 |
Plan Review Details - Permit 08010376
Plan Review Stops For Permit 08010376 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-07-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-07-09 |
Time |
08:54 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2008-07-09 |
Time |
08:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-04-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-04-30 |
Time |
10:20 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2008-04-30 |
Time |
10:20 |
Sent To |
|
|
Notes |
2008-04-30 10:32:07 | BUILDING PLAN REVIEW | | PERMIT: 08010376 | | ADD: 6901 OKEECHOBEE BLVD. # D-1 | | CONT: PUZZITOLLO BUILDERS | | TEL: (561)718-4176 | | JAN.27, 2008 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | | | 1A)INFORMATIONAL, WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 1B)INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS, | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | SUBMITTALS FOR REVIEW FOR PERMIT. | | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF | | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A | | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID | | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* | | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH | | ADMINISTRATIVE CODE. | | | | 1C) INFORMATION, 106.1.1* W.P.B. ADMINISTRATIVE | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. | | | | 1D ) INFORMATIONAL, FL S S 713.13NOTICE OF | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | INSPECTION. | | | | 1E) COMPLIED. | | | | 2 A-B) COMPLIED. | | 2C) PLEASE ALSO INDICATE PLANS DESIGNED TO THE 2004 FBC | | EXISTING BUILDING CODE WITH 2007 SUPPLEMENTS, NOTE THE | | LEVEL OF ALTERATION. | | 2D-E)COMPLIED.T | | | | 3) COMPLIED. | | | | 4) 2ND REQUEST, THE TWO HANDICAPPED RESTROOMS INDICATE | | THE REQUIRED TURNING RADIUS BUT THE CLEAR FLOOR SPACE | | FOR THE LAVATORY HAS NOT BEEN PROVIDED. 11-4.19.3. | | PLEASE ALSO SEE SECTION 11-4.22.2. | | 11-4.19.3 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY | | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE | | PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD | | APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR | | OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM | | OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE | | FIGURE 32 ). | | 11-4.22.2 DOORS. | | (1)ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL | | COMPLY WITH SECTION 11-4.13 . DOORS SHALL NOT SWING | | INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | 5) COMPLIED. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-01-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-01-27 |
Time |
18:23 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2008-01-27 |
Time |
18:23 |
Sent To |
|
|
Notes |
2008-01-27 18:49:31 | BUILDING PLAN REVIEW | | PERMIT: 08010376 | | ADD: 6901 OKEECHOBEE BLVD. # D-1 | | CONT: PUZZITOLLO BUILDERS | | TEL: (561)718-4176 | | JAN.27, 2008 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | REVIEW FOR PERMIT. | | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF | | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A | | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID | | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* | | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH | | ADMINISTRATIVE CODE. | | | | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN | | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY | | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE | | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS | | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. | | | | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE2007 SUPPLEMENTS. | | | | 2)PLANS ARE MISSING CODE SUMMARY INFORMATION,110.2* | | W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS | | REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. | | C) PLEASE ALSO INDICATE PLANS DESIGNED TO THE 2004 FBC | | EXISTING BUILDING CODE WITH 2007 SUPPLEMENTS, NOTE THE | | LEVEL OF ALTERATION. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) | | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | | 3)SHEET A-3 INDICATES CHAIRS AND TABLES ALONG THE | | NORTH WALL OF THE TENANT SPACE WHERE AS THE FLOOR PLAN | | DOES NOT INDICATE CHAIRS AND TABLES IN THIS LAYOUT, | | PLEASE PROVIDE SO THE EGRESS PATH WILL BE ABLE TO BE | | CHECKED FOR CODE COMPLIANCE. | | | | 4) THE TWO HANDICAPPED RESTROOMS INDICATE THE REQUIRED | | TURNING RADIUS BUT THE CLEAR FLOOR SPACE FOR THE | | LAVATORY HAS NOT BEEN PROVIDED. 11-4.19.3. | | | | 5) PLEASE SEE ELECTRICAL COMMENTS REGARDING LICENSING | | LAWS FOR ARCHITECTS AND INTERIOR DESIGNERS.FL S S | | 481.221/ $71.023 AND FLORIDA ADMINISTRATIVE CODE | | 61G1-16.004 & 61G15-23.002. | | | | | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-08-26 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-08-26 |
Time |
11:09 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-07-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-07-07 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-07-07 |
Time |
10:37 |
Sent To |
|
|
Notes |
2008-07-07 10:38:42 | ** REDLINED PLANS. | | | | | | WILL NEED REVISED ACTUAL FIXTURE LEGENDBEFORE FINAL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-04-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-04-28 |
Time |
17:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-04-28 |
Time |
17:01 |
Sent To |
|
|
Notes |
2008-04-28 17:02:11 | ** DENIED 2ND REVIEW ** | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING. | | ** AS NOTED ON PREVIOUS REVIEW THERE MAY CERTAINLY BE | | NEW COMMENTS ONCE ALL INFORMATION IS SUBMITTED FOR | | REVIEW. | | | | 1) NOTE: PLEASE SEE NO LIGHTING CONTROLS IN COMPLIANCE | | WITH FBC 13-415.1.ABC.1.1, .1.2 AND.1.3. | | PLEASE KNOW THIS BUILDING IS OVER 5K SQ FT AND IS | | REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS FOR ALL | | LIGHTING. | | AS NO SYSTEM OR LIGHTING CONTROLS DEVICES ARE SHOWN AT | | THIS TIME IN COMPLIANCE WITH THE FLORIDA BUILDING CODE | | CHAPTER 13 SECTIONS AS GIVEN ABOVE ARE NOT SHOWN NO | | REVIEW OF THESE ITEMS CAN BE DONE AT THIS TIME. | | | | 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | CALCULATIONS AS REQUESTED ON PREVIOUS REVIEW IN | | COMPLIANCE WITH FBC 13-415.2.ABC.1.1, .1.2. | | PLEASE KNOW ALSO AS MENTIONED ABOVE MINIMUM CODE | | COMPLIANCE IS NOT YET SHOWN. | | | | 3) NOTE: PLEASE SEE NOW PLANS SHOW CIRCUITING ETC | | HOWEVER CIRCUITS ON PANEL SCHEDULE NEED TO BE SPECIFIC | | TO AREAS AND ITEMS IN WHICH THEY FEED. | | 408.4 | | | | 4) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER | | 210.62 | | | | 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER NEC | | 220. | | PLEASE SEE LOADS FOR SHOW WINDOWS PER 220.43A | | PLEASE SEE LOADS FOR TRACK LIGHTING NEED TO BE SHOWN | | PER 220.43B. | | PLEASE SEE NO CONTINUOUS LOADS SHOWN AT 125% PER 215.3, | | 230.42 ETC. | | | | 6) NOTE: PLEASE SEE THE OWNER INFORMATION ON THE PERMIT | | APPLICATION NEEDS TO BE UPDATED AS THE OWNER IS NOT | | JOHNNY'S DREAM INC. THIS IS THE TENANTS NAME AND OWNER | | OF SAID BUILDING IS ATTACHED TO ELECTRICAL NOTES FOR | | INFORMATION. PLEASE ADJUST. | | | | 7) NOTE: PLEASE INDICATE THE ELECTRICAL AND RELEVANT | | CODE ON ELECTRICAL SHEETS AS PREVIOUSLY NOTED. | | 2005 NFPA-70 | | 2003 NFPA-101 | | 2002 NFPA-70 | | | | 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE | | COMPLIANCE. | | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | PLANS MAY BE RETAINED BY THIS OFFICE. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-01-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-23 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-23 |
Time |
11:44 |
Sent To |
|
|
Notes |
