Plan Review Details - Permit 08010413
Plan Review Stops For Permit 08010413
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-05-29 Cont ID  
Sent By rmcdouga Date 2009-05-29 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2009-05-29 Time 09:48 Sent To  
Notes
2009-05-29 09:49:57REVISION TO CHANGE SIZE OF THE B-4 BEAM IN BEAM
 SCHEDULE IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-05-27 Cont ID  
Sent By rmcdouga Date 2009-05-27 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2009-05-27 Time 10:44 Sent To  
Notes
2009-05-27 10:46:50SUBMITTED SIGNED AND SEALED 8.5" X 11" DETAIL OF
 REVISED DOOR AT COVERED PORCH #2 AS REQUESTED IN
 PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-04-09 Cont ID  
Sent By rmcdouga Date 2009-04-09 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2009-04-09 Time 09:38 Sent To  
Notes
2009-04-09 09:46:14BUILDING PROVISO
  
 THE REVISION TO REPLACE THE NANAWALL FOLDING GLASS WALL
 W/FIXED GLASS TRANSOM ABOVE WITH THE WINDOOR SERIES
 8000 SLIDING GLASS DOOR IS OKAY. CONTRACTOR IS TO
 SUBMIT TWO COPIES OF 8-1/2" X 11" SIGNED AND SEALED
 DRAWING OF THE NEW DOOR, SPECIFING THE OVERALL
 DIMENSIONS AND INDIVIDUAL PANEL SIZES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-01-27 Cont ID  
Sent By rmcdouga Date 2009-01-27 Time 13:22 Rev Time 0.00
Received By rmcdouga Date 2009-01-27 Time 13:22 Sent To  
Notes
2009-01-27 13:30:35THE REVISION TO SIZE OF THE B-4 BEAM IS DENIED. THE B-2
 BEAM ON THE REVISION HAS BEEN CHANGED FROM THE 8 X 30
 BEAM SPECIFIED ON THE APPROVED PLANS, BUT HAS NOT BEEN
 CLOUDED ON THE REVISION TO INDICATE THAT IT WAS
 CHANGED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-02 Cont ID  
Sent By amorse Date 2008-08-02 Time 09:21 Rev Time 0.00
Received By amorse Date 2008-08-02 Time 09:21 Sent To Z
Notes
2008-08-02 09:23:30 
  
 PASSED
  
 ROUTED BACK TO LUIS FOR ZONING REVIEW, REQUIRES DATE
 STAMP UPON ZONING APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-22 Cont ID  
Sent By amorse Date 2008-05-22 Time 17:50 Rev Time 0.00
Received By amorse Date 2008-05-22 Time 17:49 Sent To PC
Notes
2008-05-22 18:28:01 
  
  
 DENIED
  
 THE FOLLOWING COMMENT FROM THE 1STREVIEW WERE NOT
 ADDRESSED:
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMITSETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES. THE BALANCE DUE
 FOR RADON IS $24.22
  
 7)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES. *******ARE THE SMOKE ALARMS EXISTING
 AND HARD WIRED, PLEASE CLARIFY*******
  
 11)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 ********NO SUBMITTED PRODUCT APPROVALS HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD******
  
 12)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED ******NOTE FLORIDA APPROVAL NUMBERS ARE WRITTEN
 AT TOP OF NOA'S*******
  
 ********FLORIDA STATEWIDE PRODUCT APPROVAL SHEETS WERE
 NOT PROVIDED**********
  
 13)NO PRODUCT APPROVALS WERE SUBMITTED FOR NANA WALL
 SYSTEM. ******** THE SL70 THAT IS SPECIFIED ON SHEET
 A-1 IS A FOLDING DOOR SYSTEM IN AN EXTERIOR WALL AND AS
 SUCH CONSIDERED PART OF THE COMPONENTS AND CLADDING OF
 THE BUILDING. THEY ARE ALSO SUBJECT TO MIN DESIGN
 PRESSURES BASED ON LOCATION AND SQUARE FOOTAGE OF WALL
 AREA, THEREFORE PRODUCT APPROVALS ARE REQUIRED. PLEASE
 FIND UNDER FLORIDA STATEWIDE APPROVAL NUMBER FL6859-R1
 WITH THE COMPLIANCE REPORTS FOR DOOR TYPE. NOTE THIS
 MODEL IS LARGE MISSILE IMPACT RATED**********
  
