2008-02-04 14:47:16 | 2004 FBC W/2007 REVISIONS |
| ADDITION |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR |
| WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL |
| HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING |
| WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT |
| EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN |
| ADJACENT PROJECTION OR WALL. PROJECTIONS EXTENDING INTO |
| THE 6-FOOT (1829 MM) SEPARATION DISTANCE SHALL HAVE NOT |
| LESS THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION ON THE |
| UNDERSIDE. THE ABOVE PROVISIONS SHALL NOT APPLY TO |
| WALLS WHICH ARE PERPENDICULAR TO A LINE EXTENDING FROM |
| THE POINT FROM WHICH THE SEPARATION DISTANCE HAS BEEN |
| MEASURED RUNNING AND PARALLEL TO THE PROPERTY LINE. THE |
| DISTANCE TO THE PROPERTY LINE AT THE SIDE AND REAR IS 5 |
| FEET. SHOW DISTANCE TO STRUCTURES ON ADJACENT |
| PROPERTIES AT THESE LOCATIONS. |
| |
| 4) SHOW COMPLIANCE WITH R302.2 OPENINGS. |
| OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF |
| A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM |
| AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET |
| (1828 MM). THIS DISTANCE SHALL BE MEASURED |
| PERPENDICULAR TO THE LINE USED TO DETERMINE THE |
| SEPARATION DISTANCE. |
| |
| 5) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. THE |
| GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS |
| ATTIC AREA BY NOT LESS THAN ? -INCH (12.7 MM) GYPSUM |
| BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH |
| HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE |
| ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH (15.9 MM) TYPE |
| X GYPSUM BOARD OR EQUIVALENT. WHERE THE SEPARATION IS A |
| FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE |
| SEPARATION SHALL ALSO BE PROTECTED BY NOT LESS THAN |
| 1/2-INCH (12.7 MM) GYPSUM BOARD OR EQUIVALENT. |
| |
| 6) SPECIFY HOW TERMITE PROTECTION WILL BE PROVIDED. SEE |
| FBC R320.1. |
| |
| 7) SHOW COMPLIANCE WITH R311.5.3.2 TREAD DEPTH. WINDER |
| TREADS SHALL HAVE A MINIMUM TREAD DEPTH OF 10 INCHES |
| (254 MM) MEASURED AS ABOVE AT A POINT 12 INCHES (305) |
| MM FROM THE SIDE WHERE THE TREADS ARE NARROWER.WINDER |
| TREADS SHALL HAVE A MINIMUM TREAD DEPTH OF 6 INCHES |
| (152 MM) AT ANY POINT.WITHIN ANY FLIGHT OF STAIRS, THE |
| GREATEST WINDER TREAD DEPTH AT THE 12 INCH (305 MM) |
| WALK LINE SHALL NOT EXCEED THE SMALLEST BY MORE THAN 3 |
| / 8 INCH (9.5 MM). |
| |
| 8) SPECIFY THE REQUIRED FOOTING SIZE FOR THE EXISTING |
| FOOTINGS, IN ORDER TO ADEQUATELY SUPPORT THE SECOND |
| FLOOR ADDITION. FBC 106.1.2* CITY AMENDMENTS |
| |
| 9) DURING THE COURSE OF THE PROJECT THE CONTRACTOR WILL |
| BE REQUIRED TO PERFORM INVESTIGATIVE WORK TO DETERMINE |
| THAT THE EXISTING FOOTINGS AND TIE BEAMS ARE ADEQUATE. |
| FBC 106.1.2* CITY AMENDMENTS |
| |
| 10) SPECIFY THE REQUIRED FOOTER SIZE FOR THE POINT |
| LOADING THAT IS LOCATED WHERE THE TW0 4 X 4 COLUMNS |
| SUPPORTING THE WALL AND ROOF LOADS ABOVE ARE LOCATED. |
| FBC 106.1.2* CITY AMENDMENTS |
| |
| 11)SPECIFY THE ROOF PITCH FOR THE CLAY TILE PORCH |
| ROOF ABOVE THE GARAGE DOORS. FBC 106.1.1* CITY |
| AMENDMENTS |
| |
| 12)PROVIDE ADDITIONAL STRUCTURAL INFORMATION FOR THE |
| SLOPED PORCH ROOF ABOVE THE GARAGE DOORS. SPECIFY THE |
| ATTACHMENTS OF THE ROOF TO THE STRUCTURE. SPECIFY ALL |
| OF THE FASTENERS AND CONNECTORS. SPECIFY THE FRAMING |
| MEMBER SIZES AND SPACING.FBC 106.1.1* CITY |
| AMENDMENTS |
| |
| |
| 13) SPECIFY THE HANGERS AND CONNECTORS FOR THE WB-1 |
| BEAMS AT THE TERRACE ROOF. FBC 106.1.1* CITY |
| AMENDMENTS |
| |
| 14) SPECIFY THE FASTENING REQUIREMENTS FOR THE ROOF |
| SHEATHING AS REQUIRED BY FBC R803.2.3.1. |
| ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH |
| SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC |
| RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL |
| BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT |
| 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT |
| INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS |
| SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 |
| MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH |
| FIGURE R803.2.3.1. |
| |
| 15) PROVIDE A DETAIL OF THE FRAMING AT THE WINDOW |
| OPENINGS. SPECIFY THE HEADER SIZE, CONNECTORS, ETC. FBC |
| 106.1.1* CITY AMENDMENTS |
| |
| 16) SHOW COMPLIANCE WITH R806.1. VENTILATING OPENINGS |
| SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE MESH, |
| WIT H 1 / 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) |
| MAXIMUM OPENINGS. |
| |
| 17)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. |
| THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 18) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED |
| IN THE POLYGLASS MODIFIED BITUMEN ROOFING SYSTEM |
| PRODUCT APPROVAL WILL BE INSTALLED. SPECIFY THE |
| FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED. |
| SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| ENHANCED FASTENING FROM A FLORIDA LICENSED ARCHITECT, |
| ENGINEER OR REGISTERED ROOF CONSULTANT AS REQUIRED BY |
| LIMITATION #7 OF THE PRODUCT APPROVAL. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |