Plan Review Details - Permit 08010206
Plan Review Stops For Permit 08010206
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-10-15 Cont ID  
Sent By shill Date 2008-10-15 Time 17:27 Rev Time 0.00
Received By shill Date 2008-10-15 Time 17:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-03-07 Cont ID  
Sent By shill Date 2008-03-07 Time 09:42 Rev Time 0.00
Received By shill Date 2008-03-07 Time 09:42 Sent To  
Notes
2008-03-07 09:43:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST, SAME PLANS SUBMITTED:
  
 1.THERE ARE TWO DETAILS FOR THE SLAB.ONE IS FOR A
 FORMED AND POURED SLAB (PREPARED BY AN ENGINEER).THE
 OTHER SPECIFIES A PRECAST SLAB, WHICH IS REQUIRED TO BE
 ENGINEERED BUT IS NOT.PLEASE CLARIFY; SUBMIT ONLY ONE
 DETAIL.IF YOU ARE USING A PREFAB SLAB, SUBMIT TWO
 ORIGINAL SETS OF ENGINEERING.
  
 2.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. FS471.
  
 **CALLED CONTRACTOR'S OFFICE 3/7/8**

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-07 Cont ID  
Sent By shill Date 2008-02-07 Time 16:47 Rev Time 0.00
Received By shill Date 2008-02-07 Time 16:47 Sent To  
Notes
2008-02-07 16:49:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST, SAME PLANS SUBMITTED:
  
 1.THERE ARE TWO DETAILS FOR THE SLAB.ONE IS FOR A
 FORMED AND POURED SLAB (PREPARED BY AN ENGINEER).THE
 OTHER SPECIFIES A PRECAST SLAB, WHICH IS REQUIRED TO BE
 ENGINEERED BUT IS NOT.PLEASE CLARIFY; SUBMIT ONLY ONE
 DETAIL.IF YOU ARE USING A PREFAB SLAB, SUBMIT TWO
 ORIGINAL SETS OF ENGINEERING.
  
 2.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. FS471.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-29 Cont ID  
Sent By shill Date 2008-01-29 Time 16:51 Rev Time 0.00
Received By shill Date 2008-01-29 Time 16:51 Sent To  
Notes
2008-01-29 16:54:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THERE ARE TWO DETAILS FOR THE SLAB.ONE IS FOR A
 FORMED AND POURED SLAB (PREPARED BY AN ENGINEER).THE
 OTHER SPECIFIES A PRECAST SLAB, WHICH IS REQUIRED TO BE
 ENGINEERED BUT IS NOT.PLEASE CLARIFY; SUBMIT ONLY ONE
 DETAIL.IF YOU ARE USING A PREFAB SLAB, SUBMIT TWO
 ORIGINAL SETS OF ENGINEERING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-01-23 Cont ID  
Sent By jleahy Date 2008-01-23 Time 16:30 Rev Time 1.30
Received By jleahy Date 2008-01-23 Time 16:30 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-01-24 Cont ID  
Sent By jleahy Date 2008-01-24 Time 07:10 Rev Time 1.50
Received By jleahy Date 2008-01-24 Time 07:10 Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By mgonzale Date 2008-12-03 Time 14:13 Rev Time 1.00
Received By mgonzale Date 2008-12-03 Time 14:11 Sent To  
Notes
2008-12-03 14:13:40PASSED - NO CONFLICTS WITH UTILITIES (WATER, GRAVITY
 SEWER AND SEWER FORCEMAINS)
 CALL 811 FOR LOCATES. IT'S THE LAW CHAPTER 556 FLA
  
 MANNY GONZALEZ
 ENGINEERING SERVICES
 (561) 494-1085

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-12-03 Cont ID  
Sent By lwagner Date 2008-12-03 Time 13:35 Rev Time 0.00
Received By lwagner Date 2008-12-03 Time 13:32 Sent To ENG
Notes
2008-12-03 13:36:33REVISION OK

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-02-29 Cont ID  
Sent By mperson Date 2008-02-29 Time 10:44 Rev Time 0.00
Received By mperson Date 2008-02-29 Time 10:44 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-02-06 Cont ID  
Sent By mperson Date 2008-02-06 Time 13:26 Rev Time 0.00
Received By mperson Date 2008-02-06 Time 13:26 Sent To B
Notes
2008-02-06 13:34:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 NOTE: THERE ARE STILL COMMENTS FROM THE PREVIOUS GAS
 PLAN REVIEW THAT STILL NEED TO BE ADDRESSED.
  
 1. **OK, COMMENT ADDRESSED**
  
 2. **OK, COMMENT ADDRESSED**
  
 3. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED**
 SUBMIT TWO COPIES OF A SURVEY OR SITE PLAN CLEARLY
 INDICATING THE LOCATION OF THE PROPOSED GENERATOR
 INDICATING ALL DIMENSIONS FROM PROPERTY LINES AND
 STRUCTURES.
  
 4. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED**
 SUBMIT TWO COPIES OF MANUFACTURER'S SETBACK
 RECOMMENDATIONS FROM STRUCTURES. PER SECTION 401.1,
 SCOPE
  
 5. **NO COMMENT RESPONSE, COMMENT NOT ADDRESSED**
 THE GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/COM
 PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE
 GENERATOR LOCATION. **ZONING FAILED 1/14/08 AND
 2/04/08.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-01-15 Cont ID  
Sent By mperson Date 2008-01-15 Time 16:40 Rev Time 0.00
Received By mperson Date 2008-01-15 Time 08:14 Sent To E
Notes
2008-01-14 16:58:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET GAS ISOMETRIC: THE INDICATED BTU LOAD OF
 225,000 FOR PROPOSED GENERATOR IS WRONG. PER THE
 SUBMITTED MANUFACTURER'S SPECIFICATIONS THE CORRECT BTU
 LOAD FOR THE GENERATOR IS 437,000. PLEASE CORRECT PER
 SECTION *401.1, SCOPE.
  