2008-01-23 11:44:16 | | | | | ** DENIEDREVIEW ** | | | | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | AFFECT DESIGNS FOR ALL TRADES. | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | REVIEWER AT A MINIMUM. | | 2004 FBC W/ 2007 REVISIONS | | 2005 NFPA-70 | | 2002 NFPA-72 | | 2003 NFPA-101 | | | | ** PLANS DO NOT CONTAIN ANY MINIMUM CODES FOR REQUIRED | | DESIGNS. | | | | 2) NOTE: PLEASE SEE PLANS SUBMITTED ARE MISSING | | COMPLETED INFORMATION ON TITLE BLOCKS FOR DESIGN FIRM | | AND PROFESSIONAL(S) PER FLORIDA ADMINISTRATIVE CODE | | 61G1-16.004, 61G15-23.002, AND FLORIDA STATUTES | | 481.219, 471.023. | | ** PLEASE KNOW AS NO INFORMATION WAS SHOWN FOR SECTIONS | | ABOVE, NO REVIEW COULD BE DONE BASED ON ANY DESIGN | | PROFESSIONAL. | | | | 3) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND | | SEALED AS REQUIRED PER FS 481.221, 471.025. | | ** NO REVIEW OF STATUTORY REQUIREMENTS COULD BE DONE. | | | | 4) NOTE: PLEASE BE SURE THE SUITE/UNIT NUMBER IS PLACED | | ON TITLE BLOCKS. | | FAC 61G1-16.004, 61G15-23.002, FBC ADMIN SECTION, | | 106.5, 106.1.2 ETC | | | | 5) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS WITH | | MINIMUM COMPLIANCE WITH THE 2005 NFPA-70 (NATIONAL | | ELECTRICAL CODE). | | PLEASE SHOW ALL CIRCUITING ON PLANS AND CORRELATE WITH | | PANEL SCHEDULE(S), BRANCH CIRCUITS, OVER CURRENT | | PROTECTION DEVICES, MINIMUM CIRCUITS, LOAD | | CALCULATIONS, SIGN CIRCUIT(S), SHOW WINDOWS ETC ETC. | | ** PLEASE KNOW AS PLANS DO NOT CONTAIN ANY MINIMUM | | ELECTRICAL REQUIRED INFORMATION OR DESIGN PER THE | | NATIONAL ELECTRICAL CODE, NO REVIEW FOR ANY OF THESE | | COULD BE DONE AT THIS TIME. | | THERE MAY CERTAINLY BE NEW COMMENTS UPON THE NEXT | | REVIEW WHICH COULD NOT MADE AT THIS TIME. | | PLEASE SEE ALL OF THE 2005 NEC. | | 210, 230, 240, 220, 310.16, 408.4, 250, 600.5, ETC | | THERE ARE TOO MANY CODE SECTIONS TO MENTION. | | | | 6) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2 FOR | | MINIMUM COMPLIANCE FOR LIGHTING PERFORMANCE | | CALCULATIONS TO BE SUBMITTED. | | PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS | | MECHANICAL REVIEW WHICH WILL AFFECT CHAPTER 13 | | REQUIREMENTS. | | | | 7) NOTE: PLEASE SUBMIT MINIMUM COMPLIANCE WITH FBC | | CHAPTER 13 , 13-415.1.ABC.1.1, .1.2 AND .1.3. | | PLEASE KNOW AS NO MINIMUM DESIGN FOR CODE COMPLIANCE | | WAS SHOWN ON PLANS, NO REVIEW OF ANY OF THESE ITEMS | | COULD BE DONE AT THIS TIME. | | | | ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET | | DESIGNED OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE | | NEW COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE | | AT THIS TIME. | | | | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY | | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR | | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN | | CONTACTING THIS REVIEWER. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-07-16 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-07-16 |
Time |
13:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2008-05-14 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-05-14 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-05-14 |
Time |
13:57 |
Sent To |
|
|
Notes |
2008-05-14 14:01:15 | ***DENIED*** | | | | 1) OK | | | | 2) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | 3) PLANS INDICATE AN EXISTING FIRE ALARM SYSTEM. AS PER | | THE FIRST REVIEW, IS THERE AN EXISTING FIRE SPRINKLER | | SYSTEM? | | | | 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-02-21 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-02-21 |
Time |
13:59 |
Sent To |
|
|
Notes |
2008-02-21 14:22:29 | ***DENIED*** | | | | 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS #2 & 3. | | | | 2) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED. | | | | 3) ARE THERE EXISTING FIRE SPRINKLER AND FIRE ALARM | | SYSTEMS AS PART OF THIS SPACE? | | | | 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-08-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-12 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-08-12 |
