Plan Review Details - Permit 08010333
Plan Review Stops For Permit 08010333
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By jgomez Date 2008-01-31 Time 16:58 Rev Time 0.00
Received By jgomez Date 2008-01-31 Time 16:58 Sent To PC
Notes
2008-01-31 17:00:33RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW
 UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. IT WAS UPDATED TO $6,274AS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTSTO FBC 2004.OWES $77.43
 FOR UPDATED PERMIT VALUATION AND RADON FEES.
  
 2-PLEASE COORDINATEWITH ZONING TO SEE IF PROPOSED
 PORCH MEETS THE REQUIRED SETBACKS.
  
 3- PROVIDE COMPLETE SET OF CONSTRUCTION DRAWINGS
 SHOWING ALL THE DESIGN CRITERIA REQUIRED BY SEC. R301.1
 OF 2004 FLORIDA RESIDENTIAL CODE.NEED TO SPECIFY ALL
 LIVE LOADS, DEAD LOADS, WIND LOADS AND UPLIFT LOADS.
 PROVIDECOMPLETE FOUNDATION PLAN,FLOOR PLAN AND ROOF
 FRAMING PLAN. SPECIFY ALLSTRUCTURAL MEMBERS SIZES AND
 CONNECTIONS.
  
 4- PERSON RESPONSIBLE FOR THE DESIGNNEEDS TO PROVIDE
 NAME AND SIGNATURE IN ALL DRAWINGS.IF ARCHITECT OR
 ENGINEER IS RESPONSIBLE FOR THE DESIGN, THENSIGN AND
 SEAL DRAWINGS AS REQUIRED BY CHAPTER 481 AND 471
 RESPECTIVELY. SEC. 106.1 CITY AMENDMENTS TO FBC 2004.
  
 5- SPECIFY ROOF PITCH TO VERIFY COMPLIANCE WITH SLOPE
 REQUIRED FOR ROOF SHINGLES SEC. R905.2.2 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 6- SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE
 FOR MINIMUMTYPE AND SPACING OF NAIL REQUIRED FOR ROOF
 SHEATHING INSTALLATION. INCLUDING ON ROOF ZONE 3.
  
 7- SPECIFY ATTACHMENT OF PROPOSED PORCH TO EXISTING
 STRUCTURE TO VERIFY COMPLIANCE WITHTHE CALCULATED
 WIND LOADS AS REQUIRED BY SEC. R301.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 NOTE:TAKE INTO CONSIDERATION THAT THIS IS A MOBILE
 HOME AND PROPOSED PORCH WILL AFFECT THE STRUCTURAL
 STABILITY OF THE MAIN HOUSE.
  
 8- PROVIDE PRODUCT APPROVAL(2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES.
  
 B) ALL STRUCTURALCONNECTORS (SIMPSON OR USP)
 SPECIFIED ON PLANS AND DETAILS.
  
 9- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING(NOT SIGNING AND SEALING)BY THE
 DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-31 Cont ID  
Sent By jgomez Date 2008-01-31 Time 17:02 Rev Time 0.00
Received By jgomez Date 2008-01-17 Time 08:58 Sent To  
Notes
2008-01-17 08:59:45TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-23 Cont ID  
Sent By choops Date 2008-01-23 Time 13:57 Rev Time 0.00
Received By choops Date 2008-01-23 Time 13:57 Sent To B
Notes
2008-01-23 13:58:51***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED PORCH.INCLUDE
 ALL DIMENSIONS AND SETBACK DIMENSIONS TO THE PROPERTY
 LINES.
  
 NOTE:MUST MAINTAIN A MINIMUM FRONT SETBACK OF 25'
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - MISC. 2