G15-27.001 AND FAC 61G1-18.002
 THE ORIGINAL ENGINEER IS REQUIRED TO BE NOTIFIED BY
 CERTIFIED LETTER OF THE SUCCESSOR'S INTENTION TO USE
 THE ORIGINAL PROFESSIONAL ENGINEER'S WORK. THE
 SUCCESSOR ARCHITECT OR ENGINEER MUST BE ABLE TO
 DOCUMENT AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS
 IN FACT RECREATED ALL THE WORK DONE BY THE ORIGINAL
 PROFESSIONAL ENGINEER. FURTHER THE SUCESSOR MUST TAKE
 ALL PROFESSIONAL AND LEGAL RESPONSIBLITY FOR THE
 DOCUMENTS WHICH HE SEALED AND SIGNED AND CAN IN NO WAY
 EXEMPT HIMSELF FROM SUCH FULL RESPONSIBILITY.
  
 PLEASE SUBMIT TWO NEW LETTERS WHICH INDICATE THAT THE
 ABOVE REQUIREMENTS HAVE BEEN MET AND THAT DOCUMENTATION
 CAN BE PROVIDED UPON REQUEST.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-03-09 Cont ID  
Sent By rmcdouga Date 2009-03-09 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2009-03-09 Time 15:25 Sent To  
Notes
2009-03-09 15:27:06PLANS STAMPED FOR IMPACT FEES AND RE-RECORDED NOC
 SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-03-02 Cont ID  
Sent By rmcdouga Date 2009-03-02 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2009-03-02 Time 16:46 Sent To  
Notes
2009-03-02 16:46:10NOTE: PERMIT STATUS WILL BE CHANGED TO 'P' AND PERMIT
 PRINTED WHEN IMPACT FEES HAVE BEEN PAID AND PLANS
 STAMPED BY PALM BEACH COUNTY.
  
  
 BUILDING PROVISO
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 3'-0"
 X 6'8" ARCHED TOP WOOD ENTRY DOOR FOR APPROVAL PRIOR TO
 INSTALLATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-12-04 Cont ID  
Sent By rmcdouga Date 2008-12-04 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2008-12-04 Time 16:23 Sent To  
Notes
2008-12-04 16:39:50DENIED BY BUILDING
  
 1) THE NOTICE OF COMMENCEMENT HAS EXPIRED AND WILL NEED
 TO BE RE-RECORDED. THE ACTUAL WORK IS REQUIRED TO START
 WITHIN 90 DAYS OF THE RECORDING. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 ENTRY DOOR IS FOR A GLAZED RADIUS TOP DOUBLE DOOR FROM
 BRANNEN MILLWORK. THIS DOES NOT MATCH THE SINGLE DOOR
 THAT IS SPECIFIED ON THE PLANS. SUBMIT THE CORRECT
 PRODUCT APPROVAL. RULE 9B-72
  
 4) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT CASEMENT WINDOWS DOES NOT HAVE A 36" X 66" SIZE
 CONFIGURATION X CASEMENT WINDOW LISTED. THE PLANS
 SPECIFY THIS SIZE FOR WIDOW "E" IN THE SCHEDULE ON
 A1.1. PLEASE CORRECT. FAC RULE 9B-72
  
 NOTE: ITEMS 3 AND 4 CAN BE "PROVISO-ED" AND THE CORRECT
 PRODUCT APPROVALS SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION. ITEMS 1 AND 2 CAN BE ADDRESSED WHEN
 PERMIT IS READY FOR ISSUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-15 Cont ID  
Sent By rmcdouga Date 2008-08-15 Time 09:07 Rev Time 0.00
Received By rmcdouga Date 2008-08-15 Time 09:06 Sent To  
Notes
2008-08-15 07:26:472004 FBC W/2007 REVISIONS
 ADDITION AND REMODEL
  
 DENIED BY BUILDING
  
 1) THE NOTICE OF COMMENCEMENT HAS EXPIRED AND WILL NEED
 TO BE RE-RECORDED. THE ACTUAL WORK IS REQUIRED TO START
 WITHIN 90 DAYS OF THE RECORDING. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHEET C1 WHICH CONTAINED THE DESIGN CRITERIA WAS NOT
 RE-SUBMITTED. PLEASE SPECIFY DESIGN CRITERIA ON THE
 PLANS. ( APPLICABLE CODE, WINDSPEED, EXPOSURE CATEGORY,
 ETC.) FBC R301.2
  
 4) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS SEPARATED
 BY LESS THAN 6 FEET (1828 MM) SHALL HAVE NOT LESS THAN
 A ONE-HOUR FIRE-RESISTIVE RATING WITH EXPOSURE FROM
 BOTH SIDES. PROJECTIONS SHALL NOT EXTEND TO A POINT
 CLOSER THAN 4 FEET (1220 MM) FROM AN ADJACENT
 PROJECTION OR WALL. THE PLANS SHOW LESS THAN 6 FEET TO
 THE PROPERTY LINES AT GARAGE AND SECOND FLOOR ADDITION.
 THEREFORE, THE DISTANCE TO THE STRUCTURES ON THE
 ADJACENT LOT ARE REQUIRED TO BE NOTED ON THE SITE PLAN
 AND IF LESS THAN 6 FEET THEN THE WALLS MUST HAVE ONE
 HOUR FIRE RATING AND HAVE NO OPENINGS(R302.2).
  