 14)ALL WINDOW OPENINGS AND CONFIGURATIONS FOR
 ALTERNATE #1 SHALL BE LISTED AND APPROPRIATE PRODUCT
 APPROVALS SUBMITTED FOR WORK TO BE INCLUDED IN THIS
 PERMIT********PROVIDE FLORIDA STATEWIDE APPROVAL FL #
 9066-R1 WITH COMPLIANCE REPORT MIAMI-DADE NOA #
 08-8304.08 WHICH REVISES THE REPORT THAT WAS SUBMITTED
 WERE NOT SUBMITTED*********
  
 16)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 & 2007 AMENDMENTS
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF THE
 OLD PAGES ONLY FOR REFERENCE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-22 Cont ID  
Sent By amorse Date 2008-01-22 Time 18:25 Rev Time 0.00
Received By amorse Date 2008-01-22 Time 17:49 Sent To E
Notes
2008-01-22 18:58:33 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMITSETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES. THE BALANCE DUE
 FOR RADON IS $24.22
  
 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004. ****PLEASE NOTE THAT SIGNATURES WERE NOT DATED ON
 THE ARCHITECTURAL SHEETS*****
  
 4)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 5)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES. MINIMUM ROUGH OPENING 22"
 X 30"
  
 6)BUILDING ELEVATIONS TO INCLUDE MEAN ROOF HEIGHT
  
 7)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 8)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES REMOVE
 ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF NEW
 DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF THE OLD
 PAGES ONLY FOR REFERENCE
  
 9)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. MINIMUM 8D RING SHANK NAILS 6" O/C
 IN ZONES 1 & 2 AND 4" O/C IN ZONE 3
  
 10)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
 *****APPLIES TO MISSING PRODUCT APPROVALS*****
  
 11)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 *****APPLIES TO MISSING PRODUCT APPROVALS*****
  
 12)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED ******NOTE FLORIDA APPROVAL NUMBERS ARE WRITTEN
 AT TOP OF NOA'S*****
  
 13)NO PRODUCT APPROVALS WERE SUBMITTED FOR NANA WALL
 SYSTEM, IMPACT ENTRY DOOR, VINYL SOFFIT, CASTCRETE
 LINTELS, AND SIMPSON TIE CONNECTORS AND STRAPS. IN LUE
 OF PRODUCT APPROVALS STRAP/CONNECTOR FLORIDA APPROVAL
 NUMBERS MAY BE LISTED IN THE SCHEDULE ON THE DRAWINGS
 OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX WITH
 CONNECTORS TO BE USED HIGHLIGHTED
  
 14)ALL WINDOW OPENINGS AND CONFIGURATIONS FOR
 ALTERNATE #1 SHALL BE LISTED AND APPROPRIATE PRODUCT
 APPROVALS SUBMITTED FOR WORK TO BE INCLUDED IN THIS
 PERMIT
  
 15)ALTERNATE #4,BLOCK FENCE/SCREEN WALL ON THE
 PROPERTY LINE REQUIRES AN EASEMENT RELEASE FROM THE
 CITY OF WEST PALM BEACH UTILITIES DEPT.
  
