Plan Review Details - Permit 08010743
Plan Review Stops For Permit 08010743
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-12 Cont ID  
Sent By jgomez Date 2008-02-12 Time 16:13 Rev Time 0.00
Received By jgomez Date 2008-02-12 Time 16:13 Sent To PC
Notes
2008-02-12 16:37:08BUILDING REVIEW APPROVED WITH PROVISO:
 1- NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA OR
 ROOF SECTION OF ANY EXISTING BUILDING OR STRUCTURE
 SHALL BE REPAIRED, REPLACED OR RECOVERED IN ANY 12
 MONTH PERIOD UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF
 SECTION CONFORMS TO THE REQUIREMENTS OF THIS CODE. SEC.
 511.1.2 2004 FLORIDA EXISTINGBUILDING CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By jgomez Date 2008-01-31 Time 10:49 Rev Time 0.00
Received By jgomez Date 2008-01-31 Time 10:42 Sent To PC
Notes
2008-01-31 11:14:44BUILDING REVIEW FIRST CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-ROOF TILE NOA 02-0916.11 SUBMITTED EXPIRED ON
 12/16/07. NEED TO PROVIDE 2 COPIES OF CURRENT NOA. DCA
 RULE 9B-72.
  
 2- UNDERLAYMENT NOA 06-1101.09 SUBMITTED REQUIRES ROOF
 COVERINGPRODUCT APPROVAL TO LIST THE USE OF FAST 90
 UNDERLAYMENT.SEE GENERAL LIMITATION #11 ON PAGE 3 OF
 5.PROVIDE ROOF TILE NOA THAT LISTS THE USE OF FAST 90
 UNDERLAYMENT. OTHERWISE, PROVIDE PROVIDE COMPLETE
 DOCUMENTATION TO DEMONSTRATE COMPATIBILITY BETWEEN ROOF
 TILE AND PROPOSED UNDERLAYMENT. SEC. 106.1.2 CITY
 AMENDMENTS TOFBC 2004 TO VERIFY COMPLIANCE WITHSEC.
 1609 FBC 2004.
  
 3- CLEARLY SPECIFY ROOF TILE FASTENING METHODAS
 REQUIRED BY CITY POLICY FOR ROOFING PERMITS(SEE
 ATTACHED COPY)TO VERIFY COMPLIANCE WITH PRODUCT
 APPROVALATTACHMENT RESISTANCE AND SEC. 1609FBC
 2004.
 IF USING NAILS OR SCREWS,THEN CLEARLY MARK PRODUCT
 APPROVAL SUBMITTED TO VERIFY NUMBER AND SIZEUSED. IF
 USING POLYFOAM, THEN PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72. SEE TILE PRODUCT APPROVAL
 FOR LISTED TYPE OF FOAM.
  
 4- PERMIT APPLICATION CALLS FOR REPAIRS ON BUILDING #12
 ONLY.SITE PLAN SUBMITTED CALLS FOR REPAIRS ON
 BUILDINGS5, 7 AND 12.. CLARIFY AS REQUIRED AND UPDATE
 VALUATION AS REQUIRED.CLEARLY IDENTIFY APPROXIMATE
 AREA OF REPAIR PER BUILDING.
 ***NOTE: NOTICE OF COMMENCEMENT MAY BE REQUIRED BASED
 ON THE TOTALPROPOSED SCOPE OF WORK .
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 14:09 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 14:09 Sent To B
Notes
2008-02-12 14:10:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By jgomez Date 2008-01-31 Time 11:14 Rev Time 0.00
Received By jgomez Date 2008-01-31 Time 09:10 Sent To  
Notes
2008-01-31 09:11:21TO "JGOMEZ" DESK/PER "LMARTINEZ"(COMM ROOF)