 5) PLEASE DO NOT TAPE THE RAS 117 CALCULATIONS TO THE
 SIGNED AND SEALED PLANS (SEE SHEET A4.0) . SOME OF THE
 TEXT IS MISSING FROM THE BOTTOM RIGHT SIDE OF THE RAS
 CALCULATIONS. THE PRODUCT APPROVAL THAT WAS SUBMITTED
 DOES NOT CORRESPOND WITH THE CALCULATIONS. THE PRODUCT
 APPROVAL IS FOR A GAF BUILT-UP ROOF SYSTEM NOA NO.
 03-0501.05 AND THE CALCULATIONS ARE FOR A FIRESTONE
 SYSTEM NOA NO. 05-0830.10.
 PLEASE COORDINATE.
  
 6) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 ENTRY DOOR IS NON-IMPACT FOR THE GLAZING. SUBMIT
 PRODUCT APPROVALS FOR THE STORM PANELS FOR THIS DOOR.
 SUBMIT AN INSTALLATION SCHEDULE, SPECIFY THE FASTENER
 TYPE, FASTENER SPACING, MOUNT TYPE, EDGE DISTANCE,
 ETC.
  
 7) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. FBC CHAPTER 13-6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-14 Cont ID  
Sent By rmcdouga Date 2008-02-14 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2008-02-14 Time 06:59 Sent To Z
Notes
2008-02-14 08:34:442004 FBC W/2007 REVISIONS
 ADDITION AND REMODEL
  
 DENIED BY BUILDING
  
 1) A NOTICE OF COMMENCEMENT WILL BE REQUIRED. FS
 713.13
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) UPDATE THE APPLICABLE CODE ON SHEET C1 TO THE 2004
 FBC WITH 2007 REVISIONS.
  
 4) THE FIRM LICENSE NUMBER OR THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE GARRISON DESIGN GROUP IS
 REQUIRED IN THE TITLE BLOCK OF THE PLANS. SEE FAC
 61G1-16.004 OR 61G15-23.002.
  
 5) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL.
  
 6) SHOW COMPLIANCE WITH R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
  
 7) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS AT THE MAIN
 HOUSE.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 8) THE ROOM OFF THE BATHROOM IN THE GUEST HOUSE DOES
 NOT COMPLY WITH R310.1 EMERGENCY ESCAPE AND RESCUE
 REQUIRED.
 BASEMENTS WITH HABITABLE SPACE AND EVERY SLEEPING ROOM
 SHALL HAVE AT LEAST ONE OPENABLE EMERGENCY ESCAPE AND
 RESCUE OPENING. WHERE BASEMENTS CONTAIN ONE OR MORE
 SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM, BUT SHALL NOT
 BE REQUIRED IN ADJOINING AREAS OF THE BASEMENT. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) ABOVE THE FLOOR. WHERE A DOOR OPENING HAVING
 A THRESHOLD BELOW THE ADJACENT GROUND ELEVATION SERVES
 AS AN EMERGENCY ESCAPE AND RESCUE OPENING AND IS
 PROVIDED WITH A BULKHEAD ENCLOSURE, THE BULKHEAD
 ENCLOSURE SHALL COMPLY WITH SECTION 310.3 . THE NET
 CLEAR OPENING DIMENSIONS REQUIRED BY THIS SECTION SHALL
 BE OBTAINED BY THE NORMAL OPERATION OF THE EMERGENCY
 ESCAPE AND RESCUE OPENING FROM THE INSIDE. EMERGENCY
 ESCAPE AND RESCUE OPENINGS WITH A FINISHED SILL HEIGHT
 BELOW THE ADJACENT GROUND ELEVATION SHALL BE PROVIDED
 WITH A WINDOW WELL IN ACCORDANCE WITH SECTION R310.2 .
 THE EMERGENCY ESCAPE AND RESCUE OPENING SHALL BE
 PERMITTED TO OPEN INTO A SCREEN ENCLOSURE, OPEN TO THE
 ATMOSPHERE, WHERE A SCREEN DOOR IS PROVIDED LEADING
 AWAY FROM THE RESIDENCE. PROVIDE AN APPROPRIATE OPENING
 OR SPECIFY ON THE PLAN THAT THIS ROOM IS NOT TO BE USED
 FOR SLEEPING PURPOSES.
  
