Plan Review Details - Permit 08010311
Plan Review Stops For Permit 08010311
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-22 Cont ID  
Sent By jwitmer Date 2008-04-22 Time 07:59 Rev Time 0.77
Received By jwitmer Date 2008-04-22 Time 07:59 Sent To  
Notes
2008-04-22 08:01:07BUILDING PLAN REVIEW
 PERMIT: 08010311
 ADD: 1335 OKEECHOBEE RD SUITE# 1000
 CONT: PCF CONSTRUCTION
 TEL: (561)346-8281
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 NOTE NOT ONE COMMENT WAS ADDRESSED!!!
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS PLEASE INDICATE AS
 SUCH.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) 2004 FL BUILDING CODE, EXISTING BUILDING, ADDING A
 MEZANINE CONSTITUTES AN ADDITION SEE ASSOCIATED
 CHAPTERFOR ADDITIONS.
 C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION (FOR THE EXISTING BUILDING)
 AS DEFINEDIN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED, (AREA
 INCREASES).
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) ) NUMBER OF UNITS
 I ) NUMBER OF FLOORS
 J ) SQ. FT.OF BUILDING / PER FL
 J ) SQ. FT. FOOTPRINT
  
 3)UNTIL USE AND OCCUPANCY IS PROVIDED, VERTICAL
 ACCESSIBILITY MAY OR MAY NOT BE A ISSUE THAT MAY NEED
 TO BE ADDRESSED.11-4.1.6(1)(K)(III).
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ON REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE
 NOT PART OF THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-26 Cont ID  
Sent By jwitmer Date 2008-01-26 Time 14:41 Rev Time 1.33
Received By jwitmer Date 2008-01-26 Time 14:41 Sent To  
Notes
2008-01-26 14:55:18BUILDING PLAN REVIEW
 PERMIT: 08010311
 ADD: 1335 OKEECHOBEE RD SUITE# 1000
 CONT: PCF CONSTRUCTION
 TEL: (561)346-8281
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS PLEASE INDICATE AS
 SUCH.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) 2004 FL BUILDING CODE, EXISTING BUILDING, ADDING A
 MEZANINE CONSTITUTES AN ADDITION SEE ASSOCIATED
 CHAPTERFOR ADDITIONS.
 C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION (FOR THE EXISTING BUILDING)
 AS DEFINED IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED, (AREA
 INCREASES).
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) ) NUMBER OF UNITS
 I ) NUMBER OF FLOORS
 J ) SQ. FT.OF BUILDING / PER FL
 J ) SQ. FT. FOOTPRINT
  
 3) UNTIL USE AND OCCUPANCY IS PROVIDED, VERTICAL
 ACCESSIBILITY MAY OR MAY NOT BE A ISSUE THAT MAY NEED
 TO BE ADDRESSED.11-4.1.6(1)(K)(III).
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NOTE: A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ON REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE
 NOT PART OF THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-03 Cont ID  
Sent By dpalmer Date 2008-04-03 Time 15:02 Rev Time 0.00
Received By dpalmer Date 2008-04-03 Time 15:02 Sent To  
Notes
2008-04-03 15:03:00** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AS
 THE SAME COMMENTS APPLY.
 IF AN OCCUPANT ON THE MEZZANINE LEVEL AND LIGHTS TURN
 OFF, HOW WILL THE OCCUPANT HAVE CONTROLS FOR EGRESS
 LIGHTING FOR MINIMUM LIGHTING LEVELS?
 PLEASE SEE THE NOTES AS PREVIOUSLY MENTIONED STILL
 APPLY. MAY NOT ADD NEW MEZZANINE LEVEL WITHOUT
 ADDRESSING THE MINIMUM FOR LIFE SAFETY CODE ALONG WITH
 OTHER CODES AS NOTED PREVIOUSLY.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-28 Cont ID  
Sent By dpalmer Date 2008-01-28 Time 09:50 Rev Time 0.00
Received By dpalmer Date 2008-01-28 Time 09:50 Sent To  
Notes
2008-01-28 09:50:50** DENIEDREVIEW **
  
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE
 PLACED ON ELECTRICAL PLANS FOR RELEVANT DESIGN.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING ANY NEW
 ELECTRICAL LIGHTING AND WIRING METHODS REQUIRED FOR
 EGRESS.
 PLEASE SUBMIT PHOTO-METRICLEVELS FOR NEW EGRESS PATHS
 AND AREAS. PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2.
 PLEASE SEE FAC 61G15-33.004
 PLEASE SHOW OCCUPANCY OF MEZZ LEVEL AND LIGHTING.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 FOR LIGHTING CONTROLS REQUIRED.
 PLEASE SEE 13-415.2 FOR MAXIMUM LIGHTING PERFORMANCE
 CALCULATIONS.
  