Time |
16:24 |
Sent To |
E |
|
Notes |
2008-08-12 16:24:42 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-07-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-22 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-22 |
Time |
09:50 |
Sent To |
P |
|
Notes |
2008-07-22 09:50:33 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-06-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-13 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-13 |
Time |
10:27 |
Sent To |
|
|
Notes |
2008-06-13 10:31:00 | TO "COMM" BD#58 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-04-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-21 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-21 |
Time |
12:29 |
Sent To |
|
|
Notes |
2008-04-21 12:31:50 | TO "COMM" BD#30 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-02-21 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-01-17 |
Time |
09:40 |
Sent To |
|
|
Notes |
2008-01-17 09:40:39 | TO "COMM" BD#31 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-06-23 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-06-23 |
Time |
14:19 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-06-23 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-05-01 |
Time |
11:28 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-05-01 |
Time |
11:28 |
Sent To |
|
|
Notes |
2008-05-01 11:35:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | | | 1) PLANS PAGE E-1.0 SHOWS ONE NEW SUPPLY AND TWO NEW | | RETURN AIR GRILL. AS REQUESTED IN LAST REVIEW1-28-08 | | NOTE #1. PLEASE SHOW ON PLAN ALL NEW GRILL SIZES, DUCT | | (FLEX) SIZES AND CFM'S AT NEW SUPPLY AIR GRILLS. SEE | | 2004 FBC 106.3.5. | | | | 2) AS REQUESTED IN LAST REVIEW 1-28-08 NOTE #3. PLEASE | | ADD OUTSIDE AIR CALCULATIONS TO PLANS AND PROVIDE | | OUTSIDE AIR TO SPACE, SEE 2004 FBC/M 401.2. | | | | 3) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR | | TIMES THE FEE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-01-28 |
Time |
13:38 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2008-01-28 |
Time |
13:38 |
Sent To |
|
|
Notes |
2008-01-28 13:54:10 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLANS PAGE A-2 SHOWS ONE NEW SUPPLY AND RETURN AIR | | GRILL. PLEASE SHOW ON PLAN ALL NEW GRILL SIZES, DUCT | | (FLEX) SIZES AND CFM'S AT NEW SUPPLY AIR GRILLS. SEE | | 2004 FBC 106.3.5. | | | | 2) THE RESTROOMS REQUIRE EXHAUST FANS, SEE 2004 FBC/M | | 403.2. PLEASE CORRECT, AND LIST AS NEW OR EXISTING. | | | | 3) PLEASE ADD OUTSIDE AIR CALCULATIONS TO PLANS AND | | PROVIDE OUTSIDE AIR TO SPACE, SEE 2004 FBC/M 401.2. | | | | 4) PLEASE SHOW ALL MECHANICAL WORK TO BE DONE AND LIST | | AS NEW OR EXISTING, SEE 2004 FBC 106.3.5. | | | | 5) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2008-08-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-04 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-04 |
Time |
15:23 |
Sent To |
|
|
Notes |
2008-08-04 15:24:36 | REVISION OK--SHT PB-1.0--ADDED GREASE LINE & | | GREASE INTERCEPTOR. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2008-07-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-07-16 |
Time |
13:49 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-07-14 |
Time |
14:02 |
Sent To |
|
|
Notes |
2008-07-16 13:52:36 | | | | | PASSED/PROVISO | | | | A GREASE INTERCEPTOR IS REQUIRED FOR ALL FIXTURES | | EXCEPT THE TOILET ROOMS, WASH MACHINE AND EXISTING HAND | | SINK. ARTICLE III SECTION 90-124(7).A REVISION IS | | REQUIRED SHOWING THE GREASE INTERCEPTOR, (750 GAL), AND | | THE GREASE SYSTEM AS WELL AS THE RISER DIAGRAM. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2008-04-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-04-28 |
Time |
12:36 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-04-28 |
Time |
12:36 |
Sent To |
|
|
Notes |