 2. SHEET GAS ISOMETRIC: THE INDICATED PIPE SIZE OF
 3/4" FOR THE PROPOSED GENERATOR IS WRONG. THE CORRECT
 PIPE SIZE FOR THE PROPOSED GENERATOR WITH A BTU LOAD OF
 437,000 AND A LONGEST LENGTH OF 15' IS 1". PLEASE
 CORRECT PER TABLE *402.4(2), SCOPE.
  
 3. SUBMIT TWO COPIES OF A SURVEY OR SITE PLAN CLEARLY
 INDICATING THE LOCATION OF THE PROPOSED GENERATOR
 INDICATING ALL DIMENSIONS FROM PROPERTY LINES AND
 STRUCTURES.
  
 4. SUBMIT TWO COPIES OF MANUFACTURER'S SETBACK
 RECOMMENDATIONS FROM STRUCTURES. PER SECTION 401.1,
 SCOPE
  
 5. THE GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/COM
 PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE
 GENERATOR LOCATION. **ZONING FAILED 1/14/08.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-12 Cont ID  
Sent By adarroug Date 2008-11-12 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-11-12 Time 16:40 Sent To Z
Notes
2008-11-12 16:41:01TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 11:57 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 11:57 Sent To Z
Notes
2008-10-02 11:59:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 08:59 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 08:59 Sent To Z
Notes
2008-02-21 09:00:01TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 16:14 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 16:14 Sent To Z
Notes
2008-02-01 16:14:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-29 Cont ID  
Sent By shill Date 2008-01-29 Time 16:54 Rev Time 0.00
Received By shill Date 2008-01-10 Time   Sent To Z
Notes
2008-01-10 09:04:07TO ZONING BOX

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-10-06 Cont ID  
Sent By rkussner Date 2008-10-06 Time 09:16 Rev Time 0.00
Received By rkussner Date 2008-10-06 Time 09:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-22 Cont ID  
Sent By tgordon Date 2008-02-22 Time 11:40 Rev Time 0.20
Received By tgordon Date 2008-02-22 Time 11:40 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-04 Cont ID  
Sent By tgordon Date 2008-02-04 Time 13:32 Rev Time 0.30
Received By tgordon Date 2008-02-04 Time 13:32 Sent To B
Notes
2008-02-04 13:35:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 1-16-08, PLEASE SHOW ON
 SURVEYS THE PROPOSED LOCATION OF THE GENERATOR AND THE
 DIMENSIONS TO STRUCTURES AND BUILDING OPENINGS. SEE
 NFPA 37 - 4.1.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-16 Cont ID  
Sent By tgordon Date 2008-01-16 Time 11:10 Rev Time 0.20
Received By tgordon Date 2008-01-16 Time 11:10 Sent To E
Notes
2008-01-16 11:19:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT TWO COPIES OF A SURVEY OR SITE PLAN
 SHOWING THE PROPOSED LOCATION OF THE GENERATOR AND THE
 DIMENSIONS TO STRUCTURES AND BUILDING OPENINGS. SEE
 NFPA 37 - 4.1.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2008-11-25 Cont ID  
Sent By lfranco Date 2008-11-25 Time 20:07 Rev Time 0.00
Received By lfranco Date 2008-11-25 Time 20:07 Sent To  
Notes
2008-11-25 20:09:06PLANNING AND ZONING: **** PASSED WITH PROVISO ***
  
 LOCATION OF GENERATOR SHALL BE AS APPROVED AND SHOWN IN
 MINOR AMENDMENT PB993IIII ON 9/24/08
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-10-06 Cont ID  
Sent By mcruz Date 2008-10-06 Time 14:52 Rev Time 0.00
Received By mcruz Date 2008-10-06 Time 14:52 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2008-02-21 Cont ID  
Sent By choops Date 2008-02-21 Time 13:31 Rev Time 0.00
Received By choops Date 2008-02-21 Time 13:31 Sent To M
Notes
2008-02-21 13:32:07***FAILED - RESUB #2***
  
  
 REPEAT COMMENT:
  
 1)PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A
 MINOR AMENDMENT TO THE PLANNED DEVELOPMENT SHALL BE
 SUBMITTED TO AND APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-04 Cont ID  
Sent By choops Date 2008-02-04 Time 11:35 Rev Time 0.00
Received By choops Date 2008-02-04 Time 11:35 Sent To M
Notes
2008-02-04 11:36:25***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A
 MINOR AMENDMENT TO THE PLANNED DEVELOPMENT SHALL BE
 SUBMITTED TO AND APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status P Date 2008-12-03 Cont ID  
Sent By shill Date 2008-01-29 Time 16:54 Rev Time 0.00
Received By choops Date 2008-01-14 Time 10:49 Sent To ENG
Notes
2008-01-14 10:49:48***FAILED***
  
  
 1)PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A
 MINOR AMENDMENT TO THE PLANNED DEVELOPMENT SHALL BE
 SUBMITTED TO AND APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - GEN. BOX