Plan Review Details - Permit 08010762
Plan Review Stops For Permit 08010762
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-28 Cont ID  
Sent By jgomez Date 2008-02-28 Time 10:42 Rev Time 0.00
Received By jgomez Date 2008-02-28 Time 10:42 Sent To PC
Notes
2008-02-28 10:43:02DONNA FAXED NAIL ENHANCING LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-27 Cont ID  
Sent By jgomez Date 2008-02-27 Time 13:36 Rev Time 0.00
Received By jgomez Date 2008-02-27 Time 13:36 Sent To PC
Notes
2008-02-27 14:37:52COMMERCIAL ROOFING BUILDING REVIEW SECOND CHECKLIST:
  
 1-FLAT ROOF SYSTEM NOA05-0830.10 SUBMITTED AND
 ENGINEER'S RAS 117 CALCULATIONS ARE FOR TWO DIFFERENT
 PRODUCTS.NOA 05-0830.10 IS A PRODUCT FROM FIRESTONE
 BUILDING PRODUCTS COMPANY, WHILE NOA 06-0410.06
 REFERENCED BY THE ENGINEER IS A PRODUCT FROM POLYGLASS
 USA.NEED INFORMATION THAT MATCHES TO EACH OTHER.
  
 2-ONLY TWO SETS OF ENGINEER CALCULATIONS WERE
 PROVIDED.THREE SETS OF EVERYTHING IS REQUIRED IN THIS
 JOB BECAUSE THERE IS A THRESHOLD INSPECTOR IN THIS
 JOB.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By jgomez Date 2008-01-31 Time 15:42 Rev Time 0.00
Received By jgomez Date 2008-01-31 Time 15:42 Sent To PC
Notes
2008-01-31 16:12:43BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-THIS IS A SEPARATE PERMIT AS AGREED ON WITH
 CONTRACTOR ON PROVISO DATED 04/12/07.SEE ATTACHED
 COPY. OWES $85.14FOR PERMIT FEE BALANCE.
  
 2- SELECTED ASSEMBLY ON PAGE 31 OF NOA 05-0830.10
 SUBMITTED CAN'T BE USED IN THIS AREA BECAUSE IT DOESN'T
 MEET THE DESIGN PRESSURES FOR PERIMETER AND CORNER
 AREAS AND ASSEMBLY IS LIMITED BY GENERAL LIMITATION #9,
 WHICH DOESN'T ALLOW NAIL ENHANCING.NEED TO SELECT
 ASSEMBLYTHAT IS LIMITED BY GENERAL LIMITATION #7,
 WHICH ALLOWS NAIL ENHANCING.
  
 3- PROVIDE THE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 4- THERE IS A DESIGNER OF RECORD ON THIS PROJECT.
 DESIGNER OF RECORD NEEDS TO REVIEW AND APPROVE IN
 WRITING(NOT SIGNING AND SEALING)ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 14:47 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 14:47 Sent To B
Notes
2008-02-26 14:47:59TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By jgomez Date 2008-01-31 Time 16:12 Rev Time 0.00
Received By jgomez Date 2008-01-31 Time 12:05 Sent To  
Notes
2008-01-31 12:05:47TO "JGOMEZ" DESK/NEW ROOF