2008-04-28 12:43:38 | DENIED | | REFERENCE: FBC-2004 | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | | | 5. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOWING | | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 | | WITH ALL SUBSECTIONS. | | ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED. | | | | 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING | | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS | | PLUS SECTION 11-4.3.1(10)(A) PROVISIONS FOR THOSE WHO | | HAVE DIFFICULTY BENDING OR STOOPING. | | ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED. | | | | 7. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE SANITARY AND | | WATER AS WELL AS A PLAN VIEW OF EACH SYSTEM PIPING PER | | SECTION 106.3.5.1.3(3)(4)(6)(10)(13). SHOW ALL PIPE | | SIZES, TRAPS & VENTS FOR THE SANITARY SYSTEM, AND ALL | | THE PIPE SIZES, VALVES & WATER HAMMER ARRESTORS, (WHERE | | REQUIRED BY SECTION 604.9), FOR THE WATER SYSTEM. | | ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED FOR THE | | WATER RISER DIAGRAM. | | | | 8. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, | | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE | | THROUGHAN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. | | SECTION 802.1.1. | | ****NO COMMENT RESPONSE, AND THE FLOOR SINKS ON THE | | RISER DIAGRAM DO NOT RELFECT THE FLOOR DRAINS SHOWN ON | | THE FLOOR PLAN. PLEASE SHOW THE FLOOR SINKS ON THE | | FLOOR PLAN.--ALSO THE 2" FLOOR SINK P-009 SHOWN ON | | THE SANITARY RISER DIAGRAM IS NOT INDICATED ON THE | | FLOOR PLAN. PLEASE CORRELATE RISER & FLOOR PLAN. | | SECTION 106.1.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | ****NO RESPONSE TO THE TRANSMITTAL LETTER WITH A | | COMMENT RESPONSE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-02-12 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-02-12 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-02-12 |
Time |
15:39 |
Sent To |
|
|
Notes |
2008-02-12 17:24:22 | DENIED | | REFERENCE: FBC-2004 | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. INDICATE THAT THE PLANS HAVE BEEN DESIGNED TO THE | | CURRENT CODE, FBC-2004 W/2007 REVISIONS. PLANS SHALL BE | | DESIGNED TO CODES IN EFFECT. SECTION 110.2 | | | | 2. PLANS SHALL BE SIGNED, SEALED & DATED AS REQUIRED | | PER FS 481.221 | | | | 3. INFORMATION IS MISSING FOR THE TITLE BLOCKS OF EACH | | SHEET AS REQUIRED BY FAC 61G1-16.004 & FS 481.219, | | 481.2055. | | | | 4. SUITE, UNIT OR SPACE NUMBER REQUIRED IN THE TITLE | | BLOCK INFORMATION FOR THE ADDRESS. SECTION 106.1.2. | | | | 5. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOWING | | COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22 | | WITH ALL SUBSECTIONS. | | | | 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING | | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS | | PLUS SECTION 11-4.3.1(10)(A) PROVISIONS FOR THOSE WHO | | HAVE DIFFICULTY BENDING OR STOOPING. | | | | 7. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE SANITARY AND | | WATER AS WELL AS A PLAN VIEW OF EACH SYSTEM PIPING PER | | SECTION 106.3.5.1.3(3)(4)(6)(10)(13). SHOW ALL PIPE | | SIZES, TRAPS & VENTS FOR THE SANITARY SYSTEM, AND ALL | | THE PIPE SIZES, VALVES & WATER HAMMER ARRESTORS, (WHERE | | REQUIRED BY SECTION 604.9), FOR THE WATER SYSTEM. | | | | 8. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, | | PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE | | THROUGHAN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. | | SECTION 802.1.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2008-06-18 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2008-06-18 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2008-06-18 |
Time |
10:40 |
Sent To |
|
|
Notes |
2008-06-18 10:41:05 | *ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE | | VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | IMPROVEMENT VALUE. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |