Plan Review Details - Permit 08010423
Plan Review Stops For Permit 08010423
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-10 Cont ID  
Sent By mjacobs Date 2008-05-10 Time 10:37 Rev Time 0.00
Received By mjacobs Date 2008-05-10 Time 09:42 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-03-15 Cont ID  
Sent By mjacobs Date 2008-03-15 Time 14:56 Rev Time 0.00
Received By mjacobs Date 2008-03-15 Time 13:44 Sent To PC
Notes
2008-03-15 14:56:16 
  
 BUILDING PLAN REVIEW
 PERMIT: 08010423
 ADD: 1745 PINE HURST DR.
 CONT: HAI- TECH ELECTRIC LLC.
 TEL: (561)389-5343
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)2004 FBC 1609.1.3 PLEASE PROVIDE INFORMATION ON THE
 ANCHORAGE THE GENERATOR TO RESIST THE MOMENT OF
 OVERTURNING, UPLIFT AND SLIDING.
  
 GENERATOR SLAB & ANCHOR REQUIREMENT PLEASE PROVIDE
 SIZE OF GENERATOR(WXL),PLUS PROVIDE PLANS WITH THE
 INFORMATION DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE THE DEVICE
 REQUIRES WITHOUT LOAD REDUCTION.
  
 PROVIDE PLANS ENOUGH TO VERIFY LOCATION OF GENERATOR
 VERSES BUILDING OPENINGS WINDOWS, DOORS OR SOFFIT TYPE
 VENTS, ETC.
  
 2) 1609.6.2 WIND DESIGN PROCEDURES
 1)THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3.THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 3)PROVIDE TWO SETS OF DRAWINGS SHOWING THE LOCATION
 OF THE GENERATOR SLAB WITH ALL INFORMATION MENTIONED
 ABOVE. THE LENGTH WIDTH AND THICKNESS OF THE SLAB SHALL
 BE INDICATED ON THE DRAWINGS. IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE
 PRACTICE OF ARCHITECTURE AS PROVIDED FOR IN CHAPTER
 481, 471 FLORIDA STATUTES THEN HE OR SHE SHALL AFFIX
 HIS OR HER OFFICIAL SEAL, SIGNATURE AND DATE TO SAID
 DRAWINGS. THESE DRAWINGS SHALL CONTAIN THE ORIGINAL
 SIGNATURE OF THE PERSON SEALING THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2008-05-22 Cont ID  
Sent By btrobaug Date 2008-05-22 Time 11:49 Rev Time 0.00
Received By btrobaug Date 2008-05-22 Time 11:47 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-05 Cont ID  
Sent By btrobaug Date 2008-05-05 Time 13:48 Rev Time 0.00
Received By btrobaug Date 2008-05-05 Time 13:36 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-11 Cont ID  
Sent By btrobaug Date 2008-03-11 Time 10:20 Rev Time 0.00
Received By btrobaug Date 2008-03-11 Time 10:11 Sent To M
Notes
2008-03-11 10:20:00 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} PROVIDE A RISER DIAGRAM PER 215.5 INCLUDING
 GENERATOR AND RELATED EQUIPMENT.
  
 2} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE
 GENERATOR AND TRANSFER SWITCH.THREE MODELS ARE ON THE
 SPEC SHEET SUBMITTED.
  
 3} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC.702.5 CAPACITY AND
 RATING. AN OPTIONAL STANDBY SYSTEM SHALL HAVE ADEQUATE
 CAPACITY AND RATING FOR THE SUPPLY OF ALL EQUIPMENT
 INTENDED TO BE OPERATED AT ONE TIME.
  
 4} PROVIDE A PANEL SCHEDULE FOR THE GENERATOR PANEL.
 106.3.5.4 FBC AS AMENDED.
  
 5} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW
 PER 106.1 FBC AS AMENDED. THE PERSON TAKING
 RESPONSIBILITY FOR THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME, ALL SHEETS, PER 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 10:40 Rev Time 0.00
Received By btrobaug Date 2008-01-23 Time 10:31 Sent To I
Notes
2008-01-23 10:40:27 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THREREHAS BEEN NO GENERATOR PERMIT APPLIED FOR THIS
 PROPERTY.THE DRAWING INDICATES A GENERATOR IS EITHER
 EXISTING OR TO BE INSTALLEDA GENERATOR ( GEN RES)
 MUSTBE APPLIED FOR, AND INCLUDE THE COST OF THE
 EQUIPMENT AND LABOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-05-23 Cont ID  
Sent By mperson Date 2008-05-23 Time 10:50 Rev Time 0.00
Received By mperson Date 2008-05-23 Time 10:50 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-05-05 Cont ID  
Sent By mperson Date 2008-05-06 Time 16:35 Rev Time 0.00
Received By mperson Date 2008-05-05 Time 16:35 Sent To B
Notes
2008-05-05 16:37:52GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS GAS REVIEW COMMENTS FOR THE PURPOSE OF
 CONTINUITY.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER SECTION 401.1 SCOPE.
 **THIS INCLUDES THE EXISTING GAS SYSTEM. SEE PERMIT
 INFORMATION INDICATING EXISTING GAS TO SAID ADDRESS
 ATTACHED TO THESE COMMENTS.
  
