Plan Review Details - Permit 08010729
Plan Review Stops For Permit 08010729
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-07-30 Cont ID  
Sent By mperson Date 2008-07-30 Time 15:35 Rev Time 0.00
Received By mperson Date 2008-07-30 Time 15:35 Sent To PC
Notes
2008-07-30 15:36:46REVISION: "OK" ADDED GAS PIPING TO FIRE PIT & VALUE
 INCREASED.
  
 ****************PROVISO****************
 A} IF DRYER ROOM IS A CONFINED SPACE, OPENINGS
 REQUIRED PER SECTION 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED. MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 B} IF WATER HEATER ROOM IS A CONFINED SPACE, OPENINGS
 REQUIRED PER SECTION 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED. MINIMUM 3,850 CUBIC FEET REQUIRED.
  
 C} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2008-01-31 Cont ID  
Sent By mperson Date 2008-01-31 Time 14:59 Rev Time 0.00
Received By mperson Date 2008-01-31 Time 14:59 Sent To PC
Notes
2008-01-31 15:01:55****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,850 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 09:31 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 09:31 Sent To G
Notes
2008-07-30 09:31:50TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By mperson Date 2008-01-31 Time 15:02 Rev Time 0.00
Received By mperson Date 2008-01-30 Time 12:45 Sent To  
Notes
2008-01-30 12:45:33 
  
 TO MIKE'S DESK./WRT.