Plan Review Details - Permit 08010414
Plan Review Stops For Permit 08010414
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-05 Cont ID  
Sent By lmartine Date 2008-09-05 Time 12:43 Rev Time 0.00
Received By lmartine Date 2008-09-05 Time 12:43 Sent To  
Notes
2008-09-05 12:44:39SEE PROVISO ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-29 Cont ID  
Sent By kconrad Date 2008-04-29 Time 18:52 Rev Time 0.00
Received By kconrad Date 2008-04-29 Time 16:15 Sent To I
Notes
2008-04-29 18:56:03SPOKE WITH KEVIN DENNEHY AND ADVISED HIM THAT THE SCOPE
 OF WORK WILL BE REVISED TO REFLECT THE PROPOSED
 WINDOW/DOOR INSTALLATIONS. ALSO THE PROJECT VALUATION
 WILL BE INCREASED TO REFLECT THE SAME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-18 Cont ID  
Sent By kconrad Date 2008-03-18 Time 18:03 Rev Time 0.00
Received By kconrad Date 2008-03-18 Time 16:00 Sent To I
Notes
2008-03-18 18:01:41PROJECT: 1700 PRESIDENTIAL WAY #203
  
 CODE REVIEW:
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) PLEASE SUBMIT (2) COPIES OF EACH: FLORIDA STATE
 PRODUCT APPROVALS AND THE REVISED MIAMI_DADE PRODUCT
 APPROVALS FOR THE PW-701, SH-700 WINDOWS AND THE
 SGD-730 IMPACT SLIDING GLASS DOORS.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By kconrad Date 2008-01-31 Time 19:04 Rev Time 0.00
Received By kconrad Date 2008-01-31 Time 17:45 Sent To  
Notes
2008-01-31 17:46:50PROJECT: 1700 PRESIDENTIAL WAY #203
  
 CODE REVIEW:
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) REQUIRE A NOTICE OF COMMENCEMENT AS PER THE
 FOLLOWING:
  
 FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) PLEASE INDICATE THE LEVEL OF ALTERATION AS PER THE
 FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE, SECTION301.5 :A
 DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR A
 COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION 303,304 & 305
 OF THIS CODE.
  
 3) PLEASE INDICATE ON FLOOR PLAN:NEW WALLS/EXISTING
 WALLS.
  
 4) PLEASE PROVIDE PRODUCT APPROVALS FOR THE INDICATED
 SLIDING GLASS DOORS.
  
 5) THE PRESCRIPTIVE FIRE RESISTANCE INDICATED ON THE
 TWO HOUR RATED WALL DOES NOT REFLECT THE DATA SHOWN BY
 TABLE 720.1(2)#13-1.3.
 PLEASE CORRECT THE SAME OR INDICATE A TESTED AND
 APPROVED RATED ASSEMBLY.
  
 6) PLEASE PROVIDE INTERIOR DIMENSIONS AND SQUARE
 FOOTAGE.
  
 7) PLEASE PROVIDE ENERGY CALCULATIONS AS PER THE
 FOLLOWING:
  
 512.1MINIMUM REQUIREMENTS.
 ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 8) PLEASE CORRECT PROJECT ADDRESS LOCATED WITHIN THE
 TITLE BLOCK: 1600 PRESIDENTIAL WAY SHOULD BE 1700
 PRESIDENTIAL WAY.
  
 END COMMENTS
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-16 Cont ID  
Sent By btrobaug Date 2008-04-16 Time 16:40 Rev Time 0.00
Received By btrobaug Date 2008-04-16 Time 16:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-14 Cont ID  
Sent By dpalmer Date 2008-03-14 Time 10:09 Rev Time 0.00
Received By dpalmer Date 2008-03-14 Time 10:09 Sent To  
Notes
2008-03-14 10:09:46** DENIED2RD REVIEW **
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST
 REVIEW WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS DUE TO INFORMATION NOW BEING ADDED TO PLANS.
  
 1) NOTE: PLEASE SEE THE RISER WHICH SHOWS NO OCP FOR
 PANEL.
 230.70, 230.71. IS THIS A METER CENTER?
  
 2) NOTE: PLEASE SEE THE RISER SHOWS 3-#3, 1#8 AND
 ANOTHER #8? WHAT IS THIS SECOND #8?
 PLEASE CLARIFY.
 230, 215, 310
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE WITH RESPECT
 TO 210.11C1, 210.52B1 AND 220.52 AS ONE OR MORE OF THE
 SMALL APPLIANCE, DINING ROOM RECEPTACLE CIRCUITS ETC
 ARE REQUIRED TO BE FIGURED AT 1500VA. PLEASE SEE LOAD
 CALCULATIONS ONLY SHOW THE TWO SMALL APPLIANCE
 CIRCUITS.
  
