Plan Review Details - Permit 08010202
Plan Review Stops For Permit 08010202
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-25 Cont ID  
Sent By mwennerg Date 2008-01-25 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2008-01-25 Time 15:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By mwennerg Date 2008-01-18 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2008-01-18 Time 10:24 Sent To  
Notes
2008-01-18 10:30:56***DENIED***
  
 1) PLEASE ILLUSTRATE THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION. KNOX LOCKING CAPS SHALL BE
 REQUIRED.
  
 2) PLEASE SHOW THE DOUBLE DETECTOR CHECK ASSEMBY OR
 APPROVED METHOD THAT PREVENTS SYSTEM WATER FROM
 CONTAMINATING THE CITY SUPPLY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 11:56 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 11:56 Sent To FIRE
Notes
2008-01-23 11:56:59TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-18 Cont ID  
Sent By mwennerg Date 2008-01-18 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2008-01-10 Time 08:27 Sent To FIRE
Notes
2008-01-10 08:28:08TO FIRE BOX