 ** PLEASE KNOW AS THERE WAS NO ELECTRICAL PLANS, NO
 ELECTRICAL DETAILS ETC SUBMITTED FOR REVIEW THERE MAY
 VERY WELL BE NEW COMMENTS ON THE NEXT REVIEW. THERE ARE
 SEVERAL ITEMS WHICH COULD NOT BE REVIEWED AT THIS
 TIME.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-04-22 Cont ID  
Sent By mawillia Date 2008-04-22 Time 11:06 Rev Time 0.00
Received By mawillia Date 2008-04-22 Time 10:37 Sent To  
Notes
2008-04-22 11:06:01*****DENIED*****
  
 THE COMMENTS (NOT MARKED OK) FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.STRUCTURAL CALCULATION COVER SHEET AND MEZZANINE
 SHEET 1 STILL SHOW 100 AS THE SUITE NUMBER.SHOULD BE
 SUITE 1000
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 AS A GENERAL NOTE
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD
 AS A GENERAL NOTE
  
 4.OK
  
 5.OK
  
 6.OK
  
 7.HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE
 SPRINKLER AND FIRE ALARM DEVICES.SPRINKLERS ARE
 SHOWN, HOWEVER SPRINKLER PROTECTION NEEDED ABOVE AND
 BELOW THE MEZZANINE.PROVIDE A LAYOUT OF THE FIRE
 ALARM DEVICES IN THE SPACE INCLUDING THE PROPOSED
 MEZZANINE.
  
 8.OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-12 Cont ID  
Sent By mawillia Date 2008-02-12 Time 16:58 Rev Time 0.00
Received By mawillia Date 2008-02-12 Time 15:53 Sent To  
Notes
2008-02-12 16:52:15*****DENIED*****
  
  
 1. THE CORRECT SUITE NUMBER SHALL BE LISTED AS PART OF
 THE PROJECT SITE ADDRESS. PLEASE SEE THAT SUITE 100 AND
 SUITE 1000 ARE SHOWN ON THE SUBMITTED PLAN SHEETS AND
 STRUCTURAL CALCULATIONS DOCUMENTS. PLEASE
 RECTIFY.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4. PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED
 DURING THE SCOPE OF WORK. IF SO, MEANS OF EGRESS AND
 AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN
 PLACE AND CONTINUOUSLY MAINTAINED.
  
 5. PLEASE LIST THE FOLLOWING FOR THE BUILDING:
 OCCUPANCY TYPE, OCCUPANT LOAD, FIRE ALARM AND/OR FIRE
 SPRINKLER DEVICES, AND ANY OTHER PERTINENT
 INFORMATION.
  
 6. PLEASE PROVIDE A CLEAR REPRENSENTATION OF THE
 MEZZANINE IN RELATION TO THE FLOOR PLAN INCLUDING EXIT
 LIGHTS/DOORS, EMERGENCY LIGHTS, ETC.
  
 7. HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE
 SPRINKLER AND FIRE ALARM DEVICES.
  
 8. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-31 Cont ID  
Sent By adarroug Date 2008-03-31 Time 14:29 Rev Time 0.00
Received By adarroug Date 2008-03-31 Time 14:29 Sent To  
Notes
2008-03-31 14:31:44TO "COMM" BD#27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-24 Cont ID  
Sent By adarroug Date 2008-01-24 Time 13:18 Rev Time 0.00
Received By adarroug Date 2008-01-24 Time 13:18 Sent To  
Notes
2008-01-24 13:18:26TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-12 Cont ID  
Sent By mawillia Date 2008-02-12 Time 15:54 Rev Time 0.00
Received By mawillia Date 2008-01-15 Time 10:55 Sent To  
Notes
2008-01-15 10:58:59TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-01 Cont ID  
Sent By eschneid Date 2008-04-01 Time 09:04 Rev Time 0.00
Received By eschneid Date 2008-04-01 Time 09:04 Sent To  
Notes
2008-04-01 09:05:17APPROVED FOR 765 SQ. FT. STORAGE MEZZANINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-16 Cont ID  
Sent By eschneid Date 2008-01-16 Time 13:32 Rev Time 0.00
Received By eschneid Date 2008-01-16 Time 13:32 Sent To B
Notes
2008-01-16 13:36:12FAILED
  
 THE PLANS THAT LIST THE MEZZANINE SPECIFICATIONS
 SHALL:
  
 1) CLEARLY STATE THAT THE MEZZANINE IS FOR STORAGE
 ONLY.
  
 2) SHOW THE TOTAL MEZZANINE SQ. FT. (I.E. FINISH THE
 DIMENSION CALCULATION).
  
 CONTACT ERIC SCHNEIDER @ 822-1435.