Plan Review Details - Permit 08010376
Plan Review Stops For Permit 08010376
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-09 Cont ID  
Sent By jwitmer Date 2008-07-09 Time 08:54 Rev Time 1.11
Received By jwitmer Date 2008-07-09 Time 08:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-30 Cont ID  
Sent By jwitmer Date 2008-04-30 Time 10:20 Rev Time 2.22
Received By jwitmer Date 2008-04-30 Time 10:20 Sent To  
Notes
2008-04-30 10:32:07BUILDING PLAN REVIEW
 PERMIT: 08010376
 ADD: 6901 OKEECHOBEE BLVD. # D-1
 CONT: PUZZITOLLO BUILDERS
 TEL: (561)718-4176
 JAN.27, 2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL, WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) INFORMATION, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL, FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) COMPLIED.
  
 2 A-B) COMPLIED.
 2C) PLEASE ALSO INDICATE PLANS DESIGNED TO THE 2004 FBC
 EXISTING BUILDING CODE WITH 2007 SUPPLEMENTS, NOTE THE
 LEVEL OF ALTERATION.
 2D-E)COMPLIED.T
  
 3) COMPLIED.
  
 4) 2ND REQUEST, THE TWO HANDICAPPED RESTROOMS INDICATE
 THE REQUIRED TURNING RADIUS BUT THE CLEAR FLOOR SPACE
 FOR THE LAVATORY HAS NOT BEEN PROVIDED. 11-4.19.3.
 PLEASE ALSO SEE SECTION 11-4.22.2.
 11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 32 ).
 11-4.22.2 DOORS.
 (1)ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL
 COMPLY WITH SECTION 11-4.13 . DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
 5) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-27 Cont ID  
Sent By jwitmer Date 2008-01-27 Time 18:23 Rev Time 2.22
Received By jwitmer Date 2008-01-27 Time 18:23 Sent To  
Notes
2008-01-27 18:49:31BUILDING PLAN REVIEW
 PERMIT: 08010376
 ADD: 6901 OKEECHOBEE BLVD. # D-1
 CONT: PUZZITOLLO BUILDERS
 TEL: (561)718-4176
 JAN.27, 2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2)PLANS ARE MISSING CODE SUMMARY INFORMATION,110.2*
 W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) PLEASE ALSO INDICATE PLANS DESIGNED TO THE 2004 FBC
 EXISTING BUILDING CODE WITH 2007 SUPPLEMENTS, NOTE THE
 LEVEL OF ALTERATION.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 3)SHEET A-3 INDICATES CHAIRS AND TABLES ALONG THE
 NORTH WALL OF THE TENANT SPACE WHERE AS THE FLOOR PLAN
 DOES NOT INDICATE CHAIRS AND TABLES IN THIS LAYOUT,
 PLEASE PROVIDE SO THE EGRESS PATH WILL BE ABLE TO BE
 CHECKED FOR CODE COMPLIANCE.
  
 4) THE TWO HANDICAPPED RESTROOMS INDICATE THE REQUIRED
 TURNING RADIUS BUT THE CLEAR FLOOR SPACE FOR THE
 LAVATORY HAS NOT BEEN PROVIDED. 11-4.19.3.
  
 5) PLEASE SEE ELECTRICAL COMMENTS REGARDING LICENSING
 LAWS FOR ARCHITECTS AND INTERIOR DESIGNERS.FL S S
 481.221/ $71.023 AND FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 & 61G15-23.002.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-08-26 Cont ID  
Sent By btrobaug Date 2008-08-26 Time 11:19 Rev Time 0.00
Received By btrobaug Date 2008-08-26 Time 11:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-07 Cont ID  
Sent By dpalmer Date 2008-07-07 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2008-07-07 Time 10:37 Sent To  
Notes
2008-07-07 10:38:42** REDLINED PLANS.
  
  
 WILL NEED REVISED ACTUAL FIXTURE LEGENDBEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-28 Cont ID  
Sent By dpalmer Date 2008-04-28 Time 17:01 Rev Time 0.00
Received By dpalmer Date 2008-04-28 Time 17:01 Sent To  
Notes
2008-04-28 17:02:11** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 ** AS NOTED ON PREVIOUS REVIEW THERE MAY CERTAINLY BE
 NEW COMMENTS ONCE ALL INFORMATION IS SUBMITTED FOR
 REVIEW.
  