 9) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS AT THE
 GUEST HOUSE.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 10) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED AT
 THE GUEST HOUSE.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 11) SHOW COMPLIANCE WITH R319.1 LOCATION REQUIRED. IN
 AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY TABLE
 R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE THE
 USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS. 5.WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE
 GROUND.
  
 12) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES. IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM). SEE
 A2.0 AND A5.1.
  
 13) ON SHEET A4.1 IN THE CONNECTOR SCHEDULE THE SIMPSON
 LGT-2 REQUIRES 16-16D SINKERS INTO THE TWO MEMBER
 GIRDER PER THE SIMPSON CATALOG, NOT 1-1/2". PLEASE
 CORRECT. FBC 106.1.1* CITY AMENDMENTS.
  
 14) THE SIMPSON HGAM 10 SPECIFIED IN THE CONNECTOR
 SCHEDULE IS TESTED AND LISTED FOR MASONRY APPLICATIONS
 NOT AS A WOOD CONNECTOR. PLEASE REVISE. FBC 106.1.1*
 CITY AMENDMENTS.
  
 15) THE ROOF SLOPE IS SPECIFIED AS 5:12 ON A3.1 AND AS
 4:12 ON A4.1 AND A5.0. PLEASE CORRECT. FBC 106.1.1*
 CITY AMENDMENTS.
  
 16) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR
 ROOF ZONES 1,2 AND 3 ON A4.1. SEE TABLE R301.2(2) AND
 FIGURE R301.2(8).
  
 17) ON SHEET A5.0 THE ROOF TILE ATTACHMENT IS SPECIFIED
 AS (2) 10D NAILS. SMOOTH OR SCREW SHANK NAILS WILL NOT
 PROVIDE AN ADEQUATE MOMENT OF RESISTANCE. PLEASE
 SPECIFY RING SHANK NAILS. FBC R905.3 AND FAC RULE
 9B-72.
  
 18)SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. REVISE
 SHEET A5.0.
  
 19) THE PLAN NOTES ON A5.3 SPECIFY BEARING WALLS TO BE
 1 HOUR FIRE RATED CONSTRUCTION WITH 5/8" TYPE X GYPSUM.
 THE PLANS DO NOT REFLECT THIS. PLEASE REVISE.
  
 20) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR
 THE WINDOW OPENINGS ON THE PLANS. THEY ARE NOT LISTED
 IN THE SCHEDULE ON A1.1. SEE TABLE R301.2(2).
  
 21) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION,
 AND DESIGN PRESSURE FOR THE GAF BUR SYSTEM. SUBMIT RAS
 117 CALCULATIONS FOR ENHANCED FASTENING AT PERIMETER
 AND CORNER AREAS AS REQUIRED. SEE LIMITATION #7 OF NOA.
 FBC 106.1.2* CITY AMENDMENTS.
  
 22) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 JELD-WEN DOORS EXPIRED AUGUST 15, 2007. SUBMIT A
 CURRENT NOA. FAC RULE 9B-72
  
 23) SUBMIT PRODUCT APPROVALS FOR DOOR #9, WHICH THE
 DOOR SCHEDULE INDICATES HAS A VISION PANEL. FAC RULE
 9B-72
  
 24) SUBMIT PRODUCT APPROVALS FOR DOOR #1 IN THE DOOR
 SCHEDULE, THE ARCHED CEDAR ENTRY DOOR WITH SIDELITES
 AND TRANSOM. FAC RULE 9B-72
  
 25) THE PRODUCT APPROVAL SUBMITTED FOR THE MULLIONS
 DOES NOT HAVE ADEQUATE DESIGN PRESSURES TO BE INSTALLED
 BETWEEN THE 10' WIDE FRENCH DOOR/SIDELITE ASSEMBLY AND
 THE TRANSOM WINDOWS ABOVE. PLEASE CORRECT. RULE 9B-72
  
 26) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORMS. FBC CHAPTER 13-6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-02-12 Cont ID  
Sent By btrobaug Date 2009-02-12 Time 15:03 Rev Time 0.00
Received By btrobaug Date 2009-02-12 Time 14:44 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-03 Cont ID  
Sent By btrobaug Date 2008-12-03 Time 14:11 Rev Time 0.00
Received By btrobaug Date 2008-12-03 Time 11:12 Sent To P
Notes
2008-12-03 13:18:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 COMMENTS FOR SHEETE2.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} LOCATE ALL SERVICE EQUIPMENT ON THE RISER DIAGRAM.
 IF PANEL "B" IS THE GUEST HOUSE PANEL IT MUST HAVE A
 MAIN BREAKER OR A DISCONNECT PER 225.31, LOCATED PER
 225.32 AND GROUNDED PER 250.32.
  
 3} THE WASHER /LAUNDRY CIRCUIT IS NOT LISTED ON THE
 PANEL SCHEDULE. 210.11(C)(2).
  
 4} THERE ARE TWO GUEST HOUSE WATER HEATERS LISTED IN
 PANEL "B", BUT ONLY ONE SHOWN ON THE FLOOR PLAN,
 CORRELATE SAME.VERIFY THE MAIN HOUSE WATER HEATER IS
 FED FROM PANEL "B", IF IN FACT PANEL "B" IS LOCATED IN
 THE GUEST HOUSE.
  
 5} A SERVICE RECEPTACLE PER 210.63 IS REQUIRED FOR THE
 ACU FOR THE GUEST HOUSE.
  
 6} THE LOAD CALCULATION LISTS ALL HEAT STRIPS AT 10000W
 WHICH DOES NOT CORRELATE WITH THE PANEL SCHEDULE OR
 MANUFACTURERS SPEC'S ON M1.
  
 7} A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR
 SHOWN ON THE RISER DIAGRAM UNLESS ALL DOCUMENTS
 REQUIRED FOR A RESIDENTIAL GENERATOR ARE SUBMITTED WITH
 THIS APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-04 Cont ID  
Sent By btrobaug Date 2008-08-04 Time 14:32 Rev Time 0.00
Received By btrobaug Date 2008-08-04 Time 12:29 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-06 Cont ID  
Sent By mcruz Date 2008-08-03 Time 11:22 Rev Time 0.00
Received By btrobaug Date 2008-02-06 Time 08:55 Sent To M
Notes
2008-02-06 16:51:28 
  
 APPLICATION #08020067
 ELECTRICAL PLAN REVIEW
 270 BARCELONA ROAD
 2/6/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ON SHEET E2:
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 215.5 NEC AND 106.3.5.4 FBC.
 INDICATE WHICH IS NEW AND WHICH IS EXISTING. THIS
 INCLUDES THE GUEST HOUSE.
  
 2} THE LOAD CALCULATION TABLE ON SHEET E2 INDICATES THE
 ?GENERAL LIGHTING? LOADS TO BE ON 20 AMP CIRCUITS WITH
 #14 AWG CONDUCTORS IN VIOLATION OF 310.16, MUST BE #12
 CONDUCTORS OR 15 AMP BREAKERS WHERE ALLOWED. ALSO NOTE
 THAT THE TABLE INDICATES 21 OF THOSE BRANCH CIRCUITS.
  
 3} THE THREE SMALL APPLIANCE CIRCUITS LISTED IN THE
 CALCULATION TABLE, ARE CALCULATED AT 1200VA, THOSE
 CIRCUITS ARE REQUIRED TO BE CALCULATED AT 1500VA PER
 220.52. ALSO NOTE THERE ARE ONLY TWO SMALL APPLIANCE
 CIRCUITS LISTED ON THE PANEL SCHEDULES, CORRELATE SAME.
 NOTE: SEE 210.11(C)(1), TWO PER KITCHEN REQUIRED, CHECK
 PANEL SCHEDULES.
  
 4} THE GFI?S LISTED AT 3000 VA EACH IN THE CALCULATION
 TABLE, ARE IN VIOLATION OF 210.20(B)(1), 210.21(B)(2),
 AND 310.16, AS THOSE CIRCUITS WOULD NEED TO BE RATED
 FOR 25 AMPS.
  
 5} THE RANGE IS LISTED AS 2.6 KVA ON A 30 AMP CIRCUIT
 IN PANEL ?A?, CORRELATE WITH THE LOAD CALCULATION, ALSO
 SEE 422.11(A).
  
 6} THE WATER HEATERS LISTED IN PANELS ?A? AND ?C? ARE
 LISTED AS 2.6 KVA ON A 30 AMP CIRCUIT, SEE COMMENT #5.
  
 7} THERE ARE TWO ?APPLIANCE? CIRCUITS IN BOTH PANELS
 ?A? AND ?C? @2.6 KVA ON A 20 AMP CIRCUIT IN VIOLATION
 OF 310.16, 210.20(B)(1), AND 210.21(B)(2). INDICATE
 WHAT THESE ?APPLIANCES? ARE ON THE SCHEDULES, SEE
 408.4.- NEW VERBAGE FOR 2005 NEC: "THE IDENTIFICATION
 SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT
 TO BE DISTINGUISHED FROM ALL OTHERS."
  
 8} THERE IS ONE DISHWASHER IN THE LOAD CALCULATIONS
 LISTED AS 1200 VA, THERE ARE TWO ON THE PANEL SCHEDULES
 (A & C) LISTED AT 1500 VA, CORRELATE SAME.
  
 9} THE DISPOSAL IN THE CALCULATION IS LISTED AT 900 VA,
 AND LISTED AS 1500 VA ON A 20 AMP CIRCUIT, IN PANEL
 SCHEDULE ?A?.
  
 10} THE DRYER IN PANEL SCHEDULE ?A? IS LISTED AT 2600
 VA, OR 10.8 AMPS, ON A 30 AMP CIRCUIT, AND 5000 VA IN
 THE CALCULATIONS, CORRELATE SAME.
  
