Plan Review Details - Permit 08020013
Plan Review Stops For Permit 08020013
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-13 Cont ID  
Sent By shill Date 2008-03-13 Time 16:08 Rev Time 0.00
Received By shill Date 2008-03-13 Time 16:08 Sent To  
Notes
2008-03-13 16:08:56REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-03-11 Cont ID  
Sent By shill Date 2008-03-11 Time 14:09 Rev Time 0.00
Received By shill Date 2008-03-11 Time 14:09 Sent To  
Notes
2008-03-11 14:12:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.IT APPEARS THAT THE SCOPE OF THIS REVISION IS TO
 INCLUDE OPENINGS 8 AND 9, WHICH WERE REMOVED DUE TO THE
 SUBSTRATE NOT BEING INCLUDED IN THE PRODUCT APPROVAL.
 PLEASE REVISE THE FLOOR PLAN AND INSTALLATION SCHEDULE,
 AS THESE TWO OPENINGS WERE CROSSED OFF WHEN THE PERMIT
 WAS ISSUED.I ATTEMPTED TO DO THIS FOR YOU (SEE
 ATTACHED) BUT IT DOES NOT PROPERLY DOCUMENT THE WORK TO
 BE DONE FOR RECORD KEEPING PURPOSES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-22 Cont ID  
Sent By shill Date 2008-02-22 Time 09:16 Rev Time 0.00
Received By shill Date 2008-02-22 Time 09:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-19 Cont ID  
Sent By shill Date 2008-02-19 Time 10:47 Rev Time 0.00
Received By shill Date 2008-02-19 Time 10:47 Sent To  
Notes
2008-02-19 10:55:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE REMOVE DOCUMENTS WHICH ARE NOT A PART OF THE
 PRODUCT APPROVAL.THIS REVIEW HAS BEEN DONE BASED ON
 THE MIAMIDADE NOA PROVIDED AS I CANNOT DETERMINE WHERE
 THE CUT SHEETS CAME FROM.WHEN I GO TO THE FLORIDA
 PRODUCT APPROVAL SITE, WWW.FLORIDABUILDING.ORG, IT
 APPEARS THAT MIAMIDADE NOAS WERE SUBMITTED.THEREFORE,
 COMPLIANCE WITH THIS PRODUCT APPROVAL IS REQUIRED
 UNLESS OTHER PAPERWORK IS SUBMITTED.AS DISCUSSED, THE
 INSTALLATION SCHEDULE SPECIFIES 2" GLASS SEPARATION; 2
 7/8 REQUIRED (SHEET SSHB C 050B).
  
 2.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.THE ENGINEERING SUBMITTED ADDRESSED ONLY
 ANCHORING INTO THE EXISTING GLASS DOOR FRAME.NOTE
 THAT GLASS SEPARATION ALSO NEEDS TO BE ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-05 Cont ID  
Sent By shill Date 2008-02-05 Time 11:43 Rev Time 0.00
Received By shill Date 2008-02-05 Time 11:43 Sent To  
Notes
2008-02-05 11:43:57****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
  
 _XX_4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 _XZ_6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 ____8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 15:16 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 15:16 Sent To B
Notes
2008-03-13 15:17:04TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 11:25 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 11:25 Sent To B
Notes
2008-03-06 11:25:46TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-15 Cont ID  
Sent By adarroug Date 2008-02-15 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-02-15 Time 11:18 Sent To B
Notes
2008-02-15 11:18:32TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-05 Cont ID  
Sent By shill Date 2008-02-05 Time 11:44 Rev Time 0.00
Received By shill Date 2008-02-01 Time 14:28 Sent To  
Notes
2008-02-01 14:28:48TO "MISC" BOX#1