 1) NOTE: PLEASE SEE NO LIGHTING CONTROLS IN COMPLIANCE
 WITH FBC 13-415.1.ABC.1.1, .1.2 AND.1.3.
 PLEASE KNOW THIS BUILDING IS OVER 5K SQ FT AND IS
 REQUIRED TO CONTAIN AUTOMATED LIGHTING CONTROLS FOR ALL
 LIGHTING.
 AS NO SYSTEM OR LIGHTING CONTROLS DEVICES ARE SHOWN AT
 THIS TIME IN COMPLIANCE WITH THE FLORIDA BUILDING CODE
 CHAPTER 13 SECTIONS AS GIVEN ABOVE ARE NOT SHOWN NO
 REVIEW OF THESE ITEMS CAN BE DONE AT THIS TIME.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS AS REQUESTED ON PREVIOUS REVIEW IN
 COMPLIANCE WITH FBC 13-415.2.ABC.1.1, .1.2.
 PLEASE KNOW ALSO AS MENTIONED ABOVE MINIMUM CODE
 COMPLIANCE IS NOT YET SHOWN.
  
 3) NOTE: PLEASE SEE NOW PLANS SHOW CIRCUITING ETC
 HOWEVER CIRCUITS ON PANEL SCHEDULE NEED TO BE SPECIFIC
 TO AREAS AND ITEMS IN WHICH THEY FEED.
 408.4
  
 4) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62
  
 5) NOTE: PLEASE SEE MISSING LOAD CALCULATIONS PER NEC
 220.
 PLEASE SEE LOADS FOR SHOW WINDOWS PER 220.43A
 PLEASE SEE LOADS FOR TRACK LIGHTING NEED TO BE SHOWN
 PER 220.43B.
 PLEASE SEE NO CONTINUOUS LOADS SHOWN AT 125% PER 215.3,
 230.42 ETC.
  
 6) NOTE: PLEASE SEE THE OWNER INFORMATION ON THE PERMIT
 APPLICATION NEEDS TO BE UPDATED AS THE OWNER IS NOT
 JOHNNY'S DREAM INC. THIS IS THE TENANTS NAME AND OWNER
 OF SAID BUILDING IS ATTACHED TO ELECTRICAL NOTES FOR
 INFORMATION. PLEASE ADJUST.
  
 7) NOTE: PLEASE INDICATE THE ELECTRICAL AND RELEVANT
 CODE ON ELECTRICAL SHEETS AS PREVIOUSLY NOTED.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-70
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLANS MAY BE RETAINED BY THIS OFFICE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-23 Cont ID  
Sent By dpalmer Date 2008-01-23 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2008-01-23 Time 11:44 Sent To  
Notes
2008-01-23 11:44:16 
  
 ** DENIEDREVIEW **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2007 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2007 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLANS DO NOT CONTAIN ANY MINIMUM CODES FOR REQUIRED
 DESIGNS.
  
 2) NOTE: PLEASE SEE PLANS SUBMITTED ARE MISSING
 COMPLETED INFORMATION ON TITLE BLOCKS FOR DESIGN FIRM
 AND PROFESSIONAL(S) PER FLORIDA ADMINISTRATIVE CODE
 61G1-16.004, 61G15-23.002, AND FLORIDA STATUTES
 481.219, 471.023.
 ** PLEASE KNOW AS NO INFORMATION WAS SHOWN FOR SECTIONS
 ABOVE, NO REVIEW COULD BE DONE BASED ON ANY DESIGN
 PROFESSIONAL.
  
 3) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND
 SEALED AS REQUIRED PER FS 481.221, 471.025.
 ** NO REVIEW OF STATUTORY REQUIREMENTS COULD BE DONE.
  
 4) NOTE: PLEASE BE SURE THE SUITE/UNIT NUMBER IS PLACED
 ON TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002, FBC ADMIN SECTION,
 106.5, 106.1.2 ETC
  
 5) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS WITH
 MINIMUM COMPLIANCE WITH THE 2005 NFPA-70 (NATIONAL
 ELECTRICAL CODE).
 PLEASE SHOW ALL CIRCUITING ON PLANS AND CORRELATE WITH
 PANEL SCHEDULE(S), BRANCH CIRCUITS, OVER CURRENT
 PROTECTION DEVICES, MINIMUM CIRCUITS, LOAD
 CALCULATIONS, SIGN CIRCUIT(S), SHOW WINDOWS ETC ETC.
 ** PLEASE KNOW AS PLANS DO NOT CONTAIN ANY MINIMUM
 ELECTRICAL REQUIRED INFORMATION OR DESIGN PER THE
 NATIONAL ELECTRICAL CODE, NO REVIEW FOR ANY OF THESE
 COULD BE DONE AT THIS TIME.
 THERE MAY CERTAINLY BE NEW COMMENTS UPON THE NEXT
 REVIEW WHICH COULD NOT MADE AT THIS TIME.
 PLEASE SEE ALL OF THE 2005 NEC.
 210, 230, 240, 220, 310.16, 408.4, 250, 600.5, ETC
 THERE ARE TOO MANY CODE SECTIONS TO MENTION.
  