 16)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF THE
 OLD PAGES ONLY FOR REFERENCE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-05-27 Cont ID  
Sent By btrobaug Date 2009-05-27 Time 08:49 Rev Time 0.00
Received By btrobaug Date 2009-05-27 Time 08:30 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-29 Cont ID  
Sent By btrobaug Date 2008-07-29 Time 09:21 Rev Time 0.00
Received By btrobaug Date 2008-07-29 Time 08:04 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-19 Cont ID  
Sent By dpalmer Date 2008-05-19 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2008-05-19 Time 12:07 Sent To M
Notes
2008-05-19 12:07:42** DENIED**
  
 1) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTE WHICH
 REQUESTED THE MANUFACTURES SPECS/CUT SHEETS FOR THE NEW
 PROPOSED ATS TO BE SUBMITTED. THIS WAS INDEED DONE
 HOWEVER THE SUBMITTAL SPECS/CUT SHEETS DO NOT CORRELATE
 WITH THE SUBMITTED INFORMATION ON PLANS. THE PLANS CALL
 FOR SEPARATE EQUIPMENT, DIFFERENT MANUFACTURE ETC.
 90.7, 110.9, 110.3 ETC.
 FBC 106.1.2.
 PLEASE KNOW AT THIS TIME WITH NO INSTALLATION OF A
 GENERATOR NO VIOLATION EXISTS HOWEVER PLEASE KNOW A
 DISCONNECTING MEANS FOR THE GENERATOR FEEDERS MAY BE
 REQUIRED AT THE FUTURE DATE. 225.34.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #5. PLANS NOW
 SHOW SMOKE DETECTORS HOWEVER NO HORN, STROBE DEVICES,
 OR OTHER LOW VOLTAGE FIRE ALARM DEVICES OR SYSTEMS ARE
 SHOWN.
 PLEASE SEE NFPA-72 AS THE DEFINITION OF A SMOKE
 DETECTOR IS ONLY A DEVICE WHICH *DETECTS* AND DOES NOT
 SOUND ANY ALARM. PLEASE SEE THE SAME CODE FOR
 DEFINITION OF *SMOKE ALARMS*.SMOKE ALARMS ARE DEVICES
 WHICH *DETECT* AND *SOUND* AN ALARM.
 ARE THESE DEVICES NOT SMOKE ALARMS?
 PLEASE SEE R313, 11.5.1.1, 11.8.3 NFPA-72 2003.
 PLEASE INDICATE IF NEW TO BE INSTALLED OR ALREADY
 EXISTING.
  
 3) NOTE: PLEASE SEE THE LOADS ON THE SERVICE ARE
 REQUIRED TO BE FIGURED PER 220.83B.
  
 4) NOTE: PLEASE SEE THE CU#2 IS BEING FED FROM NEW
 PANEL B YET THE AHU IS BEING FROM EXISTING PANEL *A*.
 WHEN UNDER FUTURE GENERATOR POWER ONLY HALF OF THIS
 SYSTEM WOULD BE UNDER POWER BEING FED FROM TWO
 SOURCES.
 ** THIS IS GIVEN AS INFORMATION ONLY HOWEVER MAY WANT
 TO REVISE AT THIS TIME.
  
 ** PLANS ARE COMING BACKFOR OTHER CORRECTIONS, PLEASE
 ADDRESS COMMENTS 1-3.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-23 Cont ID  
Sent By dpalmer Date 2008-01-23 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2008-01-23 Time 15:33 Sent To M
Notes
2008-01-23 15:33:55 
  
 ** DENIEDREVIEW **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2007 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 ** PLANS SHOW THE 1999 NFPA-70 AND A 2004 NFPA/LS 101
 WHICH DOES NOT EXIST. PLEASE ADJUST.
 PLEASE ALSO INCLUDE THE ABOVE RELEVANT CODES ON
 ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SUBMIT THE RELEVANT MANUFACTURES
 SPECS/CUT SHEETS FOR THE NEW PROPOSED GENERATOR AND
 TRANSFER SWITCH.
 PLEASE BE SURE THE MANUFACTURES SPECS/CUT SHEETS
 CONTAIN ALL THE MINIMUM CLEARANCE REQUIREMENTS. 110.3,
 90.7.
 FBC ADMIN SECTION 106.1.2
  
 3) NOTE: PLEASE INDICATE IF THE GENERATOR WILL BE A
 SEPARATELY DERIVED SYSTEM. PLEASE SEE
 250.20,250.66,250.30 ETC.
 PLEASE KNOW KOHLER AS STATED ON PLANS COME SHIPPED AS
 SD AND WILL REQUIRE REMOVAL OF BONDING JUMPER IF THIS
 IS NOT GOING TO BE SD.
  