 **NOTE: THE GAS ISOMETRIC RISER DIAGRAMS BY FLORIDA
 PUBLIC UTILITIES CO. PERMIT #08040547 SUBMITTED WITH
 THIS GEN/RES PERMIT APPLICATION ARE NOT INDICATING ANY
 GAS PIPING TO THE PROPOSED GENERATOR. THE ONLY NEW GAS
 PIPING BEING INDICATED IS TO A NEW 99,000 BTU RINNAI.
 PLEASE CORRECT THE GAS ISOMETRIC TO INCLUDE THE
 PROPOSED GENERATOR. THE GAS ISOMETRIC IS NOT INDICATING
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE
 PLEASE REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED
 AREAS INDICATING THIS. THE ONLY CORRESPONDING LENGTH TO
 CUT SECTION OF PIPE FOR "NEW" WORK IS FOR THE
 UNDERGROUND PIPING TO THE RINNAI. WHAT ARE THE
 CORRESPONDING LENTHS TO THE ABOVE GROUND CUT SECTIONS
 OF PIPE AND THE MISSING GAS PIPE FOR THE PROPOSED
 GENERATOR? PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 **NOTE: THE GAS ISOMETRC RISER DIAGRAMS BY FLORIDA
 PUBLIC UTILITIES CO. ARE NOT INDICATING THE ABOVE
 GROUND PIPING MATERIAL TO THE NEW 99,000 RINNIA AND
 THERE IS NO INDICATION FOR GAS PIPING OR MATERIALS FOR
 THE PROPOSED GENERATOR. PER FBC-2004 FUEL GAS SECTION
 401.1 SCOPE.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE
 COMMENT #1.
  
 **NOTE: THE GAS ISOMETRIC RISER DIAGRAMS BY FLORIDA
 PUBLIC UTILITIES CO. ARE NOT INDICATING THE BTU LOAD
 FOR THE PROPOSED GENERATOR. PLEASE REFERENCE COMMENTS
 #1 AND 2 AND COMPLY.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE
 COMENT #1.
  
 **NOTE: PLEASE REFERENCE COMMENT #1, 2 AND 4 AND
 COMPLY.
  
 6. "OK" COMMENT ADDRESSED.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE GENERATOR CLEARLY
 INDICATING THE MODEL NUMBER, BTU LOAD CAPACITY WITH
 GENERATOR RUNNING @ 100%, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
 NOTE: EXISTING GAS SYSTEM WAS LP/GAS, IF GAS TO
 PROPOSED GENERATOR IS ALSO LP/GAS PLEASE SUBMIT TWO
 COPIES OF MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 REQUIRED 2ND STAGE REGULATOR CLEARLY INDICATING THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 **NOTE: THE RESUBMITTED MANUFACTURER'S SPECIFICATION
 SHEETS FOR THE PROPOSED GENERATOR ARE NOT CLEARLY
 INDICATING THE BTU CAPACITY WITH THE GENERATOR RUNNING
 AT 100% AND THERE ARE NOT TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE 2ND STAGE REGULATOR BEING
 INDICATED ON THE GAS ISOMETRIC WITH THE MAKE, MODEL
 NUMBER, BTU LOAD CAPACITY AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 8. "OK" COMMENT ADDRESSED.
  
 9. "OK" COMMENT ADDRESSED.
  
 10. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-03-11 Cont ID  
Sent By mperson Date 2008-03-11 Time 15:48 Rev Time 0.00
Received By mperson Date 2008-03-11 Time 15:48 Sent To B
Notes
2008-03-11 16:17:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL GEN/RES
 INSPECTION. THE FOLLOWING INFORMATION IS REQUIRED FOR
 THE GAS PERMIT APPLICATION ON THE REQUIRED GAS
 ISOMETRIC RISER DIAGRAM.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER SECTION 401.1 SCOPE.
 **THIS INCLUDES THE EXISTING GAS SYSTEM. SEE PERMIT
 INFORMATION INDICATING EXISTING GAS TO SAID ADDRESS
 ATTACHED TO THESE COMMENTS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 3. TYPE OF GAS, (LP OR NATURAL) PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE
 COMMENT #1.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **THIS INCLUDES THE EXISTING GAS SYSTEM. REFERENCE
 COMENT #1.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. LP GAS SPECIFY 10
 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS FOR THE GENERATOR CLEARLY
 INDICATING THE MODEL NUMBER, BTU LOAD CAPACITY WITH
 GENERATOR RUNNING @ 100%, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
 NOTE: EXISTING GAS SYSTEM WAS LP/GAS, IF GAS TO
 PROPOSED GENERATOR IS ALSO LP/GAS PLEASE SUBMIT TWO
 COPIES OF MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 REQUIRED 2ND STAGE REGULATOR CLEARLY INDICATING THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 8. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 **NOTE: IF TANK IS EXISTING, PLEASE INDICATE THAT IT
 IS EXISTING.
  
 9. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 10. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 11:11 Sent To E
Notes
2008-05-20 11:12:33TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-05 Cont ID  
Sent By adarroug Date 2008-05-05 Time 08:44 Rev Time 0.00
Received By adarroug Date 2008-05-05 Time 08:44 Sent To E
Notes
2008-05-05 08:47:18TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 11:44 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 11:44 Sent To E
Notes
2008-03-07 11:45:12TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 10:40 Rev Time 0.00
Received By btrobaug Date 2008-01-18 Time 11:02 Sent To PC
Notes
2008-01-18 11:02:11TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-03-11 Cont ID  
Sent By tgordon Date 2008-03-11 Time 11:44 Rev Time 0.20
Received By tgordon Date 2008-03-11 Time 11:44 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-03-10 Cont ID  
Sent By choops Date 2008-03-10 Time 16:44 Rev Time 0.00
Received By choops Date 2008-03-10 Time 16:44 Sent To E
Notes
2008-03-10 16:46:58***APPROVED***
  
 PROVISO:GENERATOR SHALL NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
  
  
  
 SENT TO "E" - BT