Plan Review Details - Permit 08010262
Plan Review Stops For Permit 08010262
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-02-01 Cont ID  
Sent By mperson Date 2008-02-01 Time 13:24 Rev Time 0.00
Received By mperson Date 2008-02-01 Time 13:24 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-01-15 Cont ID  
Sent By mperson Date 2008-01-15 Time 14:08 Rev Time 0.00
Received By mperson Date 2008-01-15 Time 13:51 Sent To PC
Notes
2008-01-15 14:07:59PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS. PER FBC FUEL GAS CODE
 SECTION 401.1, SCOPE. **THE SUBMITTED DRAWING IS NOT AN
 ISOMETRIC.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 CODE SECTION 401.1, SCOPE. **THE SUBMITTED DRAWING IS
 NOT INDICATING THE PIPING MATERIAL BEING INSTALLED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). **THE SUBMITTED PLANS ARE NOT INDICATING THE
 BTU LOAD OF THE POOL HEATER. A GAS PLAN REVIEW CAN NOT
 BE DONE WITHOUT THIS INFORMATION.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. **A GAS PLAN
 REVIEW CAN NOT BE DONE WITHOUT THE DELIVERY PRESSURE
 BEING INDICATED ON THE PLANS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 15:37 Rev Time 0.00
Received By shill Date 2008-01-25 Time 15:37 Sent To G
Notes
2008-01-25 15:37:59TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-15 Cont ID  
Sent By mperson Date 2008-01-15 Time 14:08 Rev Time 0.00
Received By mperson Date 2008-01-11 Time 16:59 Sent To G
Notes
2008-01-11 16:59:51TO GAS BOX