 6) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.2 FOR
 MINIMUM COMPLIANCE FOR LIGHTING PERFORMANCE
 CALCULATIONS TO BE SUBMITTED.
 PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS
 MECHANICAL REVIEW WHICH WILL AFFECT CHAPTER 13
 REQUIREMENTS.
  
 7) NOTE: PLEASE SUBMIT MINIMUM COMPLIANCE WITH FBC
 CHAPTER 13 , 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE KNOW AS NO MINIMUM DESIGN FOR CODE COMPLIANCE
 WAS SHOWN ON PLANS, NO REVIEW OF ANY OF THESE ITEMS
 COULD BE DONE AT THIS TIME.
  
 ** PLEASE KNOW AS THERE IS MUCH INFORMATION NOT YET
 DESIGNED OR SUBMITTED FOR REVIEW THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-16 Cont ID  
Sent By mwennerg Date 2008-07-16 Time 13:47 Rev Time 0.00
Received By mwennerg Date 2008-07-16 Time 13:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-14 Cont ID  
Sent By mwennerg Date 2008-05-14 Time 13:57 Rev Time 0.00
Received By mwennerg Date 2008-05-14 Time 13:57 Sent To  
Notes
2008-05-14 14:01:15***DENIED***
  
 1) OK
  
 2) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) PLANS INDICATE AN EXISTING FIRE ALARM SYSTEM. AS PER
 THE FIRST REVIEW, IS THERE AN EXISTING FIRE SPRINKLER
 SYSTEM?
  
 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-21 Cont ID  
Sent By mwennerg Date 2008-02-21 Time 13:59 Rev Time 0.00
Received By mwennerg Date 2008-02-21 Time 13:59 Sent To  
Notes
2008-02-21 14:22:29***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS #2 & 3.
  
 2) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) ARE THERE EXISTING FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS AS PART OF THIS SPACE?
  
 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 5) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 16:24 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 16:24 Sent To E
Notes
2008-08-12 16:24:42TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 09:50 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 09:50 Sent To P
Notes
2008-07-22 09:50:33TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 10:27 Rev Time 0.00
Received By adarroug Date 2008-06-13 Time 10:27 Sent To  
Notes
2008-06-13 10:31:00TO "COMM" BD#58

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 12:29 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 12:29 Sent To  
Notes
2008-04-21 12:31:50TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-21 Cont ID  
Sent By mwennerg Date 2008-02-21 Time 14:27 Rev Time 0.00
Received By mwennerg Date 2008-01-17 Time 09:40 Sent To  
Notes
2008-01-17 09:40:39TO "COMM" BD#31

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-23 Cont ID  
Sent By tgordon Date 2008-06-23 Time 14:19 Rev Time 0.30
Received By tgordon Date 2008-06-23 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-01 Cont ID  
Sent By tgordon Date 2008-05-01 Time 11:28 Rev Time 0.30
Received By tgordon Date 2008-05-01 Time 11:28 Sent To  
Notes
2008-05-01 11:35:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLANS PAGE E-1.0 SHOWS ONE NEW SUPPLY AND TWO NEW
 RETURN AIR GRILL. AS REQUESTED IN LAST REVIEW1-28-08
 NOTE #1. PLEASE SHOW ON PLAN ALL NEW GRILL SIZES, DUCT
 (FLEX) SIZES AND CFM'S AT NEW SUPPLY AIR GRILLS. SEE
 2004 FBC 106.3.5.
  
 2) AS REQUESTED IN LAST REVIEW 1-28-08 NOTE #3. PLEASE
 ADD OUTSIDE AIR CALCULATIONS TO PLANS AND PROVIDE
 OUTSIDE AIR TO SPACE, SEE 2004 FBC/M 401.2.
  
 3) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-28 Cont ID  
Sent By tgordon Date 2008-01-28 Time 13:38 Rev Time 0.30
Received By tgordon Date 2008-01-28 Time 13:38 Sent To  
Notes
2008-01-28 13:54:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE A-2 SHOWS ONE NEW SUPPLY AND RETURN AIR
 GRILL. PLEASE SHOW ON PLAN ALL NEW GRILL SIZES, DUCT
 (FLEX) SIZES AND CFM'S AT NEW SUPPLY AIR GRILLS. SEE
 2004 FBC 106.3.5.
  
 2) THE RESTROOMS REQUIRE EXHAUST FANS, SEE 2004 FBC/M
 403.2. PLEASE CORRECT, AND LIST AS NEW OR EXISTING.
  
 3) PLEASE ADD OUTSIDE AIR CALCULATIONS TO PLANS AND
 PROVIDE OUTSIDE AIR TO SPACE, SEE 2004 FBC/M 401.2.
  
 4) PLEASE SHOW ALL MECHANICAL WORK TO BE DONE AND LIST
 AS NEW OR EXISTING, SEE 2004 FBC 106.3.5.
  