 4) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES FOR
 CU #2 AND #3, DISCONNECTS.
  
 5) NOTE: PLEASE SEE FBC R313 FOR REQUIRED NEW OR
 EXISTING SMOKE ALARMS IN THE EXISTING DWELLING MEETING
 CURRENT NFPA-72 11.5.1.1, AND 11.8.3.
 PLEASE SHOW LAYOUT OF ALL NEW TO BE INSTALLED OR
 EXISTING MEETING CURRENT CODES.
  
 6) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE, THE
 POOL SCOPE OF WORK WILL BE REQUIRED TO BE UNDER A
 SEPARATE PERMIT.
 106.1
  
 7) NOTE: PLEASE CLARIFY HEATING SYSTEMS. LOAD
 CALCULATIONS INDICATE *SPACE HEATERS* HOWEVER SHOULD
 THESE NO BE HEAT-STRIPS? SPACE HEATERS BY DEFINITION
 ARE NOT THE SAME AS CENTRAL HEAT.
 PLEASE ADJUST.
 FBC 106.3.5.4, NEC 424, 422
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52,
 210.52H FOR FOYER/HALL AREA. PLEASE ALSO VERIFY WALL AT
 WHAT APPEARS TO BE HALL AREA #2 ON WALL SPACE ON THE
 BACK/UNDERSIDE OF COUNTER SPACE.
  
 9) NOTE: PLEASE SEE 410.8 FOR MINIMUM CLEARANCES FOR
 LIGHTING FIXTURES. THE TYPE OF FIXTURE NEEDS TO BE
 RELOCATED OR ADJUST TYPE OF FIXTURE.
  
 10) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE(S) FOR
 NEW CIRCUITS ARE TO BE SPECIFIC TO ROOMS AND AREAS IN
 WHICH THEY FEED. PLEASE SEE THE FOLLOWING TEXT WHICH IS
 TAKEN FROM THE CODE COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 AS THE PANEL SCHEDULE MENTIONS GEN LTS AND RECEPTS IN
 MANY LOCATIONS, THESE WOULD BE FOR EXAMPLE: MEDIA ROOM,
 DINING RM LTS, DINING RM RECEPTS ETC.
 IT IS KNOWN TO THIS OFFICE THIS WILL BE REVISED BEFORE
 FINAL.
 FBC 106.1.2, 106.3.5.4,
  
 11) NOTE: PLEASE SEE FOUNTAIN LOCATION AT REAR OF
 DWELLING WHICH IS SWITCHED FROM INSIDE DOES NOT SHOW
 ANY GFI PROTECTION AS REQUIRED PER 210.8A3, 680.56
  
 12) NOTE: PLEASE SEE RISER IS MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM ALL LOCATIONS AFTER THE FIRST
 MEANS OF DISCONNECT PER 250.110, 250.24, 250.6, 250.122
 ETC
  
 13) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS FOR
 FEEDERS FROM GENERATOR TO DWELLING.
 PLEASE SEE 225.31-225.39. PLEASE ALSO SEE 702.11 AS THE
 EXCEPTION OF THE DISCONNECTING MEANSMSUT MEET ALL
 REQUIREMENTS.
  
 14) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM IS
 SHOWING #4 AWG FOR GROUNDING ELECTRODE CONDUCTOR BEING
 PARALLELED WHICH IS NOT PERMITTED. PLEASE SEE 250.66
 FOR SIZING OF THE GROUNDING ELECTRODE CONDUCTOR. PLEASE
 SEE THE RISER ALSO SHOW *STRUCTURAL STEEL* AS PART OF
 THE GROUNDING ELECTRODE SYSTEM. STRUCTURAL STEEL WHERE
 PRESENT IS REQUIRED PER 250.50, HOWEVER PLEASE SEE
 250.50 AS FOOTER STEEL (NEW) IS ALSO REQUIRED.
 PLEASE ADJUST AND INCLUDE ON RISER.
  