 4) NOTE: PLEASE SEE THE CU IS BEING SHOWN ON A 1-POLE
 20AMP CIRCUIT.HOW CAN THIS BE CORRECT WITH A 2.5 TON
 CU.THE MODEL AS GIVEN BY THE MANUFACTURE STATES A
 MINIMUM OF 230V.
 PLEASE ADJUST.
 240.4, 310.16, 408.4, 110.3, 90.7
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE KITCHEN COUNTER WHICH REQUIRES GFI
 WITHIN 2FT OF THE END OF COUNTER SPACE.
 PLEASE ALSO SEE THE DISPOSAL IN KITCHEN DOES NOT SHOW
 ANY METHOD FOR CONTROL. WILL THIS BE SELF ACTUATING?
 210.52C1
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SEE 424.3B WHICH REQUIRES OCP FOR HEAT
 IN AHU TO BE SIZED AT 125%. PANEL SHOWS 40AMP OCP. MIN
 PER SECTION OF CODE GIVEN SHOULD BE 45AMPS.
 THE SIZING OF BRANCH-CIRCUIT CONDUCTORS AND
 OVER-CURRENT DEVICES SUPPLYING FIXED ELECTRIC
 SPACE-HEATING EQUIPMENT AT 125 PERCENT OF THE TOTAL
 LOAD OF THE HEATERS (AND MOTORS) IS PREDICATED ON THE
 NEED TO PROTECT OVER-CURRENT DEVICES, PARTICULARLY IN
 PANEL-BOARDS, AND CONDUCTORS FROM OVERHEATING DURING
 PERIODS OF PROLONGED OPERATION.
 ** THIS ALSO AFFECTS FEEDERS AND LOAD CALCULATIONS.
  
 7) NOTE: PLEASE GO OVER LOAD CALCULATIONS. BASED ON
 COMMENTS ABOVE THE LOAD WILL BE INCREASING DUE TO SOME
 ITEMS MISSING.
 PLEASE ALSO SEE LOADS SUCH AS DISPOSAL WHICH IS BEING
 SHOWN AS 1500VA ON PANEL SCHEDULE AND 1000VA ON LOAD
 CALCULATIONS. WHAT HAPPENED TO THE OTHER 500VA?
 PLEASE SEE 422.13 AS THIS SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.
 AS THE LOAD ON THE SERVICE PANEL IS SHOWN VERY CLOSE TO
 BEING OVERLOADED THERE IS CONCERN OVER THE SIZE.
 220, 215 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 8) NOTE: PLEASE SEE SPECIFIC NOTES ON PREVIOUS REVIEW
 AND ALONG WITH FBC AND FS REQUIRES THE CODE ADOPTED AND
 UNDER DESIGN FOR ANY PROJECT TO BE STATED ON PLANS
 ALONG WITH LEVEL OF ALTERATION.
 FS 553.73
 CODES WERE ADDED HOWEVER NOT YEAR EDITION AS GIVEN ON
 PREVIOUS REVIEW.
 2005 NFPA70
 2003 NFPA_101
 2002 NFPA-72
  
 9) NOTE: PLEASE SEE MISSING RECEPTACLE ALONG 2FT OR
 MORE OF WALL SPACE 210.52
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-22 Cont ID  
Sent By dpalmer Date 2008-01-22 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2008-01-22 Time 14:11 Sent To  
Notes
2008-01-22 14:11:41 
  
 ** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS FOR RELEVANT DESIGN.
 FBC 2004 W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FS 481.219 FOR POSSIBLE FICTITIOUS
 NAME FOR ARCHITECT.
 PLEASE COMPLETE INFORMATION ON TITLE BLOCKS PER FAC
 61G1-16.004
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULE.
 PLEASE SEE 240.4, 310.16, 408.4
 FBC 106.3.5.1.2 (ADDITIONAL INFORMATION).
  
 4) NOTE: PLEASE SEE SOME CIRCUITS ON PANEL SCHEDULE AS
 SHOWN DO NOT COMPLY WITH THE NEC. FOR EXAMPLE: PLEASE
 SEE WATER HEATER WHICH IS SHOWN AS 4500VA LOAD YET THIS
 IS ONLY SHOWN ON A SINGLE POLE 25AMP BRANCH CIRCUIT.
 PLEASE SEE 422.13, 240.4, 310.16 ETC
  
 5) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES.
 PLEASE SEE THE PLANS CALL FOR *SMOKE DETECTORS* AND BY
 DEFINITION THIS WOULD MEAN THESE ARE PART OF A FIRE
 ALARM SYSTEM. SMOKE DETECTORS ONLY DETECT AND DO NOT
 SOUND WARNING. PLEASE SEE BASED ON PLANS AND PANEL
 SCHEDULE IT SEEMS THESE ARE *SMOKE ALARMS* WHICH
 ACTUALLY DETECT AND SOUND AND ALARM.
 PLEASE CLARIFY AND COMPLETE.
  
 6) NOTE: PLEASE SEE 210.12 AS ARC FAULT PROTECTION IS
 REQUIRED FOR ALL BRANCH CIRCUITS/OUTLETS IN SLEEPING
 ROOMS.
 PLEASE SEE ONLY ONE BRANCH CIRCUIT FOR SMOKE DETECTION
 TYPE DEVICES SHOWS AFCI BREAKER.
 PLEASE ADJUST AND LIST ALL CIRCUITS REQUIRED.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 FOR
 SMALL APPLIANCE CIRCUITS ALONG WITH DINING AREAS AND
 AREAS OF THE LIKE.
  
 8) NOTE: PLEASE CLARIFY IF THE PANEL SHOWN ON PLANS IS
 NEW OR ALREADY EXIST? SHOWN ON PLANS AS NEW YET NO
 CONDUCTORS FOR NEW OR EXISTING FEEDERS IS SHOWN.
 240.4, 310.16 ETC
  
 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR SMOKE DETECTION
 DEVICE LOCATIONS. PLEASE SEE NO DEVICES SHALL BE WITHIN
 3FT OF DOORS TO BATHROOMS.
 PLEASE SEE OTHER REQUIRED DISTANCES AND ALSO SPECIFIC
 REQUIREMENTS PER THE MANUFACTURE.
 110.3
  
 10) NOTE: PLEASE SEE 210.11C3 FOR MISSING DEDICATED
 BATH CIRCUIT(S).
 MUST BE 20AMP AND #12.
  
 ** PLEASE COMPLETE THE ABOVE AND KNOW AS THERE IS
 INFORMATION NOT YET SHOWN A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-18 Cont ID  
Sent By mwennerg Date 2008-04-18 Time 14:07 Rev Time 0.00
Received By mwennerg Date 2008-04-18 Time 14:07 Sent To  
Notes
2008-04-18 14:08:12COMPLY WITH NFPA 241

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-03-20 Cont ID  
Sent By mawillia Date 2008-03-20 Time 12:23 Rev Time 0.00
Received By mawillia Date 2008-03-20 Time 12:11 Sent To  
Notes
2008-03-20 12:19:32*****DENIED*****
  
 *THE FOLLOWING COMMENT FROM THE PREVIOUS PLAN REVIEW
 STILL NEED TO BE ADDRESSED.CAPS TO INDICATE HOW
 COMMENT CAN BE ADDRESSED
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.ADD 2003 EDITION TO NFPA 101 LISTED IN
 CODE LIST
  
 *NEW
  
 A.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 NFPA 241 TO CODE LIST
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-01 Cont ID  
Sent By mwennerg Date 2008-02-01 Time 14:14 Rev Time 0.00
Received By mwennerg Date 2008-02-01 Time 14:14 Sent To  
Notes
2008-02-01 14:19:57***DENIED***
  
 1) PLEASE REFER TO ELECTRICAL REVIEW COMMENT REGARDING
 SMOKE DETECTION DEVICES. IT WOULD BE PROBABLE THAT
 REFERENCED DEVICES ARE NOT TIED TO THE BUILDING FIRE
 ALARM SYSTEM THEREBY INDICATING SMOKE ALARMS.
  
 2) IN ADDITION TO LOCATIONS ALREADY MENTIONED, SMOKE
 ALARMS SHALL BE A MINIMUM OF (3') FROM AC DIFFUSERS.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-20 Cont ID  
Sent By adarroug Date 2008-08-20 Time 16:31 Rev Time 0.00
Received By adarroug Date 2008-08-20 Time 16:31 Sent To  
Notes
2008-08-22 10:46:01TO:TOM G.
2008-08-20 16:31:27WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 16:17 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 16:17 Sent To  
Notes
2008-08-08 16:21:41TO "BOB"#16
2008-08-04 16:17:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 10:11 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 10:10 Sent To M
Notes
2008-07-03 10:11:19TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-15 Cont ID  
Sent By adarroug Date 2008-04-15 Time 10:00 Rev Time 0.00
Received By adarroug Date 2008-04-15 Time 10:00 Sent To  
Notes
2008-04-15 10:05:32TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-12 Cont ID  
Sent By adarroug Date 2008-03-12 Time 09:37 Rev Time 0.00
Received By adarroug Date 2008-03-12 Time 09:37 Sent To  
Notes
2008-03-12 09:38:05TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-01 Cont ID  
Sent By mwennerg Date 2008-02-01 Time 14:21 Rev Time 0.00
Received By mwennerg Date 2008-01-18 Time 11:09 Sent To  
Notes
2008-01-18 11:11:20TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-08-22 Cont ID  
Sent By tgordon Date 2008-08-22 Time 10:46 Rev Time 0.45
Received By tgordon Date 2008-08-22 Time 10:46 Sent To B
Notes
2008-08-22 10:46:59REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-08-11 Cont ID  
Sent By tgordon Date 2008-08-11 Time 09:31 Rev Time 0.30
Received By tgordon Date 2008-08-11 Time 09:31 Sent To  
Notes
2008-08-11 09:35:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
  
