Plan Review Details - Permit 08010629
Plan Review Stops For Permit 08010629
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-29 Cont ID  
Sent By shill Date 2008-04-29 Time 13:46 Rev Time 0.00
Received By shill Date 2008-04-29 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-02 Cont ID  
Sent By shill Date 2008-04-02 Time 13:18 Rev Time 0.00
Received By shill Date 2008-04-02 Time 13:18 Sent To  
Notes
2008-04-02 13:18:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1-4, ADDRESSED OR INFORMATIONAL.
  
 3. PLANS DO NOT PROVIDE THE VERTICAL, HORIZONTAL OR
 GRAVITY LOADS THE TRUSSES ARE GOING TO BE SUBJECTED TO.
 PLEASE PROVIDE THESE VALUES 1609.1.3 ANCHORAGE AGAINST
 OVERTURNING,UPLIFT AND SLIDING.16091.1.1 MAIN
 WINDFORCE RESISTING SYSTEMS.
  
 ARCHITECT?S RESPONSE THAT THIS WILL BE PROVIDED BY THE
 TRUSS ENGINEER IS ACKNOWLEDGED.PLEASE EITHER PROVIDE
 THE ROOF FRAMING DESIGN CRITERIA PREPARED BY THE
 DELEGATED ENGINEER OR SPECIFIED DESIGN CRITERIA,
 FBC*106.3.5.1.1(8).
  
 4-10. ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By jwitmer Date 2008-02-11 Time 21:12 Rev Time 1.33
Received By jwitmer Date 2008-02-11 Time 21:12 Sent To  
Notes
2008-02-11 21:13:406316 S DIXIE HWY
 LA SIRENA RESTAURANT
 FEB. 11,2008
  
  
 BUILDING PLAN REVIEW
 PERMIT: 08010629
 ADD: 6316 S DIXIE HWY
 CONT: KARNS CONSTRUCTION
 TEL: (561)805-7528
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. NOTE NOC
 SUBMITTED.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS PLEASE UPDATE PLANS
 TO THE 2007 FBC SUPPLEMENTS..
  
 2) PLANS DO NOT PROVIDE THE BASIC CRITERIA FOR WIND
 DESIGN. 1609.6.2 WIND DESIGN PROCEDURES
 1)THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3.
 THE WIND SHALL BE ASSUMED TO COME FROM ANY
 HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED
 IN ACCORDANCE WTIH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE
 1609.6.2.1(4)
  
 3)PLANS DO NOT PROVIDE THE VERTICAL, HORIZONTAL OR
 GRAVITY LOADS THE TRUSSES ARE GOING TO BE SUBJECTED TO,
 PLEASE PROVIDE THESE VALUES 1609.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIDING. . 1609.1.1MAIN WIND
 FORCE RESISTING SYSTEMS.
  
 4) PLANS DO NOT PROVIDE ROOF VENTILATION AT LEAST 3
 FEET ABOVE THE EAVE VENTS, 50% OF THE REQUIRED
 VENTILATION MUST BE DERIVED FROM THESE VENTS, 1203.2
 ATTIC VENTING.
  
 5) SHEET # 2 ALTERNATE INSULATION AS STATED ABOVE IN
 COMMENT ?1C? ONLY ONE TYPE OF INSULATION CAN BE
 SPECIFIED, IF THE ICYNENE INSULATION IS THE CHOSEN THIS
 IS CONSIDERED AIR CONDITIONED SPACE AND THE EAVE AND
 UPPER THIRD ROOF VENTILATION IS NOT REQUIRED.
  
 6) SHEET # 2 INDICATES THE ROOF SHEATHING TO BE NAILED
 OFF WITH 8DX 1 ?? SPIRAL SHANK NAILS.
 THESE ARE SHORT NAILS TO BE USED IN THE NAILING OF
 STRAPS INTO TRUSSES. A 8D COMMON NAIL IS 2 ?? LONG.
 SEE THERE IS NO VALUES IN SIMPON OR USP CATALOG FOR
 NAILS THAT DO NOT HAVE A 1 ?? PENETRATION INTO THE
 FRAMING MEMBERS. PLEASE CORRECT, SEE MANUFACTURERS
 SPECIFICATION.
  
 7)PLANS DO NOT PROVIDE ATTIC ACCESS, SEE 1209.2.
  
 8) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 8A)TRUSS ANCHOR STRAPS
 8B)PRE-ENGINEERED A/C STANDS (ROOF MOUNT)
 8C)ROOF VENTS IF THE ICYNENE INSULATION IS NOT USED
 8D) METAL ROOF PANEL- COMPLIED!
  
  
 9)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 10)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-16 Cont ID  
Sent By dpalmer Date 2008-04-16 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2008-04-16 Time 12:41 Sent To  
Notes
2008-04-16 12:42:27SPOKE TO ARCH,
  
 CEILING LTS ARE NEW WALL SCONCES WILL REMAIN IN THE
 SAME LOCATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-14 Cont ID  
Sent By dpalmer Date 2008-04-14 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2008-04-14 Time 18:36 Sent To  
Notes
2008-04-14 18:42:16*** DENIED THIRD REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW.
 LIGHTING PERFORMANCE CALCULATIONS AND PLANS NEEDS TO
 SHOW LIGHTING WHICH IS CONSIDERED "NEW" AND NOT
 "EXISTING".AS STATED PREVIOUSLY AS THESE FIXTURES,
 BOXES, AND ASSOCIATED WIRING IS BEING REMOVED DUE TO
 THE SCOPE OF WORK ASSHOWN ON PLANS THE NEW
 INSTALLATION IS JUST THAT, NEW. PLEASE ADJUST PLANS
 ACCORDINLY.
  