 15) NOTE: PLEASE SEE THE SERVICE IS BEING SHOWN AS
 400AMPS YET THE METER CAN IS ONLY SHOWN AS 300AMPS. IS
 THIS A TRUE 300AMP METER CAN?
 PLEASE VERIFY AND ADJUST AS ALL SERVICE EQUIPMENT SHALL
 BE RATED FOR SIZING OF SERVICE.
 110.3, 90.7, 230, ETC
  
 16) NOTE: PLEASE VERIFY CIRCUITING FOR DINING ROOM
 RECEPTACLES PER 210.52B1, 210.11C1 AND 220.53. PLEASE
 SEE LOAD CALCULATIONS INDICATE 3-SMALL APPLIANCE
 CIRCUITS YET THE PANEL SCHEDULES ONLY SHOWS 2. PLEASE
 CLARIFY IF THIS OTHER CIRCUIT AS SHOWN IS THE DINING
 ROOM.
  
 17) NOTE: PLEASE VERIFY THE KW RATING OF THE GENERATOR.
 THE UNIT IS 30KW ON RISER AND 27KW IN NOTES.
 FBC 106.1.2 FOR COORDINATION.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-05-20 Cont ID  
Sent By mperson Date 2008-05-20 Time 10:48 Rev Time 0.00
Received By mperson Date 2008-05-20 Time 10:48 Sent To B
Notes
2008-05-20 10:51:44NOTE: GAS PIPING DESIGN TO BE SUBMITTED AND PERMITTED
 SEPERATELY.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-01-28 Cont ID  
Sent By mperson Date 2008-01-28 Time 13:35 Rev Time 0.00
Received By mperson Date 2008-01-28 Time 13:35 Sent To  
Notes
2008-01-28 14:34:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-3 NATURAL GAS PIPING RISER:
 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 *THE GAS PIPING RISER DOES NOT INDICATE CORRESPONDING
 LENGTHS TO ALL CUT SECTIONS OF PIPE. REFERENCE THE RED
 CIRCLED CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW.
  
 2. SHEET P-3 NATURAL GAS PIPING RISER:
 SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION *401.1 SCOPE.
 *THE GAS PIPING RISER DOES NOT INDICATE THE TYPE OF
 PIPING MATERIAL BEING USED.
  
 3. SHEET P-3 NATURAL GAS PIPING RISER:
 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 * THE ADDED SUM OF THE INDICATED CORRESPONDING LENGTHS
 TO CUT SECTIONS OF PIPING EQUALS 151', HOWEVER NOTES:
 3) DISTANCE IS INDICATING 185'. PLANS AT A MINIMUM
 SHALL BE CORRELATED. PER FBC FUEL GAS SECTION *401.1
 SCOPE.
  
 4. SHEET P-3 NATURAL GAS PIPING RISER:
 INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 * NOTES: 4) DELIVERY PRESSURE PRESSURE IS BEING
 INDICATED AS 0.8 PSI. THIS INDICATED DELIVERY PRESSURE
 IS WRONG FOR NATURAL GAS. FLORIDA PUBLIC UTILTIES CO.
 HAS 0.5, 2 OR 5 PSI DELIVERY PRESSURE.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 *PLEASE SUBMIT TWO COPIES OF MANUFACTURER
 SPECIFICATIONS ON THE PROPOSED GENERATOR INDICATING THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY AS WELL
 AS INDICATING THE MANUFACTURER SETBACK RECOMMENDATIONS
 FROM STRUCTURES.
  