 5) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-08-04 Cont ID  
Sent By kstevens Date 2008-08-04 Time 15:23 Rev Time 0.00
Received By kstevens Date 2008-08-04 Time 15:23 Sent To  
Notes
2008-08-04 15:24:36REVISION OK--SHT PB-1.0--ADDED GREASE LINE &
 GREASE INTERCEPTOR.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-07-16 Cont ID  
Sent By kstevens Date 2008-07-16 Time 13:49 Rev Time 0.00
Received By kstevens Date 2008-07-14 Time 14:02 Sent To  
Notes
2008-07-16 13:52:36 
  
 PASSED/PROVISO
  
 A GREASE INTERCEPTOR IS REQUIRED FOR ALL FIXTURES
 EXCEPT THE TOILET ROOMS, WASH MACHINE AND EXISTING HAND
 SINK. ARTICLE III SECTION 90-124(7).A REVISION IS
 REQUIRED SHOWING THE GREASE INTERCEPTOR, (750 GAL), AND
 THE GREASE SYSTEM AS WELL AS THE RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-28 Cont ID  
Sent By kstevens Date 2008-04-28 Time 12:36 Rev Time 0.00
Received By kstevens Date 2008-04-28 Time 12:36 Sent To  
Notes
2008-04-28 12:43:38DENIED
 REFERENCE: FBC-2004
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS.
 ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED.
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS
 PLUS SECTION 11-4.3.1(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED.
  
 7. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE SANITARY AND
 WATER AS WELL AS A PLAN VIEW OF EACH SYSTEM PIPING PER
 SECTION 106.3.5.1.3(3)(4)(6)(10)(13). SHOW ALL PIPE
 SIZES, TRAPS & VENTS FOR THE SANITARY SYSTEM, AND ALL
 THE PIPE SIZES, VALVES & WATER HAMMER ARRESTORS, (WHERE
 REQUIRED BY SECTION 604.9), FOR THE WATER SYSTEM.
 ****NO COMMENT RESPONSE, COMMENT NOT ADDRESSED FOR THE
 WATER RISER DIAGRAM.
  
 8. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGHAN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
 SECTION 802.1.1.
 ****NO COMMENT RESPONSE, AND THE FLOOR SINKS ON THE
 RISER DIAGRAM DO NOT RELFECT THE FLOOR DRAINS SHOWN ON
 THE FLOOR PLAN. PLEASE SHOW THE FLOOR SINKS ON THE
 FLOOR PLAN.--ALSO THE 2" FLOOR SINK P-009 SHOWN ON
 THE SANITARY RISER DIAGRAM IS NOT INDICATED ON THE
 FLOOR PLAN. PLEASE CORRELATE RISER & FLOOR PLAN.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE TO THE TRANSMITTAL LETTER WITH A
 COMMENT RESPONSE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-12 Cont ID  
Sent By kstevens Date 2008-02-12 Time 15:40 Rev Time 0.00
Received By kstevens Date 2008-02-12 Time 15:39 Sent To  
Notes
2008-02-12 17:24:22DENIED
 REFERENCE: FBC-2004
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THAT THE PLANS HAVE BEEN DESIGNED TO THE
 CURRENT CODE, FBC-2004 W/2007 REVISIONS. PLANS SHALL BE
 DESIGNED TO CODES IN EFFECT. SECTION 110.2
  
 2. PLANS SHALL BE SIGNED, SEALED & DATED AS REQUIRED
 PER FS 481.221
  
 3. INFORMATION IS MISSING FOR THE TITLE BLOCKS OF EACH
 SHEET AS REQUIRED BY FAC 61G1-16.004 & FS 481.219,
 481.2055.
  
 4. SUITE, UNIT OR SPACE NUMBER REQUIRED IN THE TITLE
 BLOCK INFORMATION FOR THE ADDRESS. SECTION 106.1.2.
  
 5. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11-4.22
 WITH ALL SUBSECTIONS.
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS
 PLUS SECTION 11-4.3.1(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
  
 7. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE SANITARY AND
 WATER AS WELL AS A PLAN VIEW OF EACH SYSTEM PIPING PER
 SECTION 106.3.5.1.3(3)(4)(6)(10)(13). SHOW ALL PIPE
 SIZES, TRAPS & VENTS FOR THE SANITARY SYSTEM, AND ALL
 THE PIPE SIZES, VALVES & WATER HAMMER ARRESTORS, (WHERE
 REQUIRED BY SECTION 604.9), FOR THE WATER SYSTEM.
  
 8. EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGHAN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
 SECTION 802.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-18 Cont ID  
Sent By choops Date 2008-06-18 Time 10:40 Rev Time 0.00
Received By choops Date 2008-06-18 Time 10:40 Sent To  
Notes
2008-06-18 10:41:05*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.