 AS STATED ON PREVIOUS REVIEW IF THERE ARE QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WESTPALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-05 Cont ID  
Sent By dpalmer Date 2008-03-05 Time 19:45 Rev Time 0.00
Received By dpalmer Date 2008-03-05 Time 19:45 Sent To  
Notes
2008-03-05 19:45:12** DENIED2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW WITH
 RESPECT TO LIGHTING PERFORMANCE CALCULATIONS TO BE
 SUBMITTED AND SHOWN ON PLANS. 13-415.2,
 13-415.2.ABC.1.1.
 (THIS IS NOT ENERGY CALCULATIONS)
 PLEASE KNOW AS FIXTURES ARE BEING REMOVED, NEW BOXES
 ARE BEING RELOCATED AND NEW TO BE INSTALLED, THIS IS
 NEW INSTALLATION OF LIGHTING FIXTURES.
 THIS IS NOT ONLY TAKING DOWN EXISTING FIXTURES AND
 PLACING BACK ON THE SAME BOXES AND SAME LOCATIONS.
 ** THESE ARE CONSIDERED NEW AND MINIMUM ON PLANS IS
 REQUIRED.
 PLEASE KNOWAS ELECTRICAL IS ON THE SAME SHEETS WITH
 ARCHITECTURAL ONLY IF ALL OTHER REVIEWS PASS A
 *PROVISO* MAY BE SET UP TO SUBMIT REVISIONS WITHIN
 30DAYS OF ISSUANCE OF PERMIT.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL OR TO GO
 OVER NEEDED INFORMATION ON PLANS FOR LPD.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By dpalmer Date 2008-01-31 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2008-01-31 Time 14:09 Sent To  
Notes
2008-01-31 14:09:57** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT THE LIGHTING PERFORMANCE LEVELS
 FOR DINING SPACE/AREA PER 13-415.2
 PLEASE LIST THE FIXTURES BEING USED.
  
 2) NOTE: PLEASE INDICATE THE LOCATIONS OF NEW OR
 EXISTING EXIT AND EMERGENCY LIGHTING PER NFPA-101 7.8,
 7.9
  
 3) NOTE: PLEASE LIST THE FOLLOWING CODES ON PLANS FOR
 ELECTRICAL.
 2005 NFPA-70
 2003 NFPA-101
  
 4) NOTE: PLEASE KNOW ONLY TWO SETS OF SIGNED, SEALED
 DATED PLANS ARE NEEDED. PLEASE SEE 5 SETS WERE
 SUBMITTED. UP TO THREE SETS SIGNED AND SEALED MAY BE
 SUBMITTED FOR REVIEW AND STAMPING IF EXTRA COPY IS
 DESIRED BY CONTRACTOR HOWEVER AS STATED ONLY TOW ARE
 NEEDED.
 THIS IS FOR INFORMATION ONLY AS TWO SETS WERE SIGNED
 AND SEALED.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-05-02 Cont ID  
Sent By mawillia Date 2008-05-02 Time 13:58 Rev Time 0.00
Received By mawillia Date 2008-05-02 Time 13:58 Sent To  
Notes
2008-05-02 13:58:05*****APPROVED*****
  
  
 NEW PLAN SHEET 1(OF 2) STAMPED, INITIAIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-03-25 Cont ID  
Sent By mawillia Date 2008-03-25 Time 20:11 Rev Time 0.00
Received By mawillia Date 2008-03-25 Time 20:09 Sent To  
Notes
2008-03-25 20:11:36*****APPROVED*****
  
  
 PLAN SHEET 1 STAMPED, INITIAIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-02-20 Cont ID  
Sent By mawillia Date 2008-02-20 Time 16:07 Rev Time 0.00
Received By mawillia Date 2008-02-20 Time 15:55 Sent To  
Notes
2008-02-20 16:06:37*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS HAVE BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 13:38 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 13:38 Sent To  
Notes
2008-04-11 13:45:08TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 14:03 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 14:03 Sent To  
Notes
2008-02-26 14:07:26TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-20 Cont ID  
Sent By mawillia Date 2008-02-20 Time 15:58 Rev Time 0.00
Received By mawillia Date 2008-01-28 Time 09:45 Sent To  
Notes
2008-01-28 09:47:27TO "COMM" BD#26

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-01-30 Cont ID  
Sent By tgordon Date 2008-01-30 Time 09:32 Rev Time 0.20
Received By tgordon Date 2008-01-30 Time 09:32 Sent To  
Notes
2008-01-30 09:34:21NOTE: A MECHANICAL PERMIT WILL BE REQUIRED WHEN
 RELOCATING A/C CONDENSER UNIT.

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By choops Date 2008-01-31 Time 16:37 Rev Time 0.00
Received By choops Date 2008-01-31 Time 16:37 Sent To  
Notes
2008-01-31 16:37:35NEW ROOF FRAMING
  
 *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.