 6. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY CLEARLY
 INDICATING THE LOCATION OF THE PROPOSED GENERATOR
 INDICATING A DIMENTIONS FROM PROPERTY LINES AND
 DISTANCES FROM STRUCTURES. (ZONING APPROVAL REQUIRED
 FOR PROPOSED GENERATOR LOCATION PRIOR TO GAS PERMIT
 BEING ISSUED) PER FBC FUEL GAS SECTION *401.1 SCOPE
  
 7. SHEET P-1 GAS PLAN IS CLEARLY INDICATING WHERE THE
 UNDERGROUND GAS PIPING IS BENEATH THE PROPOSED
 BUILDING. PER FBC FUEL GAS SECTION *404.11 PIPING
 UNDERGROUND BENEATH BUILDINGS.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS
 PROHIBITED EXCEPT WHERE THE PIPING IS ENCASED IN A
 CONDUIT OF WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE
 DESIGNED TO WITHSTAND THE SUPERIMPOSED LOADS. SUCH
 CONDUIT SHALL EXTEND INTO AN OCCUPIABLE PORTION OF THE
 BUILDING AND, AT THE POINT WHERE THE CONDUIT TERMINATES
 IN THE BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE
 GAS PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE
 ENTRANCE OF ANY GAS LEAKAGE. WHERE THE END SEALING IS
 CAPABLE OF WITHSTANDING THE FULL PRESSURE OF THE GAS
 PIPE, THE CONDUIT SHALL BE DESIGNED FOR THE SAME
 PRESSURE AS THE PIPE. SUCH CONDUIT SHALL EXTEND NOT
 LESS THAN 4 INCHES (102 MM) OUTSIDE THE BUILDING, SHALL
 BE VENTED ABOVE GRADE TO THE OUTDOORS AND SHALL BE
 INSTALLED SO AS TO PREVENT THE ENTRANCE OF WATER AND
 INSECTS. THE CONDUIT SHALL BE PROTECTED FROM CORROSION
 IN ACCORDANCE WITH SECTION 404.8 . CLEARLY INDICATE
 THIS REQUIREMENT ON THE RESUBMITTAL. PER FBC FUEL GAS
 SECTION *401.1 SCOPE.
  
 8. SHEET P-3 NATURAL GAS PIPING RISER: NOTES: 1)
 INDICATES THE FOLLOWING "CONTRACTOR TO SUBMIT A PROPER
 GAS PIPING LAYOUT WITH PERMIT APPLICATION". BY THE
 INDICATION OF THIS NOTE, IS IT THE INTENT TO HAVE THE
 PLUMBING OR GAS CONTRACTOR TO SUBMIT THEIR OWN DESIGN
 AT THE TIME OF THE GAS PERMIT APPLICATION? IF THAT IS
 THE INTENT PLEASE REMOVE ALL GAS PIPING DESIGN FROM
 SHEETS P-1 AND P-3 AS WELL AS THE PROPOSED GENERATOR
 AND CLEARLY INDICATE THE GENERATOR AS "FUTURE". PER
 CITY WPB AMENDMENTS SECTION *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION *401.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-05-28 Cont ID  
Sent By lmartine Date 2009-05-27 Time 16:40 Rev Time 0.00
Received By lmartine Date 2009-05-27 Time 16:40 Sent To  
Notes
2009-05-28 16:41:42BEAM REVISION, GAVE TO MCDOUGL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-05-21 Cont ID  
Sent By dpalmer Date 2009-05-21 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2009-05-21 Time 11:56 Sent To B
Notes
2009-05-21 11:56:57TO RMCD DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-05-27 Cont ID  
Sent By btrobaug Date 2009-05-15 Time 08:35 Rev Time 0.00
Received By btrobaug Date 2009-05-15 Time 15:37 Sent To M
Notes
2009-05-15 15:37:55TO MECH BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-05-27 Cont ID  
Sent By btrobaug Date 2009-05-15 Time 08:36 Rev Time 0.00
Received By btrobaug Date 2009-05-15 Time 15:30 Sent To E
Notes
2009-05-21 10:50:28THIS REV IS NOT TO D PALMER, THIS IS TO BILL T DESK.
2009-05-15 15:31:34REV SENT TO D PALMER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-04-08 Cont ID  
Sent By adarroug Date 2009-04-08 Time 11:29 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 11:29 Sent To B
Notes
2009-04-08 11:29:36TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-14 Cont ID  
Sent By adarroug Date 2009-01-14 Time 16:07 Rev Time 0.00
Received By adarroug Date 2009-01-14 Time 16:07 Sent To B
Notes
2009-01-14 16:07:57TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 14:09 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 14:09 Sent To Z
Notes
2008-07-17 14:10:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 10:28 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 10:28 Sent To Z
Notes
2008-05-13 10:30:13TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-28 Cont ID  
Sent By mperson Date 2008-01-28 Time 15:09 Rev Time 0.00
Received By mperson Date 2008-01-18 Time 11:37 Sent To  
Notes
2008-01-18 11:37:15TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-05-29 Cont ID  
Sent By rregueir Date 2009-05-29 Time 11:50 Rev Time 0.00
Received By rregueir Date 2009-05-29 Time 11:50 Sent To PC
Notes
2009-05-29 11:51:03PAGE M1 REVISION 3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By tgordon Date 2008-05-20 Time 08:32 Rev Time 0.30
Received By tgordon Date 2008-05-20 Time 08:32 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-24 Cont ID  
Sent By tgordon Date 2008-01-24 Time 10:33 Rev Time 0.40
Received By tgordon Date 2008-01-24 Time 10:33 Sent To P
Notes
2008-01-24 10:38:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) RETURN AIR MAY NOT BE TAKEN FROM THE KITCHEN, SEE
 2004 FBC/R M1602.2 (4). PLEASE CORRECT.
  
 2) PLEASE SHOW ON THE MECHANICAL PLAN PAGE M-1 THE GAS
 BBQ GRILL AND EXHAUST HOOD LOCATED IN PORCH #2, SEE
 2004 FBC/R M1504.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By mperson Date 2008-05-20 Time 10:44 Rev Time 0.00
Received By mperson Date 2008-05-20 Time 10:43 Sent To G
Notes
2008-05-20 10:47:58****************PROVISO****************
 (A) 604.9 WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-28 Cont ID  
Sent By mperson Date 2008-01-28 Time 10:07 Rev Time 0.00
Received By mperson Date 2008-01-28 Time 10:07 Sent To PC
Notes
2008-01-28 10:43:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 IS INDICATING THE APPLICABLE CODE WRONG
 PLEASE CORRECT THE AMENDMENTS FROM 2006 TO 2007
 REVISIONS. PER FBC PERMIT APPLICATIONS SUBMITTED AFTER
 12/8/06.
  
 2. SHEET P-1 IS INDICATING WH-1 IN THE NEW GARAGE:
 PLEASE INDICATE HOW THE WATER HEATER WILL BE PROTECTED
 FROM VEHICLE DAMAGE BY APPROVED BARRIERS. PER FBC
 MECHANICLA SECTION * 304.4.
  
 3. SHEET P-1 IS INDICATING "EXISTING SANITARY LINE TO
 BE CAPPED OFF @ EXISTING SINK". PER FBC PLUMBING
 SECTION *704.5 DEAD ENDS.
 IN THE INSTALLATION OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 CLEANOUT EXTENSIONS AND APPROVED FUTURE FIXTURE
 DRAINAGE PIPING SHALL NOT BE CONSIDERED AS DEAD ENDS.
  
 4. SHEET P-1 AND P-2 INDICATE THE REQUIRED TWO-WAY
 CLEANOUTS PER FBC PLUMBING SECTION 708.3.5 BUILDING
 DRAIN AND BUILDING SEWER JUNCTION.
  
 5. SHEET P-1 PLEASE INDICATE THE LOCATION OF THE
 REQUIRED (EXISTING OR NEW), 1 AUTOMATIC CLOTHES WASHER
 CONNECTION. PER FBC PLUMBING TABLE 403.1 (R-3) ONE AND
 TWO FAMILY DWELLINGS.
  