 11} THE ATTIC IN THE GUEST HOUSE MUST COMPLY WITH
 210.63 AND 210.70(A)(3) SINCE MECHANICAL EQUIPMENT WILL
 BE INSTALLED.
  
 12} THERE ARE TWO A/C AND AHU?S LISTED AS #1.
  
 SHEET E1: GIVEN THE FACT THAT THERE IS NO WAY TO
 DETERMINE NEW FROM EXISTING, THIS REVIEW IS DONE AS IF
 ALL WORK IS NEW
  
 1} THE DISCONNECTS FOR THE CONDENSING UNITS DO NOT
 COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. NOTE, ONLY
 TWO SHOWN, THREE IN THE SCHEDULES.
  
 2} R313.1.1 RESIDENTIAL BUILDING CODE, SMOKE ALARMS
 SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE
 ARTICLE FOR COMPLETE TEXT. TWO ARE MISSING FROM THE
 UPPER BEDROOMS, AND ONE DOWNSTAIRS, SEE REVIEWED PLAN.
 ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2010-03-29 Cont ID  
Sent By jgomez Date 2010-03-29 Time 16:04 Rev Time 0.00
Received By jgomez Date 2010-03-29 Time 16:04 Sent To  
Notes
2010-03-29 16:15:17SENT TO R3.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2010-03-03 Cont ID  
Sent By rmcdouga Date 2010-03-03 Time 11:16 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2010-03-03 11:16:31R-8

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2010-01-19 Cont ID  
Sent By shill Date 2010-01-19 Time 11:19 Rev Time 0.00
Received By shill Date 2010-01-19 Time 11:19 Sent To  
Notes
2010-01-19 11:19:50RESTAMP ROUTED TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-10 Cont ID  
Sent By adarroug Date 2009-02-10 Time 10:59 Rev Time 0.00
Received By adarroug Date 2009-02-10 Time 10:59 Sent To E
Notes
2009-02-10 11:00:19TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-31 Cont ID  
Sent By adarroug Date 2008-10-31 Time 14:16 Rev Time 0.00
Received By adarroug Date 2008-10-31 Time 14:16 Sent To Z
Notes
2008-10-31 14:17:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-21 Cont ID  
Sent By adarroug Date 2008-07-21 Time 14:34 Rev Time 0.00
Received By adarroug Date 2008-07-21 Time 14:34 Sent To Z
Notes
2008-07-21 14:34:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-14 Cont ID  
Sent By rmcdouga Date 2008-02-14 Time 09:59 Rev Time 0.00
Received By rmcdouga Date 2008-02-05 Time 10:03 Sent To  
Notes
2008-02-05 10:03:16TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2011-02-17 Cont ID  
Sent By rkussner Date 2011-02-17 Time 10:03 Rev Time 0.00
Received By rkussner Date 2011-02-17 Time 10:03 Sent To  
Notes
2011-02-17 10:04:30***LANDSCAPE NOT REQUIRED***
  
 PLEASE REFER TO PERMIT NUMBER 11020306 FOR LANDSCAPE
 PERMIT AND PLANS.--RAK

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-11-21 Cont ID  
Sent By rkussner Date 2008-11-21 Time 12:07 Rev Time 0.00
Received By rkussner Date 2008-11-21 Time 11:42 Sent To PC
Notes
2008-11-21 12:17:39***LANDSCAPE REVIEW PASSED***
  
 NOTE ADDED TO PLAN----PROVIDE IRRINGATION IN R-O-W.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-03-03 Cont ID  
Sent By rmcdouga Date 2009-03-03 Time 14:08 Rev Time 0.00
Received By rmcdouga Date 2009-03-03 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-12-07 Cont ID  
Sent By rregueir Date 2008-12-07 Time 14:44 Rev Time 0.00
Received By rregueir Date 2008-12-07 Time 14:39 Sent To PC
Notes
2008-12-07 14:44:34REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: MECHANICAL PLANS HAVE NOW BEEN SUBMITTED FOR
 REVIEW FOR THE FIRST TIME. ALL PREVIOUS REVIEW COMMENTS
 HAVE BEEN ADDRESSED. PLEASE ADDRESS THE FOLLOWING
 RELATED TO NEW MECHANICAL PLANS:
  
 1. THE GUEST AREA AND 2ND FLOOR, ALL DUCTS ARE MISSING
 SIZES. PLEASE SHOW THE SIZE OF ALL AIR DISTRIBUTION
 COMPONENTS TO BE INSTALLED IN ORDER TO DEMONSTRATE
 COMPLIANCE WITH FBCR M1601.1 AND M1601.3 AS WELL AS
 M1602.4 FOR BALANCED RETURN AIR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-08-04 Cont ID  
Sent By tgordon Date 2008-08-04 Time 15:38 Rev Time 1.20
Received By tgordon Date 2008-08-04 Time 15:38 Sent To P
Notes
2008-08-04 16:32:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 THE FOLLOWING NOTES ARE FROM THE LAST REVIEW 2-7-08
 THAT WERE NOT CORRECTED.
  
