Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-04 Cont ID  
Sent By jgomez Date 2008-02-04 Time 13:44 Rev Time 0.00
Received By jgomez Date 2008-02-04 Time 13:44 Sent To PC
Notes
2008-02-04 13:57:48RESIDENTIAL ROOFING, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVALORMANUFACTURER
 SPECIFICATIONS FOR TAMKO TAPE TO BE USED AS SECONDARY
 WATER BARRIER REQUIRED BY THE HURRICANE MITIGATION
 RETROFIT RULE 9B-3.0475.
  
 2- CLEARLY IDENTIFY SPECIFIC FLAT ROOF ASSEMBLYWITH
 INSULATION TO BE INSTALLED AS REQUIRED BY CITY POLICY
 FOR ROOFING PERMITS TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES. SEE ATTACHED COPY.
  
 3- IF SELECTED ASSEMBLY HASSEVERAL BASE SHEET
 FASTENER OPTIONS, THEN CLEARLY IDENTIFY FASTENING
 OPTION AS REQUIRED BY CITY POLICYFOR ROOFING TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES.
  
 4- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THENPROVIDE THE RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT THE PERIMETER AND CORNER AREAS.
 NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT MAY NO BE GOOD TO BE USED FOR
 THIS AREA, SINCE NAIL ENHANCING IS NOT ALLOWED WITH
 GENERAL LIMITATION #9.
  
 5- SPECIFY MEAN ROOF HEIGHT,ROOF PITCHAND PITCHED
 ROOF AREA AND FLAT ROOF AREAAS REQUIRED BY CITY
 POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  