2008-02-05 16:54:09 | 2004 FBC W/2007 REVISIONS |
| LEVEL 2 ALTERATION |
| |
| DENIED BY BUILDING |
| |
| 1) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE |
| FBC EXISTING BUILDING CODE CHAPTER 3. |
| |
| 2) THE CODE THAT APPLIES TO THIS PROJECT IS THE 2004 |
| FBC W/2007 REVISIONS. REVISE ON PLAN. |
| |
| 3) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE |
| WINDOW OPENINGS ON THE PLANS. FBC 106.1.2* CITY |
| AMENDMENT |
| |
| 4) THE WIND FBC 106.3* CITY AMENDMENTS PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 5) THE WINDOW OPENING SIZES SPECIFIED IN NOTE #8 UNDER |
| SCOPE OF WORK DO NOT CORRESPOND WITH THE SIZES |
| SPECIFIED ON THE STORM PANEL INSTALLATION SCHEDULE. |
| PLEASE CORRECT. FBC 106.1.1* CITY AMENDMENT |
| |
| 6) SUBMIT TWO COPIES OF PAGES 1 AND 2 OF THE WINDOW |
| INSTALLATION SCHEDULE. ONLY ONE PAGE WAS ATTACHED TO |
| EACH PLAN. FBC 106.1* CITY AMENDMENT |
| |
| 7) THE STORM PANEL INSTALLATION SCHEDULE IS NOT FILLED |
| OUT CORRECTLY. THE SHUTTER SPAN IS THE LENGTH OF THE |
| PANEL. THE CONNECTION TYPES ARE LISTED IN THE NOA (C1, |
| C2, C3, C4 AND C5). TITEN TAPCONS ARE NOT SPECIFIED IN |
| THE PRODUCT APPROVAL. SPECIFY THE ANCHOR TYPE FROM THE |
| ONES LISTED IN THE NOA. SPECIFY IF THE PANELS WILL BE |
| DIRECT MOUNT OR TRACK MOUNT. SPECIFY THE TRACK TYPE FOR |
| THE BOTTOM AND TOP. THE MINIMUM GLASS SEPARATION |
| ALLOWED BY THE NOA IS 3". WINDOW NUMBERS 7 AND 8 ARE |
| INDICATED WITH 2" SEPARATION ON THE INSTALLATION |
| SCHEDULE. SEE SHEET 5 OF THE NOA FOR THE TABLES USED TO |
| DETERMINE ANCHOR SPACING WHICH IS BASED ON WALL TYPE, |
| ANCHOR TYPE, EDGE DISTANCE, SPAN, PRESSURE AND |
| CONNECTION TYPE. |
| |
| 8) THE ANCHORS SPECIFIED FOR ATTACHING THE STORM PANELS |
| TO THE INSULATED METAL PANELS AT THE FAMILY ROOM ARE |
| NOT SPECIFIED IN THE NOA. IN ORDER FOR THE PANELS TO BE |
| INSTALLED IN THIS MANNER, A SIGNED AND SEALED RATIONAL |
| ANALYSIS FROM A FLORIDA LICENSED ENGINEER IS REQUIRED. |
| NOTE: IF THIS METAL STRUCTURE IS NOT DESIGNED TO |
| WITHSTAND LARGE MISSILEIMPACT AND 140 MPH WINDSPEED, |
| THE GLAZED OPENINGS BETWEEN THE HOUSE AND THIS ADDITION |
| MAY BE EXPOSED TO WIND BORNE DEBRIS. |
| |