 6. NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSES,
 THE POOL/SPA SCOPE OF WORK WILL BE REQUIRED TO BE UNDER
 A SEPERATE PERMIT 106.1.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2008-08-11 Cont ID  
Sent By bpowell Date 2008-08-11 Time 13:51 Rev Time 0.00
Received By bpowell Date 2008-08-11 Time 13:51 Sent To  
Notes
2008-08-11 13:54:001.THE PAVERS THAT ARE PROVIDED AS THE DRIVEWAY ARE
 NOT ALLOWED TO BE SEALED AND SHALL BE SET IN SAND.
  
 IF YOU HAVE ANY QUESTIONS OR COMMENTS CONTACT: BOBBY
 POWELL JR., [email protected], (561) 822-1449

Review Stop Z ZONING
Rev No 2 Status F Date 2008-05-14 Cont ID  
Sent By choops Date 2008-05-14 Time 13:39 Rev Time 0.00
Received By choops Date 2008-05-14 Time 13:39 Sent To E
Notes
2008-05-14 13:40:37***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1) REMOVAL/ALTERATION OF LANDSCAPING WILL REQUIRE A
 TREE ALTERATION PERMIT FROM THE CITY'S PLANNING AND
 ZONING DEPARTMENT.SEE LANDSCAPE PLANNER, ROBERT
 KUSSNER, 561-822-1435.ROBERT REPORTS NO RECORD OF A
 TREE ALTERATION PERMIT FOR THIS PROPERTY.
  
 3) THE PROVIDED SITE PLAN CONTAINS A NEW VINYL
 COATED C/L FENCE TO BE INSTALLED AT THE EAST SIDE OF
 THE PROPERTY, THIS FENCE IS NOT INCLUDED UNDER THE
 CURRENT APPROVAL FROM THE CITY'S DEPARTMENT OF PUBLIC
 UTILITIES.AN APPROVED EASEMENT CONSENT FORM FROM THE
 CITY OF WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES
 (1ST FLOOR CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
  
 NOTE:A RIGHT-OF-WAY PERMIT SHALL BE REQUIRED FOR THE
 PROPOSED APPROACH, SEE ENGINEERING DEPARTMENT, WINDEL
 PALMER, 561-494-1040.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-22 Cont ID  
Sent By choops Date 2008-01-22 Time 11:10 Rev Time 0.00
Received By choops Date 2008-01-22 Time 11:09 Sent To B
Notes
2008-01-22 11:15:11***FAILED***
  
  
 1)REMOVAL/ALTERATION OF LANDSCAPING WILL REQUIRE A
 TREE ALTERATION PERMIT FROM THE CITY'S PLANNING AND
 ZONING DEPARTMENT.SEE LANDSCAPE PLANNER, ROBERT
 KUSSNER, 561-822-1435.
  
 2)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.SITE
 PLAN SHOWS REMOVAL OF LANDSCAPING, HOWEVER, A LANDSCAPE
 PLAN SHOWING COMPLIANCE WITH SECTION 94-442 AND 94-445
 OF THE ZLDRS MUST BE SUBMITTED.
  
 3)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
 4)INDICATE CHIMNEY PROTRUSION FROM REAR WALL OF
 STRUCTURE.PURSUANT TO SECTION 94-305 OF THE ZLDRS:
 CHIMNEYS MAY PROJECT NO MORE THAN 18" INTO A REQUIRED
 SETBACK.
  
 5)INDICATE ALL ROOF OVERHANG DIMENSIONS.PURSUANT
 TO SECTION 94-305 OF THE ZLDRS:ROOF OVERHANGS MAY NOT
 PROJECT MORE THAN 3' INTO A REQUIRED SETBACK.
  
 6)INDICATE HEIGHT DIMENSIONS FROM GRADE TO THE
 UPPERMOST POINT OF THE PROPOSED CHIMNEY.
  
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720