Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By shill Date 2008-02-04 Time 14:03 Rev Time 0.00
Received By shill Date 2008-02-04 Time 14:03 Sent To  
Notes
2008-02-04 14:16:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE MAKE SECONDARY WATER BARRIER CLEAR
 FS553.844(5)(A).I WAS UNABLE TO RESOLVE THIS ISSUE
 WITH THE CONTRACTOR OVER THE TELEPHONE.TO AVOID FIELD
 ISSUES, PLEASE PROVIDE THIS INFORMATION IN WRITING;
 FLAT DECK AND PITCHED ROOF.
  
 2.A PRODUCT APPROVAL WAS INCLUDED FOR POLYGLASS.IF
 USING THIS AS AN UNDERLAYMENT, PROVIDE ASSOCIATED
 DOCUMENTATION (EVALUATION REPORT AND INSTALLATION
 INSTRUCTIONS) ALONG WITH THE FLORIDA STATE PRODUCT
 APPROVAL COVER SHEET.ALSO NOTE METHOD OF INSTALLATION
 (NOTE THAT DIRECT DECK/TILE DOES NOT MEET SECONDARY
 WATER BARRIER REQUIREMENTS).
  