 1) THE MAIN HOUSE AND THE GUEST HOUSE CAN NOT BE ON THE
 SAME ENERGY CALCULATION. PLEASE SUBMIT SEPARATE ENERGY
 CALCULATIONS FOR EACH BUILDING, SEE 2004 FBC
 13-101.2.5.1. (THE OLD ENERGY CALCULATIONS WERE
 RESUBMITTED NOT REVISED ONES).
  
 2) PLEASE HAVE THE REVISED ENERGY CALCULATIONS SIGNED
 BY OWNER/AGENT ALSO, SEE 2004 FBC 13-600.3.ABC.2. (SEE
 RESPONSE ABOVE #1).
  
 3) ENERGY CALCULATIONS LINE 8B DOES NOT SHOW THE RAISED
 WOOD FLOOR OR INSULATION, SEE 2004 FBC 13-605.2.A.1.1
 AND 13-605.1.C.2. PLEASE CORRECT ALSO THE PLANS IF
 NEEDED. (SEE RESPONSE ABOVE #1).
  
 4) SHOW AN A/C EQUIPMENT SCHEDULE WITH ALL THE
 PERTINENT INFORMATION ON THE MECHANICAL PLAN, SEE 2004
 WPB AMEND. 106.3.5.4 (10). (NO MECHANICAL PLANS WERE
 SUBMITTED FOR REVIEW).
  
 5) SHOW ALL THE BATHROOM EXHAUST FANS ON THE MECHANICAL
 PLAN AS THEY ARE ON THE ELECTRICAL PLAN, SEE 2004 FBC/R
 R303.3 EXCEPT. (SEE RESPONSE ABOVE #4).
  
 6) SHOW THE LOCATION OF THE GUEST HOUSE A/C CONDENSER
 UNIT ON THE MECHANICAL AND ELECTRICAL PLANS, SEE 2004
 FBC/R M1307. (SEE RESPONSE ABOVE #4).
  
 7) A/C SYSTEM 2 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,601 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT. (REVISED COOLING
 LOAD CALCULATIONS WERE SUBMITTED BUT NO MECHANICAL
 PLANS WERE SUBMITTED).
  
 8) A/C SYSTEM 3 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,046 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT. (SEE RESPONSE
 ABOVE #7).
  
 9) ELECTRICAL PLAN E-2 IS SHOWING A GAS INSTA-HOT WATER
 HEATER IN THE GARAGE OF THE GUEST HOUSE, THIS MAY BE A
 CONFINED SPACE. PLEASE SUBMIT COMBUSTION AIR
 CALCULATIONS, SEE 2004 FBC/R G2407.5. (THE GAS
 APPLIANCE MAY BE INSTALLED UNDER A SEPARATE PERMIT BUT
 THE SPACE THE GAS APPLIANCE IS BEING INSTALLED IN IS
 PART OF THIS PERMIT, PLEASE COMPLY).
  
 10) PLEASE SUBMIT MANUFACTURER'S SPECIFICATION'S FOR
 THE GAS INSTA-HOT WATER HEATER AND GAS WATER HEATER
 BEING INSTALLED IN MAIN HOUSE, PER 2004 FBC/R G2407.1.
 (SEE RESPONSE ABOVE #9).
  
 11) NEW NOTE: PLANS SHOW A GAS WATER HEATER BEING
 INSTALLED IN A CLOSET OF THE MAIN HOUSE FIRST FLOOR.
 THIS MAY BE A CONFINED SPACE, PLEASE SUBMIT COMBUSTION
 AIR CALCULATIONS, PER 2004 FBC/R G2407.5.
  
 12) NOTICE: SEE ATTACHED NOTICE FS 553.80 (2) (B)
 REGARDING FOUR TIMES THE FEE.
  
 *** 2004 FBC/R G2407.1 (304.1) GENERAL.
 AIR FOR COMBUSTION, VENTILATION AND DILUTION OF FLUE
 GASES FOR GAS UTILIZATION EQUIPMENT INSTALLED IN
 BUILDINGS SHALL BE PROVIDED BY APPLICATION OF ONE OF
 THE METHODS PRESCRIBED IN SECTIONS G2407.5 THROUGH
 G2407.9 . WHERE THE REQUIREMENTS OF SECTION G2407.5 ARE
 NOT MET, OUTDOOR AIR SHALL BE INTRODUCED IN ACCORDANCE
 WITH ONE OF THE METHODS PRESCRIBED IN SECTIONS G2407.6
 THROUGH G2407.9 . DIRECT-VENT APPLIANCES, GAS
 APPLIANCES OF OTHER THAN NATURAL DRAFT DESIGN AND
 VENTED GAS APPLIANCES OTHER THAN CATEGORY I SHALL BE
 PROVIDED WITH COMBUSTION, VENTILATION AND DILUTION AIR
 IN ACCORDANCE WITH THE EQUIPMENT MANUFACTURER?S
 INSTRUCTIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-07 Cont ID  
Sent By btrobaug Date 2008-02-07 Time 09:36 Rev Time 1.15
Received By tgordon Date 2008-02-07 Time 09:36 Sent To P
Notes
2008-02-07 10:02:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MAIN HOUSE AND THE GUEST HOUSE CAN NOT BE ON THE
 SAME ENERGY CALCULATION. PLEASE SUBMIT SEPARATE ENERGY
 CALCULATIONS FOR EACH BUILDING, SEE 2004 FBC
 13-101.2.5.1.
  
