Plan Review Details - Permit 08010530
Plan Review Stops For Permit 08010530
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By adarroug Date 2008-01-24 Time 14:15 Rev Time 0.00
Received By adarroug Date 2008-01-24 Time 14:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-23 Cont ID  
Sent By shill Date 2008-01-23 Time 15:07 Rev Time 0.00
Received By shill Date 2008-01-23 Time 15:07 Sent To  
Notes
2008-01-23 15:24:42****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER
 REQUIRED FS553.844(5)(A). PROVIDE INFORMATION
 (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT.INFORMATION IS
 AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION.
  
 2.)THE EVALUATION REPORT IS INCOMPLETE.PLEASE
 PROVIDE THE FIRST SHEETS OF THE NOA WHICH INCLUDE
 COMPONENT INFORMTION.IF YOU ARE UNSURE AS TO WHICH
 PAGES TO INCLUDE, PROVIDE A COMPLETE REPORT AND I WILL
 REMOVE THE UNNECESSARY SHEETS FOR YOU.
  
 3.)FOR THE FLAT ROOF, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.ALSO INDICATE WHICH FASTENER YOU ARE
 USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.NOTE THAT ONE SYSTEM IS HIGHLIGHTED, BUT
 THERE ARE SEVERAL SYSTEMS INCLUDED IN THE PACKAGE YOU
 PROVIDED.
  
 4.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED FASTENING
 FOR CORNER AND PERIMETER ZONES.THIS IS TO BE EITHER
 WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED ON
 LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB SHEET).
  
  
 ONLY ONE LETTER WAS PROVIDED.PLEASE ALWAYS INCLUDE
 TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS.
  