Plan Review Details - Permit 08020025
Plan Review Stops For Permit 08020025
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-07 Cont ID  
Sent By shill Date 2008-02-07 Time 14:28 Rev Time 0.00
Received By shill Date 2008-02-07 Time 14:28 Sent To  
Notes
2008-02-07 14:36:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE TWO COMPLETE, IDENTICAL COLLATED SETS OF
 PERMIT DOCUMENTS.YOU'VE DRAWN THE GENERATOR ON AN
 "EXISTING CONCRETE PATIO" BUT THERE IS ONLY ONE COPY OF
 THIS DOCUMENT.PLEASE CHECK ALL SHEETS AND COLLATE
 INTO TWO IDENTICAL SETS.
  
 2. .)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 3.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 4.)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB
 SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER.
  
 5.)THE VALUE IS TOO LOW.PROVIDE A REASONABLE VALUE
 OR AN ESTIMATED VALUE WILL BE DONE FOR YOU USING
 MARSHALL & SWIFT.
  
 6.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-02-01 Cont ID  
Sent By btrobaug Date 2008-02-01 Time 16:56 Rev Time 0.00
Received By btrobaug Date 2008-02-01 Time 16:56 Sent To Z
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-02-06 Cont ID  
Sent By mperson Date 2008-02-06 Time 09:52 Rev Time 0.00
Received By mperson Date 2008-02-06 Time 09:52 Sent To B
Notes
2008-02-06 10:07:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 ON THE GAS ISOMETRIC. PER FBC FUEL GAS SECTION *401.1
 SCOPE.
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. *402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **PLEASE SUBMIT TWO COPIES OF MANUFACTURER
 SPECIFICATION SHEETS FOR THE GENERATOR THAT CLEARLY
 INDICATE THE MAKE, MODEL NUMBER, AND BTU LOAD CAPACITY
 OF THE PROPOSED GENERATOR.
  
 4. THE VALUE OF $1500,00 FOR THE PROPOSED GENERATOR
 AND RELATED WORK IS TO LOW.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.**SIGNATURE
 REQUIRED ON GAS ISOMETRIC RISER DIAGRAM.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-07 Cont ID  
Sent By adarroug Date 2008-02-07 Time 11:36 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 16:56 Sent To  
Notes
2008-02-01 16:57:32 
  
  
 TO E./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By tgordon Date 2008-02-04 Time 16:35 Rev Time 0.25
Received By tgordon Date 2008-02-04 Time 16:35 Sent To G
Notes
2008-02-04 16:36:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By choops Date 2008-02-04 Time 11:43 Rev Time 0.00
Received By choops Date 2008-02-04 Time 11:43 Sent To M
Notes
2008-02-04 11:44:33***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED GENERATOR WITH
 SETBACK DIMENSIONS TO ALL PROPERTY LINES.
  
 NOTE:AS PER SECTION 94-305(B)(4) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "M" - GEN. BOX