 2) PLEASE HAVE THE REVISED ENERGY CALCULATIONS SIGNED
 BY OWNER/AGENT ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 8B DOES NOT SHOW THE RAISED
 WOOD FLOOR OR INSULATION, SEE 2004 FBC 13-605.2.A.1.1
 AND 13-605.1.C.2. PLEASE CORRECT ALSO THE PLANS IF
 NEEDED.
  
 4) SHOW AN A/C EQUIPMENT SCHEDULE WITH ALL THE
 PERTINENT INFORMATION ON THE MECHANICAL PLAN, SEE 2004
 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW ALL THE BATHROOM EXHAUST FANS ON THE MECHANICAL
 PLAN AS THEY ARE ON THE ELECTRICAL PLAN, SEE 2004 FBC/R
 R303.3 EXCEPT.
  
 6) SHOW THE LOCATION OF THE GUEST HOUSE A/C CONDENSER
 UNIT ON THE MECHANICAL AND ELECTRICAL PLANS, SEE 2004
 FBC/R M1307.
  
 7) A/C SYSTEM 2 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,601 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 8) A/C SYSTEM 3 COOLING LOAD CALCULATIONS ARE CALLING
 FOR 23,046 TOTAL COOLING BTU'S. A 3 TON A/C SYSTEM AT
 34,200 TOTAL COOLING BTU'S WOULD BE TO LARGE AS YOU CAN
 ONLY GO 15% OVER THE COOLING LOAD CALCULATION, SEE 2004
 FBC 13-607.1.ABC.1.1. PLEASE CORRECT.
  
 9) ELECTRICAL PLAN E-2 IS SHOWING A GAS INSTA-HOT WATER
 HEATER IN THE GARAGE OF THE GUEST HOUSE, THIS MAY BE A
 CONFINED SPACE. PLEASE SUBMIT COMBUSTION AIR
 CALCULATIONS, SEE 2004 FBC/R G2407.5.
  
 10) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 GAS INSTA-HOT WATER HEATER AND ALL OTHER GAS APPLIANCES
 BEING INSTALLED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-02-26 Cont ID  
Sent By kstevens Date 2009-02-26 Time 15:41 Rev Time 0.00
Received By kstevens Date 2009-02-26 Time 15:41 Sent To M
Notes
2009-02-26 15:42:00PASSED PROVISO -- TABLE 909.3.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-12-04 Cont ID  
Sent By kstevens Date 2008-12-04 Time 10:23 Rev Time 0.00
Received By kstevens Date 2008-12-04 Time 10:23 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-05 Cont ID  
Sent By mperson Date 2008-08-05 Time 10:46 Rev Time 0.00
Received By mperson Date 2008-08-05 Time 10:46 Sent To B
Notes
2008-08-05 11:13:54PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
 1. "OK" COMMENT ADDRESSED.
  
 2. THE GAS WATER HEATER IN THE GUEST HOUSE GARAGE,
 SHOW HOW IT WILL BE VENTED TO THE OUTSIDE. PROVIDE
 MANUFACTURER'S SPECIFICATIONS.
  
 **RESPONSE NOTED, HOWEVER COMMENT HAS NOT BEEN
 ADDRESSED. PLEASE KNOW THAT THE GAS APPLIANCE AND
 PIPING MAY BE INSTALLED UNDER A SEPERATE PERMIT,
 HOWEVER THE SPACE THE GAS APPLIANCE IS BEING INSTALLED
 IN IS PART OF THIS PERMIT AND THE COMBUSTION AIR ISSUE
 FOR THIS APPLIANCE NEEDS TO BE RESOLVED AND COMPLY. PER
 FBC-2004 FUEL GAS SECTION 304 COMBUSTION, VENTILATION
 AND DILLUTION AIR.
  
 3. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 4. SHEET A1.0 FIRST FLOOR PLAN INDICATES A GAS WATER
 HEATER IN A CLOSET OF THE MAIN HOUSE. THIS APPEARS TO
 BE A CONFINED SPACE, PLEASE SUBMIT COMBUSTION AIR
 CALCULATION AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE WATER HEATER. PER FBC-2004 FUEL GAS SECTION 304
 COMBUSTION, VENTILATION AND DILLUTION AIR.
  