 1) PLANS SUBMITTED ARE FOR 1801 CONSULATE PLACE #201,
 THIS PERMIT IS FOR 1700 PRESIDENTIAL WAY #203. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-07-15 Cont ID  
Sent By tgordon Date 2008-07-15 Time 16:34 Rev Time 0.30
Received By tgordon Date 2008-07-15 Time 16:34 Sent To  
Notes
2008-07-15 16:35:04REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-07-03 Cont ID  
Sent By tgordon Date 2008-07-03 Time 14:46 Rev Time 0.45
Received By tgordon Date 2008-07-03 Time 14:46 Sent To  
Notes
2008-07-03 14:54:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN
 *** DENIED ***
  
 1) REVISED MECHANICAL PLAN NEEDS TO BE SIGNED AND
 SEALED BY THE ENGINEER (JAMES MINGES), PER FAC
 61G1-16.003.
  
 2) PROVIDE FOR RETURN AIR TO BEDROOMS 1 AND 2, PER 2004
 FBC/R M1602.4.
  
 3) EQUIPMENT SCHEDULE SHOWS THE SYSTEM AS A 12 SEER,
 PER 2004 FBC 13-607.1.ABC.3.2.1 THE MINIMUM SEER IS 13.
 PLEASE CORRECT.
  
 4) THE SUITE NUMBERFOR THIS UNIT IS 203 ACCORDING TO
 CITY RECORDS, PLANS SHOW THE SUITE NUMBER CHANGED TO
 103. PLEASE CORRECT.
  
 5) PLEASE SHOW THE SIZES OF ALL GRILLS ON THE
 MECHANICAL PLAN, PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 7) SHOW THE SIZES OF ALL THE SUPPLY AND RETURN AIR
 DUCTS ON THE MECHANICAL PLAN, AS NO DUCTS ARE SIZED ON
 THIS PLAN, PER 2004 WPB AMEND. 106.5.4.3 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By tgordon Date 2008-04-15 Time 14:14 Rev Time 0.30
Received By tgordon Date 2008-04-15 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-12 Cont ID  
Sent By tgordon Date 2008-03-12 Time 10:19 Rev Time 0.25
Received By tgordon Date 2008-03-12 Time 10:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By tgordon Date 2008-01-18 Time 13:30 Rev Time 0.40
Received By tgordon Date 2008-01-18 Time 13:30 Sent To  
Notes
2008-01-18 14:10:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE NAME IN THE TITLE BLOCK "BLUE MINGES ARCHITECT"
 IS A FICTITIOUS NAME AND AS A FIRMS NAME WOULD REQUIRE
 A CERTIFICATE OF AUTHORIZATION, SEE F.S. 481.219 (2).
 PLEASE CORRECT.
  
 2) PLEASE SHOW THE RETURN DUCT (FLEX) AND SIZE TO BED
 #1 AND BED #2, SEE 2004 FBC 106.3.5.
  
 3) THE RETURN AIR GRILL IN BED #3 IS SHOWN AS A SUPPLY
 GRILL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-18 Cont ID  
Sent By jleech Date 2008-04-18 Time 07:43 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-03-17 Cont ID  
Sent By jleech Date 2008-03-17 Time 13:43 Rev Time 0.00
Received By jleech Date 2008-03-17 Time 13:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-24 Cont ID  
Sent By jleech Date 2008-01-24 Time 08:15 Rev Time 0.00
Received By jleech Date 2008-01-24 Time 08:13 Sent To  
Notes
2008-01-24 08:24:46DENIED;
 1. SEE ELECTRICAL PLAN REVIEWER'S NOTE 1.
 2. ADDRESS ON APPLICATION AND DRAWING, NOT THE SAME.
 3. A PLUMBING COMPANY IS SIGNED ON THE BUILDING
 APPLICATION, AS A SUB, NO MENTION ON PLANS AS TO WHAT
 THESCOPE OF PLUMBINGWORK IS TO BE DONE. PLEASE
 LIST ON PLANS PLUMBER'S SCOPE.I.E. CHANGE OUT ALL
 PLUMBING FIXTURES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-23 Cont ID  
Sent By choops Date 2008-01-23 Time 15:12 Rev Time 0.00
Received By choops Date 2008-01-23 Time 15:12 Sent To  
Notes
2008-01-23 15:12:51*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.