 5. NOTICE: SEE ATTACHED NOTICE FS 553.80(2)(B)
 REGARDING FOUR (4) TIMES THE FEE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-08 Cont ID  
Sent By jleech Date 2008-02-08 Time 08:09 Rev Time 0.00
Received By jleech Date 2008-02-08 Time 07:09 Sent To B
Notes
2008-02-08 08:34:40DENIED;
 1. ADDRESS OF JOB ISREQUIRED ON ALLPAGES OF
 PLANS.FBC BUILDING CHAPTER 1 SECTION 106.1.1.
 2. THE GAS WATER HEATER IN THE GUEST HOUSE GARAGE, SHOW
 HOW IT WILL BE VENTED TO THE OUTSIDE. PROVIDE
 MANUFACTURE'S SPECIFICATIONS.
 3. THE RISER DIAGRAM DOES NOT MATCH THE FLOOR PLANS.
 A) BOTH 2ND FLOOR BATHROOMS HAVE 2-LAVATORYS
 B) MASTER BATH IS MISSING A TUB.
 C) BACK BATHROOM IS MISSING THE 2 LAVS. AND
 HAS AN EXTRA SHOWER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-21 Cont ID  
Sent By jroach Date 2008-11-21 Time 11:04 Rev Time 0.00
Received By jroach Date 2008-11-21 Time 11:04 Sent To L
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 11:22 Rev Time 0.00
Received By mcruz Date 2008-08-03 Time 11:21 Sent To E
Notes
2008-08-03 11:22:28***ZONING FAILED***
  
 **REPEAT COMMENTS**
  
 1.INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 2.PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDRS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR
 [email protected]
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-14 Cont ID  
Sent By choops Date 2008-02-14 Time 14:17 Rev Time 0.00
Received By choops Date 2008-02-14 Time 14:17 Sent To  
Notes
2008-02-14 15:26:07***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM ALL NEW
 CONSTRUCTION TO ALL PROPERTY LINES.ALL NEW
 CONSTRUCTION SHALL COMPLY WITH CURRENT REGULATIONS.
 PURSUANT TO SECTION 94-74 OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS):
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 A.FRONT: 25 FEET;
 B.CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
 C.REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER
 IS LESS;
 D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 THE SECOND FLOOR ADDITION AT THE REAR OF THE STRUCTURE
 DOES NOT MEET THE MINIMUM REQUIRED SETBACK OF 5' TO THE
 PROPERTY LINE.PLEASE REVISE.
  
 2)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED OR
 RELOCATED A/C EQUIPMENT (IF ANY) TO ALL PROPERTY LINES.
 AS PER SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 3)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
 4)INDICATE SEPARATION DISTANCE FROM EXISTING
 PRINCIPAL STRUCTURE TO THE PROPOSED GARAGE ADDITION.
 NOTE: MUST MAINTAIN A MINIMUM OF 6' SEPARATION.
  
 5)INDICATE HEIGHT DIMENSIONS FROM GRADE TO THE
 MIDPOINT OF THE UPPERMOST ROOF'S PITCH.PURSUANT TO
 SECTION 94-74 OF THE ZLDRS:MAXIMUM HEIGHT FOR
 PRINCIPAL BUILDING = 30'.ALSO INDICATE HEIGHT
 DIMENSION OF THE CHIMNEY FROM GRADE TO THE UPPERMOST
 POINT OF THE CHIMNEY.CLARIFY IF CHIMNEY IS PROPOSED
 OR EXISTING, IF PROPOSED, THE CHIMNEY SHALL NOT EXCEED
 33' IN HEIGHT MEASURED FROM GRADE.
  
 6)INDICATE ALL OVERHANG DIMENSIONS, AND BALCONY
 DIMENSIONS FROM THE WALL TO THE OUTERMOST POINT.
 PURSUANT TO SECTION 94-305 OF THE ZLDRS:STRUCTURAL
 OVERHANGS, INCLUDING BUT NOT LIMITED TO BALCONIES,
 CORNICES, GUTTERS, EAVES, AND ROOF OVERHANG PROJECTIONS
 SHALL NOT EXTEND FARTHER THAN THREE FEET INTO ANY
 SETBACK.
  
  
 NOTE:ACCESSORY STRUCTURE SHALL NOT EXCEED 75 PERCENT
 OF THE GROSS FLOOR AREA OF THE PRIMARY STRUCTURE WITH A
 MAXIMUM FLOOR AREA OF 1,000 SQUARE FEET.
  
 NOTE:AS THERE ARE DIMENSIONALLY NONCONFORMING
 STRUCTURES ON THE LOT WITH RESPECT TO THE SETBACK
 REQUIREMENTS, NO NEW NONCONFORMITY SHALL BE CREATED AND
 NO EXISTING NONCONFORMITY SHALL BE INCREASED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720